Specifications

ELECTRICAL DATA ASYG07LMCE ASYG09LMCE
INDOOR UNIT Model ASYG07LMCE ASYG09LMCE
OUTDOOR UNIT AOYG07LMCE AOYG09LMCE
Cooling POWER SOURCE 230 V 50 Hz Single phase
CAPACITY 2.00 kW 2.50 kW
POWER CONSUMPTION 0.465 kW 0.65 kW
EER 4.30 kW/kW 3.85 kW/kW
RUNNING CURRENT 2.5 A 3.2 A
MAXIMUM CURRENT 6.0 A 6.0 A
MOISTURE REMOVAL 1.0 L/h 1.3 L/h
Heating CAPACITY 3.00 kW 3.20 kW
POWER CONSUMPTION 0.685 kW 0.73 kW
COP 4.38 kW/kW 4.38 kW/kW
RUNNING CURRENT 3.3 A 3.5 A
MAXIMUM CURRENT 7.5 A 7.5 A

Dimensions

Unit Dimensions (H x W x D)
INDOOR UNIT 270 x 870 x 204 mm
OUTDOOR UNIT 535 x 663 x 293 mm

Weight

Unit Net / Shipping
INDOOR UNIT 8.5 kg / 11 kg
OUTDOOR UNIT 21 kg / 25 kg

Fan Motor and Fan Revolution

INDOOR UNITS Discrimination MFD-12CYBL
OUTDOOR UNITS Discrimination MFE-22AVAL
INDOOR UNIT Cooling High 1,320 rpm
Medium 1,160 rpm
Low 930 rpm
Quiet 680 rpm
INDOOR UNIT Heating High 1,320 rpm
Medium 1,160 rpm
Low 980 rpm
Quiet 710 rpm
OUTDOOR UNIT Cooling High 730 rpm
Heating 650 rpm

Airflow

INDOOR UNIT Cooling
High 750 m³/h
Medium 640 m³/h
Low 480 m³/h
Quiet 310 m³/h
INDOOR UNIT Heating High 750 m³/h
Medium 640 m³/h
Low 520 m³/h
Quiet 330 m³/h
OUTDOOR UNIT Cooling High 1,670 m³/h
Heating 1,470 m³/h

Noise Level

High Medium Low Quiet
INDOOR UNIT Cooling 43 dB 40 dB 32 dB 21 dB
INDOOR UNIT Heating 43 dB 38 dB 33 dB 22 dB
OUTDOOR UNIT Cooling 45 dB
Heating 45 dB

Compressor and Refrigerant

COMPRESSOR TYPE Hermetic type, 4 pole, 3 phase, DC inverter motor, Rotary
DISCRIMINATION 5SS072XHA01
WEIGHT (with oil) 6.0 kg
PRECHARGED REFRIGERANT 700 g
REFRIGERANT TYPE R410A
FULL CHARGE Pipe length 15 m 700 g
20 m 800 g
ADDITIONAL CHARGE 20 g/m
MAXIMUM PIPING HEIGHT 15 m

Refrigerant System Diagram

Diagram illustrating the flow of refrigerant through the compressor, heat exchangers, valves, and strainers. Arrows indicate refrigerant direction for cooling and heating. Pipe diameters are specified for liquid (1/4") and gas (3/8").

Circuit Diagram

Detailed circuit diagram for both the indoor and outdoor units, showing connections between the Main PCB, Indicator PCB, Fan Motor, Louver, Thermistors, Compressor, Expansion Valve Coil, and 4-way Valve Coil. Includes wire colors and terminal designations.

PCB Circuit Diagram

Schematic of the Printed Circuit Board (PCB) layout for the control unit, main PCB, indicator PCB, and fan motor. Includes thermistor characteristics and terminal functions.

Error Detection

If a wireless remote control is used, error codes are indicated by blinking patterns on the photo detector unit's lamp. For wired remote controls, error codes appear on the display. The table below lists operation indicators (green and orange lamps) and their corresponding error codes and descriptions.

OPERATION lamp (green) TIMER lamp (orange) ECONOMY lamp (green) Wired remote controller Error code Description
(1) (1) 11 Serial communication error
(1) (2) 12 Wired remote controller communication error
(1) (5) 15 Check run unfinished
(2) (1) 21 Unit number or Refrigerant circuit address setting error [Simultaneous Multi]
(2) (2) 22 Indoor unit capacity error
(2) (3) 23 Combination error
(2) (4) 24 Connection unit number error (indoor unit or branch unit) [Flexible Multi]
(2) (7) 27 Master unit, slave unit set-up error [Simultaneous Multi]
(3) (2) 32 Indoor unit PCB model information error
(3) (5) 35 Manual auto switch error
(4) (1) 41 Room temp. sensor error
(4) (2) 42 Indoor unit Heat Ex. Middle temp. sensor error
(5) (1) 51 Indoor unit fan motor error
(5) (3) 53 Drain pump error
(5) (7) 57 Damper error
(5) (8) 58 Intake grille error
(6) (2) 62 Outdoor unit main PCB model information error or communication error [Flexible Multi]
(6) (3) 63 Inverter error
(6) (4) 64 Active filter error, PFC circuit error
(6) (5) 65 Trip terminal L error
(6) (10) 6A Display PCB microcomputers communication error
(7) (1) 71 Discharge temp. sensor error
(7) (2) 72 Compressor temp. sensor error
(7) (3) 73 Outdoor unit Heat Ex. liquid temp. sensor error
(7) (4) 74 Outdoor temp. sensor error
(7) (5) 75 Suction Gas temp. sensor error
(7) (6) 76 2-way valve temp. sensor error / 3-way valve temp. sensor error
(7) (7) 77 Connection unit number error (indoor slave unit)
(8) (2) 82 Sub-cool Heat Ex. gas inlet temp. sensor error
(8) (3) 83 Sub-cool Heat Ex. gas outlet temp. sensor error
(8) (4) 84 Liquid pipe temp. sensor error
(8) (6) 86 Current sensor error
(9) (4) 94 Trip detection
(9) (5) 95 Compressor rotor position detection error
(9) (7) 97 Outdoor unit fan motor error
(9) (9) 99 4-way valve error
(10) (1) A1 Discharge temp. error
(10) (3) A3 Compressor temp. error
(10) (4) A4 High pressure error
(10) (5) A5 Low pressure error
(13) (2) 12 Branch boxes error [Flexible Multi]

Troubleshooting with the Wired Remote Control Display (Option): If an error occurs, the following display will be shown. ("Er" will appear in the set room temperature display.)

Error display example: 00:11 Er

Display mode: 0.5s ON / 0.5s OFF

Error code blinking: 0.1s ON / 0.1s OFF

(): Number of flashing

Parts - Indoor Unit

The following tables and diagrams detail the parts for the Indoor Unit (ASYG07LMCE, ASYG09LMCE).

Ref. Description Part number
1 Remote Control 9319208008
2 Remote Control Holder 9318912005
3 Bracket Panel 9332882025
4 Electric Filter Holder 9332911008
5 Air Clean Filter Assy 9317250009
6 Air Filter 9332875010
7 Screw Cap 9309002074
11 Wire Cover 9333504018
12 Louver Assy 9333353043
13 Diffuser Assy 9332998085
14 Front Panel Sub Assy (FUJITSU) 9333525051
21 Intake Grille Assy 9333526010
22 Front Panel C 9333497020
23 Under Cover 9333503011
24 Front Panel Cover R 9333502014
25 Front Panel R 9333500003
26 Front Panel Cover L 9333501017
27 Front Panel L 9333499000
31 Control Box 9332892000
32 Main PCB (ASYG07LMCE) 9709427033
32 Main PCB (ASYG09LMCE) 9709427019
33 Terminal 9900720001
34 Display Assy 9709430019
35 Room Thermistor Holder 9332868005
- Thermistor Assy 9900930011
41 Evaporator Total Assy 9332989090
42 Fan Motor 9603269005
43 Crossflow Fan Assy 9316830004
44 Bearing C Assy 9306628017
45 Casing Assy 9333009001
51 Casing 9332890006
52 Casing Cover F 9332909005
53 Casing Cover B 9332908008
54 R and L Louver 9332891003
55 Fan Guard 9332905007
56 Drain Cap 9316177017
57 Drain Hose Assy 9316904002
61 Motor Holder L/R 9332859003
62 Cable Guide 9332903003
63 Step Motor 9900790004
64 Step Motor 9900790011

Parts - Outdoor Unit

The following tables and diagrams detail the parts for the Outdoor Unit (AOYG07LMCE, AOYG09LMCE).

Ref. Description Part number
1 Protective Net 9332855005
2 Thermistor Holder 9332505009
3 Top Panel Assy 9332977004
4 Front Panel Assy 9332965001
5 Cabinet Left Assy 9332962000
6 Emblem 9319151007
7 Cabinet Right Assy 9332963007
8 Switch Cover A Assy 9332964011
9 Switch Cover B 9332843002
10 Fan Motor 9603074043
11 Propeller Fan 9309909014
12 Drain Assy 9332574005
13 Motor Bracket Assy 9332583021
21 Reactor Assy (AOYG07LMCE) 9900872014
21 Reactor Assy (AOYG09LMCE) 9900787028
22 PCB Holder 9332506013
23 Main PCB with Terminal (07) 9709434147
23 Main PCB with Terminal (09) 9709434031
24 Heat Sink B 9332522006
- Thermistor Assy 9900901011
- Thermistor 9900880019
31 Condenser Total Assy 9332924008
32 Compressor Assy 9317083034
33 Solenoid 9970079030
34 4-way Valve Assy 9333012001
35 Expansion Valve Coil 9970137013
36 Pulse Motor Valve Sub Assy 9333023007

Accessories

The following are accessories for the Indoor and Outdoor Units.

INDOOR UNIT Name and Shape Part number Name and Shape Part number OUTDOOR UNIT Name and Shape Part number
Bracket Panel 9332882025 Cloth tape 9310519004 Drain pipe assy 9332574005
Remote Control 9319208008 Tapping screw (M4 x 25 mm) 0700076046
Remote Control Holder 9318912005 Tapping screw (M3 x 12 mm) 0700019036
Battery (penlight) 0600185541 Air cleaning filter assy 9317250009
Filter holder 9332911008
Models: ASYG07LMCE, AOYG07LMCE, ASYG09LMCE, AOYG09LMCE, ASYG07LMCE Split Type Room Air Conditioner Wall Mounted, Split Type Room Air Conditioner Wall Mounted, Room Air Conditioner Wall Mounted, Air Conditioner Wall Mounted, Conditioner Wall Mounted, Wall Mounted, Mounted

File Info : application/pdf, 21 Pages, 3.58MB

PDF preview unavailable. Download the PDF instead.

asyg07lmce-aoyg07lmce-asyg09lmce-aoyg09lmce-service-manual compr PDF reDirect v2 iLovePDF

Related Documents

Preview Fujitsu ASYA18LEC / AOYR18LEC Split Type Room Air Conditioner Service Manual
This service manual provides detailed specifications, diagrams, error codes, and parts lists for the Fujitsu ASYA18LEC indoor unit and AOYR18LEC outdoor unit, split-type room air conditioners.
Preview Fujitsu Split Type Room Air Conditioner Service Manual
Service manual for Fujitsu Split Type Room Air Conditioner, Wall Mounted Type, covering models ASU9RLF, ASU12RLF, ASU15RLS and AOU9RLFW, AOU12RLFW, AOU15RLS. Includes specifications, dimensions, refrigerant system diagram, circuit diagrams, error detection, parts lists, and accessories.
Preview Fujitsu Split Type Room Air Conditioner Service Manual - ABY45RBA3W, AOY45RPA3L
Comprehensive service manual for Fujitsu Split Type Room Air Conditioner, Ceiling type (50Hz), models ABY45RBA3W and AOY45RPA3L. Covers specifications, diagrams, error codes, disassembly procedures, parts lists, and standard accessories.
Preview Fujitsu Split Type Room Air Conditioner Service Manual
Comprehensive service manual for Fujitsu split type room air conditioners, covering models ASYA14LCC, AOYR14LCC, ASYA14LCL, ASYA18LCC, AOYR18LCC, and AOYR18LCL. Includes specifications, diagrams, error codes, and parts lists.
Preview Fujitsu Split Type Room Air Conditioner Wall Mounted Type Service Manual
This service manual provides detailed specifications, diagrams, error contents, parts lists, and accessories for Fujitsu Split Type Room Air Conditioners, Wall Mounted Type, including models ASYA07LGC, ASYA09LGC, ASYA12LGC, AOYR07LGC, AOYR09LGC, and AOYR12LGC.
Preview Fujitsu ASYG14LMCA / AOYG14LMCA Split Type Room Air Conditioner Service Manual
Comprehensive service manual for the Fujitsu ASYG14LMCA and AOYG14LMCA split type wall-mounted room air conditioners, covering specifications, diagrams, error detection, and parts.
Preview Fujitsu Inverter Multi Air Conditioner Service Manual
Comprehensive service manual for Fujitsu Inverter Multi Air Conditioners, Wall Mounted Type, covering indoor and outdoor units, specifications, diagrams, error codes, and parts.
Preview Fujitsu Split Type Room Air Conditioner Service Manual - ASY9USCCW, AOY9USCC, ASY9USCCW, AOY9UFCC, ASY12USCCW, AOY12USCC
This service manual provides detailed specifications, diagrams, error codes, disassembly instructions, and parts lists for Fujitsu Split Type Room Air Conditioners, Wall Mounted models ASY9USCCW, AOY9USCC, ASY9USCCW, AOY9UFCC, ASY12USCCW, and AOY12USCC.