AAON VCC-X EM1 Expansion Module ASM01691
Stay in control with customizable control solutions. AAON offers a wide range of control solutions to optimally regulate and monitor the operation of your HVAC systems.
Physical Specifications
Feature | Details |
---|---|
Model | VCC-X EM1 Expansion Module |
Part Number | ASM01691 |
Dimensions (L x W x D) | 5.63" x 5.00" x 1.50" (approx.) |
Mounting | Designed for mounting using three holes in the enclosure base with #8 x 1" sheet metal screws. |
Enclosure | Plastic |
Electrical and Environmental Specifications
Parameter | Value |
---|---|
Operating Power | 18-30 VAC |
Operating Temperature | -22°F to 158°F |
Power Consumption | 5 VA Maximum |
Operating Humidity | 0-95% RH (Non-Condensing) |
Inputs and Outputs
The VCC-X EM1 Expansion Module connects to the VCCX2 Controller via an EBC E-BUS cable, providing additional inputs and outputs.
Inputs
- 4 Analog Inputs
- 3 Binary Inputs
Outputs
- 5 Relay Outputs
- 4 Analog Outputs
Features and Benefits
- Adds Title 24 Exhaust Damper Control Feedback.
- Supports Return Air Bypass functionality.
- Enables Chilled Water control.
- Relay outputs must be wired as wet contacts (connected to 18-30 VAC).
Installation Requirements
The VCC-X EM1 must be installed in an environment that can maintain a temperature range of -22°F to 158°F and humidity not exceeding 95% RH (Non-Condensing). Ensure the device is mounted in a location free from extreme temperatures, moisture, dust, and dirt to prevent damage to electronic components.
Support
For technical assistance, contact AAON Support at www.aaon.com/contact.