Secop BDN50K-A Direct Current Compressor R600a 12/24V DC

Code number: 109Z0465

Electronic unit: Automotive

Compressors on pallet: 240

General Specifications

Application LBP/MBP
Application range 8.5-17 / 19-34 VDC
Voltage range 8.5-17 / 19-34 VDC

Cooling Requirements

Application LBP MBP
32°C / 38°C / 43°C S S

Note: S = Static cooling normally sufficient. In case fan cooling is used: condenser => fan => electronic => compressor.

Absolute Maximum Ratings

Compressor compartment operating temperature -10 to 55 °C
Max. compressor tilt angle for temporary operation ±30°
Operating pressure range See diagram to the right

Compressor Compartment Temperature Protection is available. Please refer to controller instruction sheet. Any levels of stress exceeding the absolute maximum value of machine compartment temperature range or operating pressure range or tilt angle may damage the device. Prolonged exposure to stress above the recommended operating conditions may also affect the device's reliability.

Motor

Motor type Permanent magnet, brushless DC
Speed Variable speed
Resistance, each of the three windings (25°C) 3.1 Ω

Design

Displacement 2.60 cm³
Oil quantity (type) 53 cm³ (polyolester)
Maximum refrigerant charge 70 g
Free gas volume in compressor 472 cm³
Weight - Compressor/Electronic unit 1.37 / 0.14 kg

Standard Battery Protection Settings

Voltage (0.1 steps) Cut out level (VDC) Default (VDC) Min. value (VDC) Max. value (VDC)
12V ± 0.3V DC, all values Cut out level 10.4 8.5 17
24V ± 0.3V DC, all values Cut out level 22.8 19 32
± 0.3V DC, all values range Cut out level 10.4 8.5 32
Battery cut-in difference VDC 1.3 0.5 10

Dimensions

Height A: 89.0 mm
B: 82.4 mm
B1: 48.7 mm
B2: 45.8 mm
Suction connector location/I.D. mm | angle C: 6.25° | D: Copper | Rubber plug
Process connector location/I.D. mm | angle D: 77.9° | Copper | Rubber plug
Discharge connector location/I.D. mm | angle E: 86.9° | Cu-plated steel | Rubber plug
Connector tolerance I.D. mm: ±0.09, on 5.0 +0.12/+0.20

Remarks: Please follow the brazing instructions on page 3 (Product Bulletin DES.N.101.M).

Performance Data (Capacity and Power Consumption)

Capacity (EN 12900 Household/CECOMAF) - 12V DC, static cooling

rpm \ °C -30 -25 -23.3 -20 -15 -10 -5 0 5
2,300 16.8 23.3 25.9 31.3 40.9 52.2 65.4 80.5 97.7
3,000 23.8 32.6 35.9 43.0 55.4 70.0 87.0 106.8
4,000 32.5 44.7 49.2 58.9 75.8 95.7 119.1 146.4
4,500 36.0 50.2 55.3 65.5 82.8 103.2 127.9

Capacity (ASHRAE LBP) - 12V DC, static cooling

rpm \ °C -30 -25 -23.3 -20 -15 -10 -5 0 5
2,300 20.6 28.5 31.6 38.3 50.0 63.8 79.9 98.4 119.4
3,000 29.3 39.9 43.9 52.6 67.6 85.4 106.2 130.4
4,000 39.8 54.6 60.2 72.0 92.6 116.9 145.5 178.9
4,500 44.6 62.0 68.1 80.6 101.6 126.5 156.4

Power consumption - 12V DC, static cooling

rpm \ °C -30 -25 -23.3 -20 -15 -10 -5 0 5
2,300 16.8 20.2 21.4 24.0 28.2 32.5 36.8 41.1 45.1
3,000 21.9 26.6 28.2 31.3 36.1 40.9 45.6 50.2
4,000 30.1 36.9 39.3 43.8 50.6 57.4 64.3 71.2
4,500 34.4 41.8 44.3 49.0 56.0 62.9 69.7

Current consumption (for 24V applications the following must be halved)

rpm \ °C -30 -25 -23.3 -20 -15 -10 -5 0 5
2,300 1.40 1.68 1.79 2.00 2.35 2.71 3.07 3.42 3.76
3,000 1.82 2.22 2.35 2.61 3.01 3.41 3.80 4.19
4,000 2.51 3.08 3.27 3.65 4.22 4.79 5.36 5.93
4,500 2.87 3.49 3.69 4.09 4.67 5.24 5.80

COP (EN 12900 Household/CECOMAF) - 12V DC, static cooling

rpm \ °C -30 -25 -23.3 -20 -15 -10 -5 0 5
2,300 1.00 1.16 1.21 1.30 1.45 1.61 1.78 1.96 2.17
3,000 1.09 1.23 1.27 1.37 1.53 1.71 1.91 2.13
4,000 1.08 1.21 1.25 1.35 1.50 1.67 1.85 2.06
4,500 1.05 1.20 1.25 1.34 1.48 1.64 1.84

COP (ASHRAE LBP) - 12V DC, static cooling

rpm \ °C -30 -25 -23.3 -20 -15 -10 -5 0 5
2,300 1.24 1.42 1.48 1.53 1.60 1.79 1.98 2.18 2.41
3,000 1.33 1.48 1.53 1.65 1.85 2.04 2.27 2.53
4,000 1.32 1.48 1.53 1.65 1.85 2.04 2.27 2.53
4,500 1.30 1.48 1.54 1.65 1.82 2.02 2.25

Operational Errors (TOOL4COOL® or LED flashes)

Error code or LED flashes Error type Description
7 Communication error Communication of master controller stopped for 15 minutes (default).
6 Thermostat failure If a NTC thermistor is short-circuit or has no connection, the electronic unit will enter manual mode.
5 Thermal cut-out of electronic unit PCB or compressor compartment temperature exceeds minimum or maximum limits.
4 Minimum motor speed error If the refrigeration system is too heavily loaded, the motor cannot maintain min. speed at approximately 2,150 rpm.
3 Motor start error The rotor is blocked or the differential pressure in the refrigeration system is too high (>5 bar).
2 Fan over-current cut-out The fan is overloading the electronic unit.
1 Battery protection cut-out The voltage is outside the cut-out setting.

Wire Dimensions DC

Cross section AWG Max. length* 12V operation Max. length* 24V operation
[mm²] [Gauge] [m] [ft.] [m] [ft.]
2.5 12 5 16 4 13
4 10 8 26 6 20
6 8 10 33 8 26
10 6 16 52 12 39

*Length between battery and electronic unit.

Accessories for BDN50K-A

Item Code number
Mounting Bolt joint for one compressor 118-1960
Secop Gateway 105N9518

Test conditions

EN 12900 CECOMAF ASHRAE LBP
Condensing temperature 55°C 54.4°C
Ambient temperature 32°C 32°C
Suction gas temperature 32°C 32°C
Liquid temperature No subcooling 32°C

Wiring Diagram

Spade connectors 6.3 mm | 1/4 in.

The diagram shows a typical wiring setup for the Secop BDN50K-A compressor, including connections for power supply, Secop Gateway, PC option (TOOL4COOL®), display, and NTC resistor. It illustrates the use of spade connectors and highlights the different connection points for various options.

Key connections:

Brazing Instructions

BD Nano Discharge Connector

Secop BDN45F/-A, BDN50K/-A, MB3CKV, and BDN-EV compressors utilize a special discharge connector element designed to optimize energy consumption. This element is made of plastic and is sensitive to high heat exposure.

Important considerations during brazing:

Further information: Product Bulletin – Brazing Technique for Compressor Connectors (DES.N.600.A1.02).

PDF preview unavailable. Download the PDF instead.

bdn50k-a 109z0465 r600a 12-24vdc 06-2025 desd102m202 Adobe InDesign 20.3 (Windows) Adobe PDF Library 17.0

Related Documents

Preview Secop MB3CKV Direct Current Compressor R600a, Medical 12/24V DC - Technical Data
Technical specifications and performance data for the Secop MB3CKV Direct Current Compressor, designed for medical applications with R600a refrigerant and 12/24V DC power supply. Includes operating ranges, power consumption, COP values, dimensions, and safety features.
Preview Secop BDN45F-A DC Compressor R134a, R1234yf 12/24V Technical Data
Technical specifications and performance data for the Secop BDN45F-A Direct Current Compressor, compatible with R134a and R1234yf refrigerants, operating on 12/24V DC. Includes performance tables, electrical specifications, dimensions, and brazing instructions.
Preview Secop BDN45F Direct Current Compressor - Technical Data Sheet
Technical specifications, performance data, and application information for the Secop BDN45F direct current compressor, compatible with R134a and R1234yf refrigerants for 12/24V DC systems.
Preview Secop BDN50K R600a 12/24V DC Direct Current Compressor Technical Data
Technical specifications and operational data for the Secop BDN50K R600a 12/24V DC direct current compressor, including performance charts, electrical specifications, and dimensions.
Preview Secop BD35K 12/24V DC PM Compressor - Technical Specifications and Information
Detailed technical specifications, application data, and service information for the Secop BD35K 12/24V DC PM compressor, including electrical and mechanical properties, performance charts, and safety guidelines.
Preview Secop DC-Powered Compressors for Mobile Cooling
Secop offers advanced DC-powered compressors for mobile cooling applications, including 12V, 24V, and 48V DC models. These compressors are designed for stability, reliability, and efficiency in various mobile environments such as vehicles, boats, and portable units. The product line includes models like BD Nano, BD Micro, and various BD series compressors, utilizing refrigerants like R134a, R1234yf, R600a, and R290. Secop provides solutions for stationary, mobile, and medical cooling needs.
Preview Secop BD1.4F-VSD Electronic Unit 101N2130: Installation and Operation Guide
Detailed instructions for installing and operating the Secop BD1.4F-VSD electronic unit (model 101N2130) for 12-24V DC compressors. Covers power, battery protection, thermostat, fan control, setpoint adjustment, and troubleshooting with the TOOL4COOL® software.
Preview Secop Compressor Type Designation Guide
A comprehensive guide to understanding Secop's AC, DC, and Medical compressor type designations, covering fixed-speed, variable-speed, and specialized series.