Generac Guardian Series Residential Standby Generators (16/20/22 kW)
The Generac Guardian Series offers reliable air-cooled gas engine standby generators designed for residential use, providing essential power during outages.
Key Features & Inclusions
- True Power™ Electrical Technology: Delivers utility-quality power with less than 5% Total Harmonic Distortion, suitable for sensitive electronics and micro-chip based appliances.
- Two-Line LCD Multilingual Digital Evolution™ Controller: Supports English, Spanish, French, and Portuguese for easy operation and status monitoring.
- Transfer Switch Options: Available with a 100 Amp Pre-Wired Switch or a 200 Amp Service Rated Switch (details on page 4).
- Electronic Governor: Ensures stable engine speed and power output.
- External Main Circuit Breaker, System Status & Maintenance Interval LED Indicators: Provide clear operational status and maintenance alerts.
- GFCI Duplex Outlet: For convenient temporary power needs.
- Sound Attenuated Enclosure: Offers quiet operation and protection against weather, withstanding winds up to 150 mph.
- Flexible Fuel Line Connector: Accommodates natural gas or LP gas.
- Composite Mounting Pad: Eliminates the need for a concrete pad in many installations.
- 5 Year Limited Warranty: Provides peace of mind.
- Installation Flexibility: Can be installed as close as 18 inches (457 mm) from a building (subject to local codes and safety requirements).
Generac's Commitment to Quality
Generac emphasizes Innovative Design & Prototype Testing, along with rigorous reliability, environmental, destruction, and life testing to meet CSA, NEMA, EGSA, and other standards. This ensures superior performance and confidence in their power systems.
Solid-State, Frequency Compensated Voltage Regulation is standard, providing optimized response to load changes and maximum motor starting capability with digital voltage regulation at ±1%.
Single Source Service Response is available through Generac's extensive dealer network for parts and service.
Generac also manufactures its own Transfer Switches, ensuring total system compatibility.
Test Criteria Met:
- ✔️ Prototype Tested
- ✔️ NEMA MG1-22 Evaluation
- ✔️ System Torsional Tested
- ✔️ Motor Starting Ability
Generator Specifications
Model | 006459-0, 006461-0, 006462-1, 006721-0 (16 kW) | 006729-1, 006730-0 (20 kW) | 006551-1, 006552-0 (22 kW) |
---|---|---|---|
Rated Maximum Continuous Power Capacity (LP) | 16,000 Watts* | 20,000 Watts* | 22,000 Watts* |
Rated Maximum Continuous Power Capacity (NG) | 16,000 Watts* | 18,000 Watts* | 19,500 Watts* |
Rated Voltage | 240 | 240 | 240 |
Rated Maximum Continuous Load Current - 240 Volts (LP/NG) | 66.6/66.6 | 83.3/75 | 91.6/81.3 |
Total Harmonic Distortion | Less than 5% | Less than 5% | Less than 5% |
Main Line Circuit Breaker | 65 Amp | 90 Amp | 100 Amp |
Phase | 1 | 1 | 1 |
Number of Rotor Poles | 2 | 2 | 2 |
Rated AC Frequency | 60 Hz | 60 Hz | 60 Hz |
Power Factor | 1.0 | 1.0 | 1.0 |
Battery Requirement (not included) | Group 26R, 12 Volts and 525 CCA Minimum | Group 26R, 12 Volts and 525 CCA Minimum | Group 26R, 12 Volts and 525 CCA Minimum |
Unit Weight (lb/kg) | 513/232.7 (Steel); 448/203.2 (Aluminum) | 516/234.1 | 526/238.6 |
Dimensions (L x W x H) in/mm | 48 x 25 x 29 / 1218 x 638 x 732 | 48 x 25 x 29 / 1218 x 638 x 732 | 48 x 25 x 29 / 1218 x 638 x 732 |
Sound output in dB(A) at 23 ft (7 m) (normal load)** | 66 | 66 | 67 |
Sound output in dB(A) at 23 ft (7 m) (Quiet-Test™ low-speed exercise)** | 60 | 60 | 58 |
Exercise duration | 5 min | 5 min | 5 min |
Engine Specifications
Feature | GENERAC OHVI V-TWIN | GENERAC OHVI V-TWIN | GENERAC OHVI V-TWIN |
---|---|---|---|
Type of Engine | GENERAC OHVI V-TWIN | GENERAC OHVI V-TWIN | GENERAC OHVI V-TWIN |
Number of Cylinders | 2 | 2 | 2 |
Displacement | 992 cc | 999 cc | 999 cc |
Cylinder Block | Steel | Aluminum w/ Cast Iron Sleeve | Overhead Valve |
Valve Arrangement | Overhead Valve | Overhead Valve | Overhead Valve |
Ignition System | Solid-state w/ Magneto | Solid-state w/ Magneto | Solid-state w/ Magneto |
Governor System | Electronic | Electronic | Electronic |
Compression Ratio | 9.5:1 | 9.5:1 | 9.5:1 |
Starter | 12 Vdc | 12 Vdc | 12 Vdc |
Oil Capacity Including Filter | Approx. 1.9 qt/1.8 L | Approx. 1.9 qt/1.8 L | Approx. 1.9 qt/1.8 L |
Operating rpm | 3,600 | 3,600 | 3,600 |
Fuel Consumption
Natural Gas
Load | 16 kW | 20 kW | 22 kW |
---|---|---|---|
1/2 Load (ft³/hr / m³/hr) | 193 (5.47) | 205 (5.8) | 184 (5.21) |
Full Load (ft³/hr / m³/hr) | 312 (8.83) | 308 (8.72) | 281 (7.96) |
Liquid Propane
Load | 16 kW | 20 kW | 22 kW |
---|---|---|---|
1/2 Load (ft³/hr / gal/hr) [l/hr] | 72.4 (1.99) [7.53] | 75.6 (2.08) [7.87] | 83 (2.16) [8.16] |
Full Load (ft³/hr / gal/hr) [l/hr] | 130 (3.19) [13.53] | 140 (3.85) [14.57] | 127 (3.68) [13.99] |
Note: Fuel pipe must be sized for full load. Required fuel pressure to generator fuel inlet at all load ranges - 3.5-7" water column (7-13 mm mercury) for natural gas, 10-12" water column (19-22 mm mercury) for LP gas. For Btu content, multiply ft³/hr x 2500 (LP) or ft³/hr x 1000 (NG). For Megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG).
Control Features
- 2-Line Plain Text Multilingual LCD Display: Simple interface for ease of operation.
- Mode Buttons: Auto, Manual, Off.
- Ready to Run/Maintenance Messages: Provides status and alerts.
- Engine Run Hours Indication: Standard.
- Programmable start delay: Between 2-1500 seconds.
- Utility Voltage Loss/Return to Utility Adjustable: Includes brownout setting.
- Exerciser/Exercise Set Error Warning: Standard.
- Run/Alarm/Maintenance Logs: Stores up to 50 events.
- Engine Start Sequence: Cyclic cranking (16 sec on, 7 sec rest, 90 sec max duration).
- Starter Lock-out: Prevents re-engagement for 5 seconds after engine stops.
- Smart Battery Charger: Standard.
- Charger Fault/Missing AC Warning: Standard.
- Low Battery/Battery Problem Protection: Standard.
- Automatic Voltage Regulation: With over and under voltage protection.
- Under-Frequency/Overload/Stepper Overcurrent Protection: Standard.
- Safety Fused/Fuse Problem Protection: Standard.
- Automatic Low Oil Pressure/High Oil Temperature Shutdown: Standard.
- Overcrank/Overspeed (@ 72 Hz)/rpm Sense Loss Shutdown: Standard.
- High Engine Temperature Shutdown: Standard.
- Internal Fault/Incorrect Wiring Protection: Standard.
- Common External Fault Capability: Standard.
- Field Upgradable Firmware: Standard.
* Maximum wattage and current are subject to and limited by such factors as fuel Btu/megajoule content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5 percent for each 1,000 feet (304.8 meters) above sea level; and also will decrease about 1 percent for each 6 °C (10 °F) above 16 °C (60 °F).
Switch Options
Pre-wired Features (Available on Steel 16 kW models only)
- Electrically operated, mechanically-held contacts for fast, positive connections.
- Rated for all classes of load, 100% equipment rated, both inductive and resistive.
- 2 pole, 250 VAC contactors.
- 30 millisecond transfer time.
- Dual coil design.
- Main contacts are silver plated or silver alloy to resist welding and sticking.
- NEMA 1 (indoor rated) enclosure.
- Includes pre-wired 30-foot (9.1 meter) whip and 2-foot (0.61 meter) color-coded whip.
Model 006461-0 (16 kW) - Pre-wired Switch
No. of Poles | 2 |
Current Rating (Amps) | 100 |
Voltage Rating (VAC) | 120/240, 1Ø |
Utility Voltage Monitor (Fixed) | Pick-up: 80%, Dropout: 60% |
Return to Utility* | approx. 15 sec. |
Exercise weekly for 12 minutes* | Standard |
Total of Pre-wired Circuits | 16 (including various 120V and 240V circuits) |
Circuit Breaker Protected Available RMS Symmetrical Fault Current @ 250 Volts | 10,000 |
*Function of Evolution Controller
Service Rated Switch Features
- Electrically operated, mechanically-held contacts for fast, clean connections.
- Rated for all classes of load, 100% equipment rated, both inductive and resistive.
- 2 pole, 250 VAC contactors.
- Service equipment rated, dual coil design.
- Rated for both aluminum and copper conductors.
- NEMA/UL 3R aluminum outdoor enclosure.
- Main contacts are silver plated or silver alloy to resist welding and sticking.
Models 006462-1 (16 kW)/006729-1 (20 kW)/006551-1 (22 kW) - Service Rated Switch
No. of Poles | 2 |
Current Rating (Amps) | 200 |
Voltage Rating (VAC) | 120/240, 1Ø |
Utility Voltage Monitor (Fixed) | Pick-up: 80%, Dropout: 60% |
Return to Utility* | approx. 13 sec. |
Exercise weekly for 12 minutes* | Standard |
Enclosure Type | NEMA/UL 3R |
Withstand Rating (Amps) | 22,000 |
Lug Range | 250 MCM - #6 |
*Function of Evolution Controller
Available Accessories
Model # | Product | Description |
---|---|---|
006463-3 | Mobile Link™ | Allows remote status checking via internet connection (PC or smart device), with email/text notifications for status changes. |
005819-0 | 26R Wet Cell Battery | Recommended battery for air-cooled standby products (excluding PowerPact®). |
006212-0 | Cold Weather Kit | Maintains optimal battery and oil temperatures in temperatures below 32 °F (0 °C). Includes battery warmer and oil filter heater. |
005621-0 | Auxiliary Transfer Switch Contact Kit | Allows transfer switch to lock out a single large electrical load. Not compatible with 50 amp pre-wired switches. |
005839-0 (Bisque) 005666-0 (Gray) |
Fascia Base Wrap Kit* | Snaps around the bottom of the generator for a sleek appearance and protection from rodents/insects. (*Bisque for steel, Gray for aluminum enclosures). |
005703-0 (Bisque) 005704-0 (Gray) |
Paint Kit* | For touching up generator enclosure paint to protect from corrosion. (*Bisque for steel, Gray for aluminum enclosures). |
006484-0 (16 kW) 006485-0 (20 & 22 kW) |
Scheduled Maintenance Kit | Provides hardware for complete routine maintenance. |
006664-0 | Wireless Remote Monitor | Provides instant status information wirelessly. Not compatible with CorePower or EcoGen systems. |
006873-0 | Smart Management Module (50 Amps) | Enhances power management capabilities when used with an Automatic Transfer Switch. |
Dimensions & UPCs
Dimensions shown are approximate. Refer to installation manual for exact dimensions.
View | Height (in/mm) | Width (in/mm) | Depth (in/mm) |
---|---|---|---|
Left Side | 28.8 / 731.9 | 25.1 / 637.6 | 25.3 / 642 |
Front | 48.3 / 1226 | 47.9 / 1218 | N/A |
Model | UPC |
---|---|
006459-0 | 696471064599 |
0064610 | 696471064612 |
006721-0 | 696471067217 |
006729-1 | 696471067293 |
006730-0 | 696471067309 |
006551-1 | 696471065510 |
006552-0 | 696471065527 |
006462-1 | 696471064629 |
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2015 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0K8458-F Printed in U.S.A. 04/10/15