STUDER AJ Series Pure Sine Wave Inverters

High-quality inverters for industrial and domestic applications, manufactured in Switzerland.

Introduction

The Studer AJ series pure sine wave inverters convert battery voltage into high-quality 230/120Vac, suitable for all electrical appliances. Designed to meet industrial and domestic needs, the AJ series offers an optimal solution for standalone applications, ensuring comfort, safety, and reliability. Manufactured in Switzerland, these inverters are delivered with AC and battery cables, providing a true ‘plug and forget’ solution.

Key features include high and steady efficiency, outstanding overload capabilities, digital regulation and control by microprocessor, electrical supply for any type of appliance, full internal protection, battery lifetime optimization (B.L.O.) function, and Plug&Play setup.

Technical Specifications

The following tables detail the specifications for the Studer AJ series inverters across different models and voltage configurations.

AJ Series Overview
Specification aj 275-400 aj 500-700 aj 1000-1300 aj 2100-2400
Nominal battery voltage 12/24/48 Vdc 12/24 Vdc 12/24 Vdc 12/24 Vdc
Continuous power @ 25°C 200-300 VA 400-500 VA 800-1000 VA 2000 VA
Power 30 min. @ 25°C 275-400 VA 500-700 VA 1000-1300 VA 2100-2400 VA
Power 5 sec. @ 25°C 450-1000 VA 1000-1400 VA 2200-2800 VA 5000-5200 VA
Output voltage and frequency Sine wave 230 Vac (120 Vac*) ±5% / 50 Hz (60 Hz*) ± 0.05% (crystal controlled)
Weight 2.4-2.6 kg 4.5 kg 8.5 kg 18-19 kg
Dimensions (h/w/l) 142/163/84 mm 142/240/84 mm 142/428/84 mm 273/399/117 mm
Ingress Protection (DIN 40050) IP 30 IP 30 IP 30 IP 20
Remote control rcm01/02/03 jt8 jt8 jt8

aj 275-400 Series

aj 275-400 Series Specifications
Specification aj 275-12 aj 350-24 aj 400-48
Nominal battery voltage (Input range)12 Vdc (10.5 - 16 Vdc)24 Vdc (21-32 Vdc)48 Vdc (42-60 Vdc)
Continuous power @ 25°C200 VA300 VA300 VA
Power 30 min. @ 25°C275 VA350 VA400 VA
Power 5 min. @ 25°C350 VA500 VA600 VA
Power 5 sec. @ 25°C450 VA650 VA1000 VA
Asymmetric load max.150 VA150 VA200 VA
Max. efficiency (%)93%94%94%
Cos φ max.0.1-1 up to 200 VA0.1-1 up to 300 VA0.1-1 up to 300 VA
Detection of the load (Stand-by)2 W only with the solar option -S
Short-circuit current AC 2 sec.2.3 Aac (4.6 Aac*)3.2 Aac (6.4 Aac*)4.6 Aac (9.2 Aac*)
Output voltageSine wave 230 Vac (120 Vac*) ±5%
Frequency50 Hz (60 Hz*) ± 0.05% (crystal controlled)
Consumption Stand-by / ON no load0.3 W**/2.4 W0.5 W**/3.5 W1.1 W**/5.2 W
Reverse polarity protection as internal fuse60 A40 A25 A
Protection FeaturesDistortion THD (resistive load) < 3% (@Pnom & Uin nom.) | Overheat protection (±5°C) Shut down @ 75°C - Auto-restart @ 70°C | Overload and short circuit protection Automatic disconnection with 2 time restart attempt | Deep discharge battery protection Shut off @ 0.87 x Unom - Automatic restart @ Unom | Max. battery voltage Shut off @ >1.33 x Unom - Automatic restart @ < Umax | Acoustic alarm Before low battery or overheating disconnection
General dataWeight: 2.4 kg
Dimensions h/w/l: 142/163/84 mm
Weight: 2.6 kg
Dimensions h/w/l: 142/240/84 mm
Weight: 2.6 kg
Dimensions h/w/l: 142/428/84 mm
ConformityLow voltage directive (LVD) 2014/35/EU: EN/IEC 62109-1, 62109-2, 62477-1, electromagnetic compliance (EMC) directive 2014/30/EU: EN/IEC 61000-3-3, 61000-6-2, 61000-6-4, 62040-2
Ingress protection of enclosuresIP30IP30IP30
Operating temperature range-20 to 50°C
Relative humidity95% (non condensing)
Ventilation forcedfrom 45°C ± 5°C
Length cables (battery/AC out)1.2 m/1m1.2 m/1m1.2 m/1m
Acoustic level< 45 dB (with ventilation)
Approximate correction of Pnom-1.5% / °C from + 25°C
Recommended battery capacity> 5 x Pnom/Unom (recommended value in Ah)

aj 500-700 Series

aj 500-700 Series Specifications
Specification aj 500-12 aj 600-24 aj 700-48
Nominal battery voltage (Input range)12 Vdc (10.5 - 16 Vdc)24 Vdc (21-32 Vdc)48 Vdc (42-60 Vdc)
Continuous power @ 25°C400 VA500 VA500 VA
Power 30 min. @ 25°C500 VA600 VA700 VA
Power 5 min. @ 25°C575 VA675 VA900 VA
Power 5 sec. @ 25°C1000 VA1200 VA1400 VA
Asymmetric load max.250 VA300 VA300 VA
Max. efficiency (%)93%94%94%
Cos φ max.0.1-1 up to 400 VA0.1-1 up to 500 VA0.1-1 up to 500 VA
Detection of the load (Stand-by)Adjustable: 1 to 20 W
Short-circuit current AC 2 sec.5.2 Aac (10.4 Aac*)5.7 Aac (11.4 Aac*)7 Aac (14 Aac*)
Output voltageSine wave 230 Vac (120 Vac*) ±5%
Frequency50 Hz (60 Hz*) ± 0.05% (crystal controlled)
Consumption Stand-by / ON no load0.4 W/ 4.6 W0.6 W/ 7.2 W1.5 W/ 12 W
Reverse polarity protection as internal fuse120 A90 A60 A
Protection FeaturesDistortion THD (resistive load) < 3% (@Pnom & Uin nom.) | Overheat protection (±5°C) Shut down @ 75°C - Auto-restart @ 70°C | Overload and short circuit protection Automatic disconnection with 2 time restart attempt | Deep discharge battery protection Shut off @ 0.87 x Unom - Automatic restart @ Unom | Max. battery voltage Shut off @ >1.33 x Unom - Automatic restart @ < Umax | Acoustic alarm Before low battery or overheating disconnection
General dataWeight: 4.5 kg
Dimensions h/w/l: 142/240/84 mm
Weight: 4.5 kg
Dimensions h/w/l: 142/240/84 mm
Weight: 4.5 kg
Dimensions h/w/l: 142/240/84 mm
ConformityLow voltage directive (LVD) 2014/35/EU: EN/IEC 62109-1, 62109-2, 62477-1, electromagnetic compliance (EMC) directive 2014/30/EU: EN/IEC 61000-3-3, 61000-6-2, 61000-6-4, 62040-2
Ingress protection of enclosuresIP30IP30IP30
Operating temperature range-20 to 50°C
Relative humidity95% (non condensing)
Ventilation forcedfrom 45°C ± 5°C
Length cables (battery/AC out)1.5 m / 1 m1.5 m / 1 m1.5 m / 1 m
Acoustic level< 45 dB (with ventilation)
Approximate correction of Pnom-1.5% / °C from + 25°C
Recommended battery capacity> 5 x Pnom/Unom (recommended value in Ah)

aj 1000-1300 Series

aj 1000-1300 Series Specifications
Specification aj 1000-12 aj 1300-24
Nominal battery voltage (Input range)12 Vdc (10.5 - 16 Vdc)24 Vdc (21-32 Vdc)
Continuous power @ 25°C800 VA1000 VA
Power 30 min. @ 25°C1000 VA1300 VA
Power 5 min. @ 25°C1200 VA2000 VA
Power 5 sec. @ 25°C2200 VA2800 VA
Asymmetric load max.500 VA600 VA
Max. efficiency (%)93%94%
Cos φ max.0.1-1 up to 800 VA0.1-1 up to 1000 VA
Detection of the load (Stand-by)Adjustable: 1 to 20 W
Short-circuit current AC 2 sec.10 Aac (20 Aac*)13 Aac (26 Aac*)
Output voltageSine wave 230 Vac (120 Vac*) ±5%
Frequency50 Hz (60 Hz*) ± 0.05% (crystal controlled)
Consumption Stand-by / ON no load0.7 W/ 10 W1.2 W/13 W
Reverse polarity protection as internal fuse125 A100 A
Protection FeaturesDistortion THD (resistive load) < 3% (@Pnom & Uin nom.) | Overheat protection (±5°C) Shut down @ 75°C - Auto-restart @ 70°C | Overload and short circuit protection Automatic disconnection with 2 time restart attempt | Deep discharge battery protection Shut off @ 0.87 x Unom - Automatic restart @ Unom | Max. battery voltage Shut off @ >1.33 x Unom - Automatic restart @ < Umax | Acoustic alarm Before low battery or overheating disconnection
General dataWeight: 8.5 kg
Dimensions h/w/l: 142/428/84 mm
Weight: 8.5 kg
Dimensions h/w/l: 142/428/84 mm
ConformityLow voltage directive (LVD) 2014/35/EU: EN/IEC 62109-1, 62109-2, 62477-1, electromagnetic compliance (EMC) directive 2014/30/EU: EN/IEC 61000-3-3, 61000-6-2, 61000-6-4, 62040-2
Ingress protection of enclosuresIP30IP30
Operating temperature range-20 to 50°C
Relative humidity95% (non condensing)
Ventilation forcedfrom 45°C ± 5°C
Length cables (battery/AC out)1.5 m / 1 m1.5 m / 1 m
Acoustic level< 45 dB (with ventilation)
Approximate correction of Pnom-1.5% / °C from + 25°C
Recommended battery capacity> 5 x Pnom/Unom (recommended value in Ah)

aj 2100-2400 Series

aj 2100-2400 Series Specifications
Specification aj 2100-12 aj 2400-24
Nominal battery voltage (Input range)12 Vdc (10.5 - 16 Vdc)24 Vdc (21-32 Vdc)
Continuous power @ 25°C2000 VA2000 VA
Power 30 min. @ 25°C2100 VA2400 VA
Power 5 min. @ 25°C2450 VA2800 VA
Power 5 sec. @ 25°C5000 VA5200 VA
Asymmetric load max.1000 VA1200 VA
Max. efficiency (%)92%94%
Cos φ max.0.1-1 up to 2000 VA0.1-1 up to 2000 VA
Detection of the load (Stand-by)Adjustable: 1 to 20 W
Short-circuit current AC 2 sec.26 Aac (52 Aac*)30 Aac (60 Aac*)
Output voltageSine wave 230 Vac (120 Vac*) ±5%
Frequency50 Hz (60 Hz*) ± 0.05% (crystal controlled)
Consumption Stand-by / ON no load0.7 W/ 16 W1.2 W/ 16 W
Reverse polarity protection as internal fuseNot protected150 A
Protection FeaturesDistortion THD (resistive load) < 3% (@Pnom & Uin nom.) | Overheat protection (±5°C) Shut down @ 75°C - Auto-restart @ 70°C | Overload and short circuit protection Automatic disconnection with 2 time restart attempt | Deep discharge battery protection Shut off @ 0.87 x Unom - Automatic restart @ Unom | Max. battery voltage Shut off @ >1.33 x Unom - Automatic restart @ < Umax | Acoustic alarm Before low battery or overheating disconnection
General dataWeight: 19 kg
Dimensions h/w/l: 273/399/117 mm
Weight: 18 kg
Dimensions h/w/l: 273/399/117 mm
ConformityLow voltage directive (LVD) 2014/35/EU: EN/IEC 62109-1, 62109-2, 62477-1, electromagnetic compliance (EMC) directive 2014/30/EU: EN/IEC 61000-3-3, 61000-6-2, 61000-6-4, 62040-2
Ingress protection of enclosuresIP20IP20
Operating temperature range-20 to 50°C
Relative humidity95% (non condensing)
Ventilation forcedfrom 45°C ± 5°C
Length cables (battery/AC out)1.7 m/1m1.7 m/1m
Acoustic level< 45 dB (with ventilation)
Approximate correction of Pnom-1.5% / °C from + 25°C
Recommended battery capacity> 5 x Pnom/Unom (recommended value in Ah)

Options

The AJ series offers various options for enhanced functionality:

Specific options and their configurations:

Option Details
Feature aj 275-400 aj 500-700 aj 1000-1300 aj 2100-2400
Solar regulator Voltage max. 25 Vdc 45 Vdc 25 Vdc 45 Vdc
Solar regulator Current max. 10 Adc 15 Adc 25 Adc 30 Adc
Solar regulator Principle Floating 3 stages (I/U/UO)
Solar regulator Absorption voltage 14.4 Vdc 28.8 Vdc 14.4 Vdc 28.8 Vdc
Solar regulator Floating voltage 13.6 Vdc 27.2 Vdc 13.6 Vdc 27.2 Vdc
Remote control rcm01/02/03 ✔️ ✔️ ✔️ ✔️

Note: The checkmark ✔️ indicates availability for the respective model series.

Certifications

The manufacturing facilities are certified according to ISO 9001:2015 and ISO 14001:2015 standards.

Image: Logos for ISO 9001, ISO 14001, Net (Netzbetreiber), and other certification marks.

PDF preview unavailable. Download the PDF instead.

Studer AJ A4-WEB Adobe PDF library 17.00 Adobe Illustrator 29.8 (Windows)

Related Documents

Preview Studer next3 Quick Guide - Smart Battery Inverter/Charger
This quick guide provides essential information for the Studer next3 smart battery inverter/charger, including installation, wiring, configuration, technical specifications, and maintenance. Designed and manufactured in Switzerland.
Preview Studer RCC 02/03 Quick Guide: Battery Management System Remote Control
A concise guide to installing and operating the Studer RCC 02/03 remote control for battery-based energy systems, detailing setup, configuration, and technical specifications.
Preview Studer nextOS Manual: Interface and Operation Guide for next3 and next1 Systems
Comprehensive guide to Studer's nextOS environment, covering the nx-interface and webserver for programming and operating next3 and next1 renewable energy systems. Details installation, configuration, monitoring, and maintenance.
Preview STUDER next interface Quickstart Guide: Installation, Monitoring & Remote Control
A quickstart guide to the STUDER next interface, covering installation, configuration, remote control, monitoring, and updates for power management systems. Learn about dashboard features, device settings, and system integration.
Preview Studer xcom 485i-nx Communication Module Quick Guide
Quick guide for the Studer xcom 485i-nx communication module, detailing its connection to nx systems and vario solar chargers, including RS485 MODBUS and nx bus termination configurations. Features technical specifications and contact information for Studer Innotec SA.
Preview nextOS Manual: Programming and Operating Studer Energy Systems
Comprehensive guide to Studer's nextOS for programming and operating next3 and next1 renewable energy systems, covering HMI, configuration, monitoring, and maintenance.
Preview STUDER xconnect Quick Guide
A concise guide to the STUDER xconnect mounting frame, detailing its features, installation, cabling possibilities, and multi-unit system configurations for high-power inverter systems.
Preview STUDER next3 Inverter Charger Technical Specifications and Features
Explore the STUDER next3, a versatile 3-phase smart inverter charger with built-in solar MPPT inputs. Discover its features, specifications, and accessories for off-grid and on-grid applications, designed for outstanding performance and Swiss quality.