Honeywell INNCOM Direct D-X47 HVAC Controller

Honeywell's INNCOM Direct is an energy management system tailored to provide an all-in-one control and management for a hotel's guestroom and common area HVAC systems.

Product Overview

Out of the box, INNCOM Direct DX47 controller is an essential part of Honeywell's online HVAC solution designed to reduce energy usage in guestroom and common area, enabling hoteliers to reach sustainability goals faster. Additionally, INNCOM Direct provides the capability for portfolio management to optimize room and equipment performance to increase guest satisfaction and decrease operational costs.

The DX47 provides five relay outputs and a range of digital and analog I/O to control a wide variety of light duty HVAC systems. The DX47 is the companion to the wireless D1-529-6V battery powered thermostat, and uses INNCOM's low cost, self-forming RF mesh network for wireless communications, fast setup, and easy maintenance.

Features and Highlights

Part Numbers

DX47 Part Numbers

PART NUMBER DESCRIPTION
D-X47-24 INNCOM DX47 HVAC Controller

Accessories Parts

PART NUMBER DESCRIPTION
62-1511 DX47 Low voltage harness (H2, H5)
62-1465.B DX47 Low voltage harness (H3, H4, H8, H9)
62-1464.R DX47 24 VAC Harness
62-1467 DX47 Low Voltage Cable
13-4019 1/4 wave antenna for 2.4 Ghz RF transceiver
04-1095 External ruggedized thermistor

Dimensions

The DX47 controller has the following dimensions: Width: 2.83 inches (72 mm), Height: 4.09 inches (104 mm), Depth: 1.55 inches (39.6 mm). The mounting is designed for four 6/32" screws with a 1/2" thread length.

System Overview

The system overview illustrates a typical setup involving a Niagara Gateway, a Remote Building Manager, and various INNCOM devices. The network includes IP Ethernet and RF Network connections. Devices shown are D1-529 Thermostats and D-X47 HVAC Controllers, connected via a D-578 Edge Router. The system supports common areas and guest rooms, with connections to a network switch.

Legend: IP Ethernet, RF Network

Product Specifications

Electrical

PARAMETER SPECIFICATION
Input Power 24 VAC 50/60 Hz, 2.4 VA
Class-2 Output (H9) 12 VDC 200 mA (The DX47 should not be used to provide more than 70 mA of external class-2 power)
S5bus I/O +18 dBm
RF Transmit Power -98 dBm
RF Receive Sensitivity -98 dBm

Current Consumption

PARAMETER DESCRIPTION
All relays actuated 130 mA Maximum Load (including logic board)

Environmental Specifications

PARAMETER SPECIFICATION
Operating Temperature 32 °F to 104°F (0°C to 40 °C)
Storage Temperature -40 °F to 158°F (-40 °C to 70°C)

Weight and Dimensions

PARAMETER SPECIFICATION
Dimensions (W x H x D) 2.83 inches x 4.09 inches x 1.55 inches, (72 mm x 104 mm x 39.6 mm)
Shipping Weight 0.37 lbs (0.171 kg)
Mounting 4 hole mounting 6/32" bit, 1/2" screw

Relay Ratings

RELAY RELAY RATING PIN ASSIGNMENT
K1 1A sealed, 10A inrush, class 2 pilot duty P4
K2 1A sealed, 10A inrush, class 2 pilot duty P5
K3 1A sealed, 10A inrush, class 2 pilot duty P10
K4 1A sealed, 10A inrush, class 2 pilot duty P7
K5 1A sealed, 10A inrush, class 2 pilot duty P6
Common 1 K1, K2, K3 P9
Common 2 K4, K5 P8

Typical HVAC Applications

4 pipe, 3 fan, heat/cool FCU 2 pipe, 3 fan, Cool only FCU Heat Pump, 2 fan 2nd stage heat Heat pump, 3 fan speeds PTAC, 2 Fan with heat strip
K1 High Fan High Fan High Fan High Fan High Fan
K2 Medium Fan Medium Fan Medium Fan Medium Fan Medium Fan
K3 Low Fan Low Fan Low Fan Low Fan Low Fan
K4 Cool Signal Cool Signal Y-Compressor Y-Compressor Y-Compressor
K5 Heat Signal Not Connected B/O Reversing Valve B/O Reversing Valve W-Heat

Wired Communications & Digital/Analog IO

PIN COLOR TYPICAL FUNCTION
1 Brown Common
2 Red 12 VDC Output/Input
3 Orange S5bus Data
4 Yellow Digital Input
5 Green Not Connected
6 Blue Not Connected

Wired External Temperature Sensors

External temperature sensor input: H3, H4

Standards and Approvals

Regulatory Information

This device compiles with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

PDF preview unavailable. Download the PDF instead.

hon-ba-bms-inncom-dx47-hvac-controller-datasheet-31-00719-01 ?download=false Adobe PDF Library 17.0

Related Documents

Preview Honeywell INNCOM Direct D1-529 Wireless Thermostat Datasheet
Datasheet for the Honeywell INNCOM Direct D1-529 wireless thermostat, an energy management system for hotel guestrooms and common areas, detailing its features, specifications, and applications.
Preview Honeywell INNCOM Direct D1-529 Thermostat & D-X47 HVAC Controller Installation Guide
Comprehensive installation guide for the Honeywell INNCOM Direct D1-529 Thermostat and D-X47 HVAC Controller, detailing setup, configuration, specifications, and troubleshooting for building automation systems.
Preview Honeywell INNCOM Direct D-578 Edge Router Datasheet
Datasheet for the Honeywell INNCOM Direct D-578 Edge Router, an energy management system for hotel guestroom and common area HVAC, featuring the INNCOM Deep Mesh Network (DMN) for efficient control and energy savings.
Preview Honeywell Y8150/W8150 Fresh Air Ventilation System Installation and Operation Guide
Comprehensive guide to installing, configuring, and operating the Honeywell Y8150 Fresh Air Ventilation System and W8150 Ventilation Control for optimal indoor air quality, meeting ventilation codes like ASHRAE 62.2.
Preview Honeywell X45B Controller Card Product Guide
Product guide for the Honeywell X45B Controller Card, detailing its features, specifications, operational characteristics, installation, and ordering information for HVAC energy management systems.
Preview Honeywell INNCOM Direct Quick Start Guide
A quick start guide for installing and setting up the Honeywell INNCOM Direct HVAC control system. It covers compatibility checks, order intake, and installation procedures for thermostats, routers, and gateways.
Preview Honeywell INNCOM Direct Battery-Powered Sensor Installation Guide
Comprehensive installation guide for Honeywell's INNCOM Direct battery-powered sensors, including S541.RF, S541.RFT, S541.RFH, K594, and K595 models. Covers installation, mounting, binding, and testing procedures for room automation systems.
Preview Honeywell GoldTop Air Vent FV180, FV180A, FV183 Product Data
Product data and specifications for the Honeywell GoldTop Air Vent (models FV180, FV180A, FV183). Learn about its features, application, installation, and ordering information for this legacy HVAC component.