Honeywell INNCOM Direct D-X47 HVAC Controller
Honeywell's INNCOM Direct is an energy management system tailored to provide an all-in-one control and management for a hotel's guestroom and common area HVAC systems.
Product Overview
Out of the box, INNCOM Direct DX47 controller is an essential part of Honeywell's online HVAC solution designed to reduce energy usage in guestroom and common area, enabling hoteliers to reach sustainability goals faster. Additionally, INNCOM Direct provides the capability for portfolio management to optimize room and equipment performance to increase guest satisfaction and decrease operational costs.
The DX47 provides five relay outputs and a range of digital and analog I/O to control a wide variety of light duty HVAC systems. The DX47 is the companion to the wireless D1-529-6V battery powered thermostat, and uses INNCOM's low cost, self-forming RF mesh network for wireless communications, fast setup, and easy maintenance.
Features and Highlights
All-in-one system - both hardware and software
Property wide - both guestrooms and common areas
Occupancy and Scheduled Energy Savings
No system engineering or commissioning experience needed.
Part Numbers
DX47 Part Numbers
PART NUMBER
DESCRIPTION
D-X47-24
INNCOM DX47 HVAC Controller
Accessories Parts
PART NUMBER
DESCRIPTION
62-1511
DX47 Low voltage harness (H2, H5)
62-1465.B
DX47 Low voltage harness (H3, H4, H8, H9)
62-1464.R
DX47 24 VAC Harness
62-1467
DX47 Low Voltage Cable
13-4019
1/4 wave antenna for 2.4 Ghz RF transceiver
04-1095
External ruggedized thermistor
Dimensions
The DX47 controller has the following dimensions: Width: 2.83 inches (72 mm), Height: 4.09 inches (104 mm), Depth: 1.55 inches (39.6 mm). The mounting is designed for four 6/32" screws with a 1/2" thread length.
System Overview
The system overview illustrates a typical setup involving a Niagara Gateway, a Remote Building Manager, and various INNCOM devices. The network includes IP Ethernet and RF Network connections. Devices shown are D1-529 Thermostats and D-X47 HVAC Controllers, connected via a D-578 Edge Router. The system supports common areas and guest rooms, with connections to a network switch.
Legend: IP Ethernet, RF Network
Product Specifications
Electrical
PARAMETER
SPECIFICATION
Input Power
24 VAC 50/60 Hz, 2.4 VA
Class-2 Output (H9)
12 VDC 200 mA (The DX47 should not be used to provide more than 70 mA of external class-2 power)
S5bus I/O
+18 dBm
RF Transmit Power
-98 dBm
RF Receive Sensitivity
-98 dBm
Current Consumption
PARAMETER
DESCRIPTION
All relays actuated
130 mA Maximum Load (including logic board)
Environmental Specifications
PARAMETER
SPECIFICATION
Operating Temperature
32 °F to 104°F (0°C to 40 °C)
Storage Temperature
-40 °F to 158°F (-40 °C to 70°C)
Weight and Dimensions
PARAMETER
SPECIFICATION
Dimensions (W x H x D)
2.83 inches x 4.09 inches x 1.55 inches, (72 mm x 104 mm x 39.6 mm)
Shipping Weight
0.37 lbs (0.171 kg)
Mounting
4 hole mounting 6/32" bit, 1/2" screw
Relay Ratings
RELAY
RELAY RATING
PIN ASSIGNMENT
K1
1A sealed, 10A inrush, class 2 pilot duty
P4
K2
1A sealed, 10A inrush, class 2 pilot duty
P5
K3
1A sealed, 10A inrush, class 2 pilot duty
P10
K4
1A sealed, 10A inrush, class 2 pilot duty
P7
K5
1A sealed, 10A inrush, class 2 pilot duty
P6
Common 1
K1, K2, K3
P9
Common 2
K4, K5
P8
Typical HVAC Applications
4 pipe, 3 fan, heat/cool FCU
2 pipe, 3 fan, Cool only FCU
Heat Pump, 2 fan 2nd stage heat
Heat pump, 3 fan speeds
PTAC, 2 Fan with heat strip
K1
High Fan
High Fan
High Fan
High Fan
High Fan
K2
Medium Fan
Medium Fan
Medium Fan
Medium Fan
Medium Fan
K3
Low Fan
Low Fan
Low Fan
Low Fan
Low Fan
K4
Cool Signal
Cool Signal
Y-Compressor
Y-Compressor
Y-Compressor
K5
Heat Signal
Not Connected
B/O Reversing Valve
B/O Reversing Valve
W-Heat
Wired Communications & Digital/Analog IO
PIN
COLOR
TYPICAL FUNCTION
1
Brown
Common
2
Red
12 VDC Output/Input
3
Orange
S5bus Data
4
Yellow
Digital Input
5
Green
Not Connected
6
Blue
Not Connected
Wired External Temperature Sensors
External temperature sensor input: H3, H4
Standards and Approvals
UL 244A and CSA C22.2 No. 14. file E231654
FCC ID: 2A8LT-24DX47 (FCC Part 15 subpart B and C class B)
IC ID: 1609A-24DX47
Prop65: Hazardous substances (RoHS I + II), amended by (EU) 2015/863 (RoHS III)
Regulatory Information
This device compiles with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
hon-ba-bms-inncom-dx47-hvac-controller-datasheet-31-00719-01 ?download=false Adobe PDF Library 17.0
Related Documents
Honeywell INNCOM Direct D1-529 Wireless Thermostat Datasheet Datasheet for the Honeywell INNCOM Direct D1-529 wireless thermostat, an energy management system for hotel guestrooms and common areas, detailing its features, specifications, and applications.
Honeywell INNCOM Direct D-578 Edge Router Datasheet Datasheet for the Honeywell INNCOM Direct D-578 Edge Router, an energy management system for hotel guestroom and common area HVAC, featuring the INNCOM Deep Mesh Network (DMN) for efficient control and energy savings.
Honeywell X45B Controller Card Product Guide Product guide for the Honeywell X45B Controller Card, detailing its features, specifications, operational characteristics, installation, and ordering information for HVAC energy management systems.
Honeywell INNCOM Direct Quick Start Guide A quick start guide for installing and setting up the Honeywell INNCOM Direct HVAC control system. It covers compatibility checks, order intake, and installation procedures for thermostats, routers, and gateways.
Honeywell INNCOM Direct Battery-Powered Sensor Installation Guide Comprehensive installation guide for Honeywell's INNCOM Direct battery-powered sensors, including S541.RF, S541.RFT, S541.RFH, K594, and K595 models. Covers installation, mounting, binding, and testing procedures for room automation systems.
Honeywell GoldTop Air Vent FV180, FV180A, FV183 Product Data Product data and specifications for the Honeywell GoldTop Air Vent (models FV180, FV180A, FV183). Learn about its features, application, installation, and ordering information for this legacy HVAC component.