REGIN IO-16DI Distributed I/O
Distributed I/O module for expanding Regin's programmable controllers EXOflex, EXOcompact, and EXOdos.
Product Overview
The IO-16DI is an I/O module designed to expand Regin's programmable controllers, including EXOflex, EXOcompact, and EXOdos. It facilitates easy system expansion by providing 16 additional inputs per controller.
Key Features:
- Simple wiring
- Easy to install in a standard casing
Functionality
The IO-16DI enables straightforward expansion of a system with 16 additional inputs per controller. Communication is managed via EXOline or CAN-Bus protocols. The desired protocol is selected using DIP switches.
Inputs
The IO-16DI features 16 digital inputs (DI) that support pulse counting. Each input is equipped with an LED indicator for status visualization.
Input Configuration:
Digital inputs (DI) are configured as potential-free closing contacts between +C and DI. They can also be configured for 24 V DC operation and as pulse inputs.
Technical Data
Parameter | Value |
---|---|
Supply voltage | 24 V AC ±15%, 50 Hz |
Power consumption | Max. 3.5 VA |
Communication | EXOline, CAN-bus |
Communication speed (EXOline) | 9600 bps |
Communication speed (CAN-bus) | 20000 bps |
Operating temperature | 0...50°C |
Storage temperature | -20...+70°C |
Ambient humidity (operation) | Max. 90% RH |
Protection class | IP20 |
Mounting | DIN-rail or in a standard casing |
Dimensions (WxHxD) | 148 x 123 x 60 mm (incl. terminals) |
DIN-rail module width | 148 x 123 x 60 mm (incl. terminals) |
Wiring Information
The module features terminals for supply voltage, digital inputs, and communication interfaces (EXOline/CAN-bus).
Terminal Connections:
Terminal | Description | Function |
---|---|---|
1 | G (F24~)/+ | Supply voltage 24 V AC |
2 | G (F24~)/+ | Supply voltage 24 V AC |
12 | DI9 | Digital input 9 |
13 | +C | 24 V DC for all digital inputs |
14 | DI10 | Digital input 10 |
15 | DI11 | Digital input 11 |
16 | +C | 24 V DC for all digital inputs |
17 | DI12 | Digital input 12 |
22 | DI13 | Digital input 13 |
23 | +C | 24 V DC for all digital inputs |
24 | DI14 | Digital input 14 |
25 | DI15 | Digital input 15 |
26 | +C | 24 V DC for all digital inputs |
27 | DI16 | Digital input 16 |
30 | B | EXOline RS485 |
31 | A | EXOline RS485 |
32 | N | EXOline RS485 / CAN ground |
33 | E | EXOline RS485 Send/Receive alternating |
34 | CL | CAN-Low |
35 | CH | CAN-High |
42 | DI1 | Digital input 1 |
43 | +C | 24 V DC for all digital inputs |
44 | DI2 | Digital input 2 |
45 | DI3 | Digital input 3 |
46 | +C | 24 V DC for all digital inputs |
47 | DI4 | Digital input 4 |
52 | DI5 | Digital input 5 |
53 | +C | 24 V DC for all digital inputs |
54 | DI6 | Digital input 6 |
55 | DI7 | Digital input 7 |
56 | +C | 24 V DC for all digital inputs |
57 | DI8 | Digital input 8 |
Dimensions
The module has dimensions of 148 x 123 x 60 mm (Width x Height x Depth), including terminals.
A diagram illustrating the module's physical dimensions and terminal layout is provided.
Documentation
Further documentation for the IO-16DI module can be downloaded from the Regin website: www.regincontrols.com.