Regin IO-8DO8AI-M Distributed I/O Module
IO module for expanding Regin's programmable controllers EXOflex, EXOcompact and EXOdos.
- Simple wiring
- Easy to install in a standard casing
- Built-in relays
- Control switches on the front panel
Function
The IO-8DO8AI-M enables easy expansion of a system by 16 additional in-/outputs per controller. All outputs can be controlled manually. Communication takes place via EXOline or CAN-Bus. The protocol used is set via DIP switches.
Inputs and Outputs
The IO-8DO8AI-M has 8 inputs and 8 outputs.
8 Digital Outputs
Features manual switches, LEDs, and potential-free closing contacts.
8 Analogue Inputs
Supports PT1000, Ni1000 (only CAN-Bus), microsensors, 0-10 V, 0-20 mA, and 0-10 kΩ.
Technical Data
Parameter | Specification |
---|---|
Supply voltage | 24 V AC ±15 %, 50 Hz |
Power consumption | Max. 3.5 VA |
Communication | EXOline, CAN-bus |
Communication speed (EXOline) | 9600 bps |
Communication speed (CAN-bus) | 20000 bps |
Operating temperature | 0–50 °C |
Storage temperature | -20–+70 °C |
Ambient humidity (operation) | Max. 90 % RH |
Protection class | IP20 |
Mounting | DIN-rail or in a standard casing |
Dimensions (WxHxD) | 148 x 123 x 74 mm (incl. terminals) |
DIN-rail module width | 8.5 |
Inputs and Outputs Specifications
Type | Specification |
---|---|
Analogue inputs (AI) | PT1000, Ni1000 (only CAN-Bus), microsensors, 0–10 kΩ, 0–10 V, 0(4)–20 mA |
Digital outputs (DO) | Potential-free relay (closing), 24 / 230 V AC (not mixable), max. 1 A inductive load or 4 A resistive load |
Note: The relays have an estimated limit of 10,000 operations and should not be used with 3-point actuators or equivalent equipment.
This product carries the CE-mark. More information is available at www.regincontrols.com.
Wiring
The following table details the terminal connections:
Terminal | Description | Function |
---|---|---|
1 | G (F24~)/+ | Supply voltage 24 V AC |
2 | G0 (F24 )/- | Supply voltage 24 V AC |
12 | AI9 | Analogue input 9 |
13 | Agnd | Reference for all analogue inputs |
14 | AI10 | Analogue input 10 |
15 | AI11 | Analogue input 11 |
16 | Agnd | Reference for all analogue inputs |
17 | AI12 | Analogue input 12 |
22 | AI13 | Analogue input 13 |
23 | Agnd | Reference for all analogue inputs |
24 | AI14 | Analogue input 14 |
25 | AI15 | Analogue input 15 |
26 | Agnd | Reference for all analogue inputs |
27 | AI16 | Analogue input 16 |
30 | B | EXOline RS485 |
31 | A | EXOline RS485 |
32 | N | EXOline RS485 / CAN ground |
33 | E | EXOline RS485 Send/Receive alternating |
34 | CL | CAN-Low |
35 | CH | CAN-High |
40 | DO1 | Digital output 1; closing contact, normally open |
41 | NO1 | Supply for DO1 |
42 | DO2 | Digital output 2; closing contact, normally open |
43 | NO2 | Supply for DO2 |
44 | DO3 | Digital output 3; closing contact, normally open |
45 | NO3 | Supply for DO3 |
46 | DO4 | Digital output 4; closing contact, normally open |
47 | NO4 | Supply for DO4 |
50 | DO5 | Digital output 5; closing contact, normally open |
51 | NO5 | Supply for DO5 |
52 | DO6 | Digital output 6; closing contact, normally open |
53 | NO6 | Supply for DO6 |
54 | DO7 | Digital output 7; closing contact, normally open |
55 | NO7 | Supply for DO7 |
56 | DO8 | Digital output 8; closing contact, normally open |
57 | NO8 | Supply for DO8 |
Dimensions
The module dimensions are 148 x 123 x 74 mm (WxHxD) including terminals. The DIN-rail module width is 8.5.
A visual representation of the module's dimensions is provided, showing its overall size and mounting compatibility.
Documentation
All documentation for the IO-8DO8AI-M can be downloaded from www.regincontrols.com.