First Alert ReadyGuard-R Series

Quick Start Guide for ReadyGuard-R and ReadyGuard-REN

Brand: First Alert PROFESSIONAL SECURITY SYSTEMS®

Introduction

This Quick Start Guide can help you install the rechargeable ReadyGuard-R and ReadyGuard-REN quickly and easily by providing the basic steps for installation using the built-in defaults. For more detailed information and important notes, refer to the ReadyGuard-R Series Installation Instructions.

The following steps assume that one of the system's default tables will be used. For programming data values and Powerline Carrier Devices other than those listed in the default tables, see the Installation Instructions.

Default Table Summary

Zone Table 1 Table 2 Table 3 Table 4
1front doorfront doorfront doorfront door
2front doorfront doorfront doorfront door
3back doorback doorback doorback door
4windowwindowwindowwindow
5motion detectorwindowwindowwindow
6smoke detectorwindowwindowwindow
7windowwindowwindow
8motion detectormotion detectormotion detector
9smoke detectorsmoke detectorsmoke detector
26loop 3 arm awayloop 3 arm awayloop 3 arm awayloop 3 arm away
27loop 2 disarmloop 2 disarmloop 2 disarmloop 2 disarm
28loop 4 arm stayloop 4 arm stayloop 4 close deviceloop 4 close device
29loop 1 restore device 1loop 1 restore device 1loop 1 restore device 1loop 1 restore device 1
30loop 3 arm awayloop 3 arm awayloop 3 arm awayloop 3 arm away
31loop 2 disarmloop 2 disarmloop 2 disarmloop 2 disarm
32loop 4 arm stayloop 4 arm stayloop 4 close deviceloop 4 close device
33loop 1 restore device 1loop 1 restore device 1loop 1 restore device 1loop 1 restore device 1
92duressduressduressduress
99silent alarmaudible alarmsilent alarmsilent alarm

Master User Code: 1-2-3-4

Installer Code: 4-1-1-2

Duress Code: ------

Entering Program Mode: Installer Code + 800

Interactive Mode:

Exiting Program Mode: *99 allows re-entry into the Program mode using Installer Code + 800. *98 inhibits re-entry into the Programming mode using the Installer Code.

Notes:

Installation and Electrical Connections

  1. Step 1: Install the control

    a. Separate the front assembly from the back plate and disconnect the cable from the front assembly board. Note: Disconnect the cable only from the front assembly board, not from the terminal block PC board.

    b. Mount the back plate.

  2. Step 2: Make wiring connections

    a. Connect the incoming phone line to either the 8-position jack or terminals 2 (TIP) and 3 (RING).

    b. Connect the handset phone lines to either the RJ11 jack or terminals 4 (TIP) and 5 (RING). Note: For full line seize operation, see the installation instructions.

    c. If used, connect a piezo sounder to terminals 10 ([+] ) and 11 ([–]).

    d. If used, connect a bell to terminals 11 ([–]) and 12 ([+]).

    e. If using Powerline Carrier Devices, connect com/data/sync/ lines from the 1332X10 transformer to terminals 9, 13, and 14 respectively. Note: Install Powerline Carrier Devices according to their instructions.

    f. Connect wires from the 1332/1332X10 (1332CN) AC Transformer to terminals 15 and 16.

    Diagram Description: The diagram shows the back plate of the security system with various terminals labeled 1 through 16. It illustrates connections for phone lines, sounders, bells, powerline carrier devices, and the AC transformer. Key components like the battery receptacle and wiring terminals are also indicated.

  3. Step 3: Make battery connections

    a. Remove battery retainer.

    b. Remove backing from tape on back plate.

    c. Insert battery pack into back plate.

    d. Install battery retainer.

    e. Connect battery connector to receptacle on terminal block PC board.

    f. Carefully reconnect the ribbon cable to the front assembly PC board connector (properly aligning the red wire).

    g. After all wiring connections have been made, snap the front assembly to the back plate so it is held by the locking tabs.

    h. Plug the transformer into a 24-hour, 110VAC unswitched outlet. Note: Rechargeable batteries may take up to 48-hours to fully charge. "LOW BAT" message should clear within four hours, or by entering Test Mode.

    Diagram Description: Two diagrams illustrate the physical installation of the battery pack and the connection of the front assembly to the back plate. One shows the battery pack being inserted into the back plate with a retainer. The other shows the front assembly being connected to the back plate, highlighting the ribbon cable connection and locking tabs.

System Programming

Warning: TO PREVENT RISK OF SHOCK, DISCONNECT TELEPHONE LINE AT TELECOM JACK BEFORE SERVICING THIS UNIT. ALL OUTPUT CIRCUITS ARE POWER LIMITED.

Certain features differ between the ReadyGuard-R and the ReadyGuard-REN models. Verify the specific model being installed prior to the system programming.

  1. Step 1: Set a programming default

    a. Enter Programming mode: Installer Code + 800.

    b. Press *97, then press a number 1-4 to select a default table from the tables listed on page 1.

  2. Step 2: Program the variable data fields

    a. RF House ID - Press *24, then enter the desired 2-digit RF House ID for wireless keypads.

    b. PABX Access Code (if used) - Press *40, then enter up to 6 digits. If fewer than 6 digits are used, press [*] to end the field and advance to the next field.

    c. Primary Phone Number - Press *41, then enter the primary phone number, up to 20 digits. If fewer than 20 digits are used, press [*] to end the field and advance to the next field.

    d. Secondary Phone Number (if used) - Press *42, then enter the secondary phone number, up to 24 digits. If fewer than 24 digits are used, press [*] to end the field and advance to the next field.

    e. Secondary Account Number (if used) - Press *44, then enter the secondary account number. If only 3 digits are used, press [*] to end the field and advance to the next field.

    f. Pager Characters - Press *88 if using Default Table 2 or 4, then enter up to 16 digits which may be required by your pager service (e.g. account number, PIN, etc.). If fewer than 16 digits are used, press [*] to end the field and advance to the next field.

    g. Download Phone Number - Press *94, then enter the downloading computer phone number, up to 20 digits. If fewer than 20 digits are used, press [*] to end the field.

  3. Step 3: Enhanced Sequential Mode

    Press *83, then follow the prompts:

    a. Zone Number: Enter 2-digit zone number. The system will announce the Voice Descriptor for the selected zone number, if programmed. Press [*] to continue. The system searches for the first transmitter with pre-programmed attributes: correct input type (*56), correct loop number (*56), no serial number programmed, and zone type.

    Note 1: If the first zone number entered does not meet the criteria, the system searches its database for the first zone that does and displays it at the ENROLL SERIAL NUMBER prompt.

    Note 2: Pressing 00 exits mode, and the prompt "83" blinks, indicating the mode is inactive.

    b. Enroll Mode: If "L" is displayed, the serial number has already been entered and can be confirmed, viewed, or deleted.

    • If the transmitter's serial number has not been previously entered, press "1" to enter enroll serial number mode, or press "2" to copy the last entered serial number.
    • If the serial number has been previously entered, press "3" to view or "9" to delete.
    • Note: When viewing, each digit is re-displayed, and the keypad beeps once for digits 1-6, and three times for the last digit.
    • Once the serial number is entered, the system returns to the (1A) prompt with "L" displayed.
    • This point can be faulted and restored, and the panel listens for transmission.
    • The serial number/loop number combination can be confirmed by faulting and restoring the zone. If the panel receives a matching transmission, it beeps three times, and "C" is displayed, indicating confirmation. No further transmissions are needed.
    • Note: When confirming a 4-button key, it's assumed all loops are used and only the serial number is confirmed. Pressing any key allows confirmation. Two beeps indicate acceptance; a single long beep indicates illegal entries or duplicate serial number/loop entry.
    • When the last zone is entered, the display remains on that zone. To exit and return to data field program mode, press 00 at the ZONE NUMBER prompt.
    • Once all zones are programmed, test each zone using the system's Test mode. Do not use the Transmitter ID Sniffer mode, as it only checks for transmission of one zone on a particular transmitter, not all assigned zones.

    c. Serial Number: This prompt enrolls the transmitter serial number via RF transmission or manually. If using RF Learning, proceed to c.1). If using manual mode, skip to c.2).

    1) RF Learning: Two (2) transmissions (key depressions at least five seconds apart) are required for BR type, or four (4) transmissions (fault, restore, fault, restore) for UR or RF type. BR type devices can only be enrolled by BR devices; UR and RF devices by UR or RF devices.

    Note: If the learned serial number has a different loop number than entered in *56, the system announces the Voice Descriptor (if programmed), followed by two beeps, and returns to Prompt (1A) with "L" displayed. If the loop number matches, the system announces the Voice Descriptor (if programmed), followed by three beeps, and returns to Prompt (1A) with "LC" displayed.

    Note: BR type devices can only be enrolled by transmission from BR devices. Likewise, UR and RF devices can only be enrolled by transmission from a UR or RF device.

    2) Manual Entry: Enter the 7-digit serial number printed on the transmitter. If an incorrect digit is entered, press the [#] key to backup to prompt (1A) and start over. When all seven digits are entered, press the [*] key.

    Note: If less than 7 digits are entered, the keypad emits a single long beep and returns to the (1A) prompt without displaying "L". If more than 7 digits are entered, the first 6 digits are saved along with the last entered digit (e.g., 123456789 yields 1234569). If 52 seconds pass with no entry, the system returns to prompt (1A).

    d. Delete Serial Number: This prompt deletes the serial number programmed for the zone. Enter "0" to discard or "1" to confirm.

  4. Step 4: Set RF House ID in wireless keypads

    a. 5827 wireless keypad - Set DIP switches to the RF House ID programmed in field *24.

    b. 5804BD button key - Set the RF House ID per its instructions.

    c. Powerline Carrier Devices - Set their House ID to "A," (programmed as "0") or use field *25 to change the ID to avoid conflicts with existing installations.

  5. Step 5: Set the Real-Time Clock

    a. Enter time/date setting mode: User Code + FUNCTION + [63].

    b. The hour prompt is displayed. Enter the correct hour, then press [*] to accept and advance.

    c. For each subsequent prompt, enter the correct value, then press [*].

    d. The system exits this mode automatically after entering the year, or if no keys are pressed for 1 minute.

  6. Step 6: Test the system

    a. After installation and programming, enter Installer Code + TEST.

    b. To exit Test mode, enter Installer Code + OFF.

  7. Step 7: Assign User Codes

    Assign desired User Codes by following the procedures on the next page and in the User Guide. Show the user how to perform the various system functions.

  8. Step 8: Perform site-initiated downloader session

    Load central station ID by Installer Code + [#] + [1].

Diagram Description: The "5800 Series Transmitter Loop Numbers" section contains illustrations of various transmitters (e.g., 5800RL, 5801, 5802 MN, 5804, 5804BD, 5806/5807/5808/5808LST, 5814, 5816, 5817, 5818, 5819, 5827, 5849, 5850, 5890/5890PI) with their associated input types and loop designations indicated. Some transmitters are marked as not intended for UL installations.

Keypad Functions (when default programming is used)

Security Functions

Message Center

Volume Control

Other Functions

Remote Phone Control Operation

Speaker Phone Operation (ReadyGuard-REN Only)

(Note: The ARMED and READY LEDs blink alternately when the Speaker Phone feature is active)

Note: The Babysitter Code and Installer Code cannot disarm the system unless it was the code used to arm the system. In addition, if the system is armed by pressing and holding the Quick-Arm buttons, neither the Babysitter Code nor the Installer Code can disarm the system.

Final Notes

REFER TO THE INSTALLATION AND SETUP GUIDE FOR THE LIMITATIONS OF THIS SYSTEM AND WARRANTY INFORMATION.

Company Information: First Alert PROFESSIONAL SECURITY SYSTEMS®, 175 Eileen Way, Syosset, New York 11791, http://firstalertpro.com, Copyright © 2001

PDF preview unavailable. Download the PDF instead.

ReadyGuard-R Quick Start Guide Acrobat Distiller 4.0 for Windows

Related Documents

Preview First Alert ReadyGuard-R and ReadyGuard-REN Programming Guide
This programming guide provides detailed instructions for configuring the First Alert ReadyGuard-R and ReadyGuard-REN security systems, covering zone programming, device setup, and system settings.
Preview First Alert ReadyGuard Quick Start Guide
A quick start guide for installing the First Alert ReadyGuard security system, covering basic installation steps, default table configurations, and keypad functions.
Preview First Alert FA1600C/CA/CB Programming Guide
A comprehensive programming guide for the First Alert FA1600C/CA/CB Fire and Burglary Partitioned Security Systems with Scheduling. This document details system-wide and partition-specific programming fields, commands, and procedures for setting up and configuring the security system.
Preview First Alert 1200C Installation and Programming Guide
This document provides detailed installation and programming notes for the First Alert 1200C security system, including installer codes, response types, downloading information, and system configuration options.
Preview First Alert FA2100C Programming Form
A programming form for the First Alert FA2100C alarm system, detailing fields for system setup, miscellaneous options, dialer programming, zone assignments, report codes, and download information. This document guides users through configuring various parameters of the alarm system.
Preview First Alert Professional Security System User's Manual
User's manual for the First Alert Professional Security System, covering installation, operation, and maintenance of Alpha Display and Fixed Word Display consoles, including features like arming/disarming, zone bypassing, and emergency functions.
Preview First Alert FA2000C Control/Communicator Installation Instructions
Comprehensive installation guide for the First Alert FA2000C Control/Communicator, detailing setup, wiring, programming, and system operation for professional security systems.
Preview First Alert Professional Home Security Systems: Personalized, Smart, and Expertly Installed
Discover First Alert's professional home security systems, offering personalized solutions, smart home integration, advanced video monitoring, and expert installation for enhanced safety and convenience. Manage your home from anywhere with the Total Connect 2.0 app.