Cooper&Hunter CH-REL30-230VO + CH-RS30MAHU
Brand: Cooper&Hunter
Key Features
- Auto restart
- Quiet operation
- Multiple fan speeds
- Auxiliary heater
- Adjustable static pressure
- Multi position
- Fast cool/heat function
- Aluminium coil
- WIFI ready
- Refrigerant leak detect
Certifications
- R454B CERTIFIED
- ENERGY STAR
- AHRI CERTIFIED
- NE
- Intertek
- TU1
- GoldFin
- INVERTER
Product Overview
The Cooper&Hunter CH-REL30-230VO + CH-RS30MAHU is a split system air conditioner designed for efficient cooling and heating. The system comprises an indoor unit (CH-RS30MAHU) and an outdoor unit (CH-REL30-230VO).
Indoor Unit Description: The indoor unit is a tall, rectangular cabinet in a grey finish, featuring visible vents or grilles on its front and sides for airflow intake and output, along with access panels. It is designed for installation within a building's conditioned space.
Outdoor Unit Description: The outdoor unit is a rectangular, grey unit designed for external placement. It features a prominent circular fan grille on its top surface and side panels with fins for heat exchange. This unit houses the compressor and other components responsible for heat rejection or absorption.
Indoor Unit Specifications (CH-RS30MAHU)
Specification | Value |
---|---|
Indoor Model | CH-RS30MAHU |
Power supply | 208-230V, 1Ph, 60Hz |
Communication wiring | AWG 14-4 |
Cooling Capacity | 30,000 Btu/h (9,200~34,000) |
Cooling Input | 2,730 W (300~3,400) |
Cooling Rated current | 12.5 A (2.51~15) |
EER/EER2 | 11 Btu/w |
SEER/SEER2 | 17 Btu/w |
Heating Capacity | 30,000 Btu/h (8,500~33,000) |
Heating Input | 2,440 W (370~2,700) |
Heating Rated current | 11.2 A (2.92~11.9) |
COP | 3.6 W/W |
HSPF4/HSPF2-4 | 8.7 |
HSPF5/HSPF2-5 | 7 |
Indoor fan motor Qty | 1 |
Indoor fan motor Input | 375 W |
Indoor fan motor RLA | 4.5 A |
Indoor air flow (Turbo/Hi/Med/Lo) | 988.8 / 894.7 / 806.4 / 712.2 CFM |
ESP (range) | 0-0.8 In.wg. |
Indoor noise level (Hi/Med/Lo) | 44/41/26 dB(A) |
Dehumidification | 7.4 Pnt/H |
Indoor unit Dimensions (WxDxH) | 21.02 x 21.02 x 49.02 inch |
Indoor unit Packing (WxDxH) | 24.41 x 26.57 x 52.56 inch |
Indoor unit Net/Gross weight | 127.43/151.68 lbs |
Drainage water pipe diameter | 3/4" inch |
Refrigerant piping (Liquid side/Gas side) | 3/8"/5/8" inch |
Design pressure | 550/340 PSIG |
Controller | Wire controller + remote controller available |
Room temperature Cooling | 60~90 F |
Room temperature Heating | 32~86 F |
Outdoor Unit Specifications (CH-REL30-230VO)
Specification | Value |
---|---|
Outdoor Model | CH-REL30-230VO |
Power supply | 208-230V, 1Ph, 60Hz |
Min. circuit ampacity | 28 A |
Max. fuse | 30 A |
Compressor Model | KTF250D22UMT |
Compressor Type | ROTARY |
Compressor Brand | GMCC |
Compressor Capacity | 27,620 Btu/h |
Compressor Input | 2,200 W |
Compressor Rated current (RLA) | 17.5 A |
Refrigerant oil | VG74 22.7 oz |
Outdoor fan motor Qty | 1 |
Outdoor fan motor Input | 120 W |
Outdoor fan motor RLA | 1.3 A |
Outdoor fan motor Speed | 900/700/500 r/min |
Outdoor air flow (Max) | 2,236.7 CFM |
Outdoor noise level (Max) | 61 dB(A) |
Throttle type | EXV+Capillary |
Outdoor unit Dimensions (WxDxH) | 37.24 x 16.14 x 31.89 inch |
Outdoor unit Packing (WxDxH) | 42.91 x 19.68 x 34.84 inch |
Outdoor unit Net/Gross weight | 142.86/154.54 lbs |
Refrigerant Type | R454B |
Refrigerant Precharge | 25 ft |
Additional charge for 1/4 inch liquid pipe | 0.32 oz |
Refrigerant piping (Liquid side/Gas side) | 3/8"/5/8" inch |
Refrigerant piping Max. pipe length | 164 ft |
Refrigerant piping Max. difference in level | 82 ft |
Ambient temperature Cooling | -13 ~ 122 F |
Ambient temperature Heating | -13 ~ 75 F |
Unit Dimensions and Piping Details
Indoor Unit Piping Plate Diagram Description
This diagram details the piping and connections on the indoor unit. It shows a 'PIPING PLATE' with labeled connection points for 'SUCTION LINE' and 'LIQUID LINE' using 3/8" and 5/8" flare connections respectively. It illustrates multiple 'CONDENSATE DRAINS' for horizontal, upflow, and downflow configurations, with primary and secondary (emergency) drain pipes specified as 3/4" FPT. The diagram also indicates 'FILTER ACCESS' and a 'FILTER COVER', as well as a 'CIRCUIT BREAKER COVER' for auxiliary heater connections. Various inlet points for electrical wiring are marked, including 'LOW VOLTAGE INLETS' and 'LINE VOLTAGE INLETS', with notes specifying that strong electricity and communication wires should not use the same knock hole.
Indoor Unit Airflow and Electrical Inlet Description
The indoor unit features a 'SUPPLY AIR OPENING' for conditioned air distribution. It also has designated 'LOW VOLTAGE INLETS' (located on the top and left side) and 'LINE VOLTAGE INLETS' (located on the top and right side) for electrical connections. A note indicates that separate knock holes should be used for strong electricity wiring and communication wiring.
Outdoor Unit Dimensions Description
This diagram provides the external dimensions for the outdoor unit in both inches and millimeters. It includes side views showing height (31-7/8in / 810mm) and depth (16-1/8in / 410mm), and front views showing width (37-1/4in / 946mm) and height (26-1/2in / 673mm). A top view is also provided, showing the overall width (40-1/2in / 1030mm) and depth (15-1/4in / 386mm). Detail A illustrates mounting hole dimensions, showing slots for securing the unit.