Nortek Global HVAC, LLC

Owner's Manual

Installation Instructions

Mini Split Heat Pump Systems

Outdoor Units

Safety Precautions

WARNING: This symbol indicates the possibility of death or serious injury.

CAUTION: This symbol indicates the possibility of injury or damage to property.

NOTICE: Indicates important but not hazard-related information, used to indicate risk of property damage.

Installation

Installation (Continued)

Operation and Maintenance

Parts Name

Outdoor Unit

The outdoor unit has an air inlet and an air outlet.

Installation Notice

WARNING: When installing or relocating the unit, ensure the refrigerant circuit is free from air or substances other than the specified refrigerant. The presence of air or other foreign substances can cause system pressure rise or compressor rupture, resulting in injury.

When installing or moving the unit, do not charge with non-compliant or unqualified refrigerant. This may cause abnormal operation, malfunction, or safety accidents.

When refrigerant needs to be recovered during relocation or repair, ensure the unit is in cooling mode. Fully close the high-pressure (liquid) valve, then after 30-40 seconds, fully close the low-pressure (gas) valve. Stop the unit and disconnect power immediately. Refrigerant recovery should not exceed 1 minute. If it takes too long, air may be sucked in, causing pressure rise or compressor rupture.

During refrigerant recovery, ensure both valves are fully closed and power is disconnected before detaching the connection pipe. If the compressor runs with stop valves open and pipes not connected, air may be sucked in.

When installing the unit, ensure the connection pipe is securely connected before the compressor starts. If the compressor runs with stop valves open and pipes not connected, air may be sucked in.

Do not install the unit where corrosive or flammable gas may leak, as this could cause explosions.

Do not use extension cords for electrical connections. If the wire is not long enough, contact an authorized service center. Poor connections can lead to electric shock or fire.

Use specified wire types for electrical connections between indoor and outdoor units. Ensure terminals are securely clamped and free from external stress. Insufficient capacity wires, incorrect connections, or insecure terminals can cause electric shock or fire.

Tools for Installation

Selection of Installation Location

Basic Requirement

Installing the unit in the following locations may cause malfunction. If unavoidable, consult the local dealer:

Outdoor Unit

Safety Precaution (Installation)

Requirements for Electric Connection

Grounding Requirement

Installation of Outdoor Unit

Step 1: Fix the support of outdoor unit

Select installation location based on house structure. Fix the support of the outdoor unit on the selected location using expansion screws.

NOTICE: Take sufficient protective measures. Ensure the support can withstand at least four times the unit's weight. The outdoor unit should be installed at least 1.18" above the floor for drain joint installation (or 7.87" if heating tube is included). The number of expansion screws required varies by cooling capacity: 2300W-5000W need 6 screws; 6000W-8000W need 8 screws; 10000W-16000W need 10 screws.

Step 2: Install drain joint (for some models)

Connect the outdoor drain joint to the chassis hole and then connect the drain hose to the drain vent.

NOTICE: Refer to the current product for the drainage joint shape. Do not install the drainage joint in areas with severe cold, as it may freeze and cause malfunction.

Step 3: Fix outdoor unit

Place the outdoor unit on the support and fix the foot holes with bolts.

Step 4: Connect indoor and outdoor pipes
  1. Remove the screw on the right handle of the outdoor unit and remove the handle.
  2. Remove the screw cap of the valve and align the pipe joint with the bellmouth of the pipe.
  3. Pretighten the union nut by hand.
  4. Tighten the union nut with a torque wrench according to the provided table (Hex nut diameter vs. Tightening torque).
Step 5: Connect outdoor electric wire

Remove the wire clip. Connect the power connection wire and signal control wire (for cooling and heating units) to the wiring terminal according to color. Fix with screws. Secure the power and signal control wires with the wire clip. After tightening the screw, pull the power cord gently to check firmness. Never cut the power connection wire to adjust its length.

Step 6: Neaten the pipes
  1. Place the pipes along the wall, bent reasonably, and hidden. The minimum bending radius is 4".
  2. If the outdoor unit is higher than the wall hole, create a U-shaped curve in the pipe before it enters the room to prevent rain from entering.

NOTICE: The through-wall height of the drain hose should not be higher than the outlet pipe hole of the indoor unit. The water outlet should not be placed in water. Slant the drain hose slightly downwards; avoid curves, upward bends, or fluctuations.

Test and Operation

Use vacuum pump
  1. Remove valve caps and refrigerant charging vent nut.
  2. Connect the piezometer's charging hose to the gas valve's charging vent and the other hose to the vacuum pump.
  3. Open the piezometer fully and operate for 10-15 minutes to check if the pressure remains at -0.1MPa.
  4. Close the vacuum pump and maintain this status for 1-2 minutes. If pressure decreases, there may be a leakage.
  5. Remove the piezometer and fully open the valve cores of the liquid and gas valves using an inner hexagon spanner.
  6. Tighten the screw caps of valves and the refrigerant charging vent.
  7. Reinstall the handle.

Leakage detection

Test operation

Check after installation

Items to be checked Possible malfunction
Has the unit been installed firmly? The unit may drop, shake, or emit noise.
Have you done the refrigerant leakage test? It may cause insufficient cooling/heating capacity.
Is heat insulation of pipeline sufficient? It may cause condensation and water dripping.
Is water drained well? It may cause condensation and water dripping.
Is the voltage of power supply according to the voltage marked on the nameplate? It may cause malfunction or damage the parts.
Is electric wiring and pipeline installed correctly? It may cause malfunction or damage the parts.
Is the unit grounded securely? It may cause electric leakage.
Does the power cord follow the specification? It may cause malfunction or damage the parts.
Is there any obstruction in the air inlet and outlet? It may cause insufficient cooling/heating capacity.
Are dust and sundries caused during installation removed? It may cause malfunction or damage the parts.
Are the gas and liquid valves of the connection pipe open completely? It may cause insufficient cooling (heating) capacity.
Is the inlet and outlet of piping hole covered? It may cause insufficient cooling (heating) capacity or waste electricity.

Configuration of connection pipe

1. Standard length of connection pipe: 16.4', 24.6', 26.25'.

2. Minimum length of connection pipe is 10'.

3. Maximum length of connection pipe is shown in the table.

Cooling capacity Maximum length of connection pipe (ft)
5000Btu/h (1465W) 49
7000Btu/h (2051W) 49
9000Btu/h (2637W) 49
12000Btu/h (3516W) 65.6
18000Btu/h (5274W) 82
24000Btu/h (7032W) 82
28000Btu/h (8204W) 98.4
36000Btu/h (10548W) 98.4
42000Btu/h (12306W) 98.4
48000Btu/h (14064W) 98.4

Additional refrigerant charging amount for R410A

Model SKU# Standard Line Set Length Additional Refrigerant charge (oz/ft)
GXH09(2.6)LSA4DL2 1042163 24.6' 0.2
GXH12(3.5)LSA4DL2 1042165 24.6' 0.2
GXH09(2.6)LSK4DL2 1044143 24.6' 0.2
GXH12(3.5)LSK4DL2 1044144 24.6' 0.2
GXH18(5.3)LSK4DL2 1044145 24.6' 0.2
GXH24(7.0)LSK4DL2 1044146 24.6' 0.5
GXH09(2.6)LSK4DH2 1044154 24.6' 0.2
GXH12(3.5)LSK4DH2 1044155 24.6' 0.2
GXH18(5.3)LSK4DH2 1044156 24.6' 0.5
GXH24(7.0)LSK4DH2 1044157 24.6' 0.5
GXH30(8.8)LSK4DH2 1044147 24.6' 0.5
GXH36(10.6)LSK4DH2 1044158 24.6' 0.5

4. Additional refrigerant oil and refrigerant charging is required after prolonging the connection pipe.

Pipe expanding method

NOTICE: Improper pipe expanding is the main cause of refrigerant leakage. Please expand the pipe according to the following steps:

A: Cut the pipe

Confirm the pipe length according to the distance between the indoor unit and outdoor unit. Cut the required pipe with a pipe cutter. Ensure the cut is perpendicular, without leaning, unevenness, or burrs.

B: Remove the burrs

Remove burrs with a shaper and prevent them from entering the pipe. Ensure a smooth inner surface.

C: Put on suitable insulating pipe

Apply insulating pipe to the pipe.

D: Put on the union nut

Remove the union nut on the indoor connection pipe and outdoor valve, then install the union nut on the pipe.

E: Expand the port

Expand the port with an expander. Ensure the length is equal and the surface is smooth.

NOTICE: "A" (expansion depth) varies by diameter. Refer to the sheet below.

Outer diameter (inch) Max Min
Φ6 - 6.35(1/4") .05" .027"
Φ9 - 9.52(3/8") .06" .039"
Φ12-12.7(1/2") .070" .039"
Φ15.8-16(5/8") .09" .086"
F: Inspection

Check the quality of the expanding port. If there are any blemishes, re-expand the port according to the steps above.

Working temperature range

Various model numbers are listed with their corresponding indoor and outdoor side temperature ranges (DB/WB in °C/°F).

NOTE: The operating temperature range (outdoor temperature) for cooling is -18°C(0°F) to 48°C(118°F); for heat pump units, it is -25°C(-13°F) to 48°C(118°F).

Models: GXH09 2.6 LSA4DL2, GXH12 3.5 LSA4DL2, GXH09 2.6 LSK4DL2, GXH12 3.5 LSK4DL2, GXH18 5.3 LSK4DL2, GXH24 7.0 LSK4DL2, GXH09 2.6 LSK4DH2, GXH12 3.5 LSK4DH2, GXH24 7.0 LSK4DH2, GXH30 8.8 LSK4DH2, GXH36 10.6 LSK4DH2, GXH09 2.6 LSA4DL2 Mini Split Heat Pump Systems, Mini Split Heat Pump Systems, Split Heat Pump Systems, Heat Pump Systems, Pump Systems

File Info : application/pdf, 20 Pages, 2.19MB

PDF preview unavailable. Download the PDF instead.

905f

References

Adobe Illustrator CS6 (Windows) Adobe PDF library 10.01

Related Documents

Preview Nortek Global HVAC Split System Heat Pump Owner's Manual & Installation Guide
This comprehensive manual provides essential guidance for the installation, operation, and maintenance of Nortek Global HVAC's 16 SEER Split System Heat Pumps. It details model specifications, safety precautions, troubleshooting tips, and step-by-step installation procedures for both indoor and outdoor units.
Preview GXH24-36MSK4DH 2/3 Ton Inverter Split System Heat Pump ODU Submittal
Submittal document for the GXH24-36MSK4DH 2/3 Ton Inverter Split System Heat Pump Outdoor Unit (ODU). Details features, benefits, specifications, and installation clearances for this high-efficiency heat pump system.
Preview Nortek Global HVAC Flex Match Series Floor and Ceiling Type Indoor Unit Owner's Manual
This manual provides installation instructions and operation details for the Nortek Global HVAC Flex Match Series Floor and Ceiling Type Indoor Unit Heat Pump. It covers safety precautions, unit outlines, remote controller operation, installation procedures, troubleshooting, and maintenance.
Preview Nortek Global HVAC Flex Match Series System-Outdoor Unit Manual
This manual provides detailed information on the installation, operation, and maintenance of the Nortek Global HVAC Flex Match Series System-Outdoor Unit, including models GXH30(8.8)FMK4DH, GXH36(10.6)FMK4DH, and GXH42(12.3)FMK4DH.
Preview R104GD-U Series Gas/Electric Packaged Units Technical Specifications
Technical specifications and performance data for the R104GD-U Series single packaged gas/electric units, featuring Ultra-Low NOx technology, R-410A refrigerant, and various cooling and heating capacities.
Preview Nortek Global HVAC GHH18(5.3)LUK4DH Ductfree Mini-Split System Replacement Parts List
This document provides a comprehensive replacement parts list for the Nortek Global HVAC GHH18(5.3)LUK4DH Ductfree Mini-Split System Universal Heat Pump Model. It includes item numbers, component descriptions, part codes, and Nortek part numbers for each component.
Preview Nortek GHH36(10.6)LSK4DL DuctFree Mini-Split System Replacement Parts List
Comprehensive replacement parts list for the Nortek GHH36(10.6)LSK4DL single-zone heat pump mini-split system, detailing components, part codes, and Nortek part numbers for efficient maintenance and repair.
Preview Outdoor Split System Heat Pump Installation Instructions - SH3BF4M2SX Series
Comprehensive installation guide for Nortek Global HVAC outdoor split system heat pumps, model series SH3BF4M2SX (2-5 Ton). Covers safety, electrical wiring, refrigerant charging, start-up procedures, and maintenance.