Nortek Global HVAC, LLC - Flex Match Series System-Outdoor Unit

Model: GXH30(8.8)FMK4DH, GXH36(10.6)FMK4DH, GXH42(12.3)FMK4DH

Preface

The Flex Match System utilizes advanced manufacturing. Please read this manual carefully before installation and operation. Key points include:

Model Specifications
Model GXH30(8.8)FMK4DH GXH36(10.6)FMK4DH GXH42(12.3)FMK4DH
Minimum connectable indoor units 2 2 2
Maximum connectable indoor units 4 5 5
Minimum capacity of connectable indoor units 18K Btu 18K Btu 18K Btu
Maximum capacity of connectable indoor units 42K Btu 48K Btu 51K Btu

Additional operational notes:

User Notice

Individuals with reduced mental, sensory, or physical capabilities should not operate or maintain this equipment. Children should not play with the appliance.

If the power cord is damaged, it must be replaced with an equivalent cord by a qualified professional to prevent damage or fire hazards.

Installation should be performed by expert or trained users.

DISPOSAL: Do not dispose of this product as unsorted household waste. Please dispose or recycle responsibly.

Contents

  1. Safety Precautions
  2. Product Introduction
  3. Preparation before Installation
  4. Installation Instruction
  5. Troubleshooting
  6. Common malfunctions and troubleshooting
  7. Troubleshooting
  8. Maintenance
  9. After-sales Service

1 Safety Precautions

WARNING: Failure to comply with warning notices may result in property damage, serious personal injury, or death.

CAUTION: Failure to comply with caution notices may result in property damage or personal injury.

NOTICE: Failure to comply with notices may result in property damage.

WARNING

  1. Installation and use instructions are provided by the manufacturer and should be kept for future reference.
  2. Installation must comply with NEC and CEC requirements and be performed by authorized personnel only.
  3. Verify power supply requirements against the unit's nameplate before installation. Ensure power safety.
  4. Ensure the unit is properly and securely grounded to prevent electric shock. Do not connect the ground wire to gas pipes, water pipes, lightning rods, or telephone lines.
  5. Use only approved accessories and parts to prevent water leakage, electric shock, or fire.
  6. In case of refrigerant leakage during installation, ventilate immediately. Refrigerant gas can produce toxic fumes when exposed to flame.
  7. Ensure the power cord is adequately sized. Replace damaged cords with approved cable.
  8. Secure the electric box cover after connecting the power cord to prevent accidents.
  9. Always comply with nitrogen charge requirements. Charge with nitrogen during pipe welding.
  10. Never short-circuit or bypass the pressure switch, as this can damage the unit.
  11. Connect the wired controller before turning on the power to avoid damage to the controller.
  12. Before use, verify correct piping and wiring to prevent water leakage, refrigerant leakage, electric shock, or fire.
  13. Do not insert fingers or objects into the air outlet/inlet grille.
  14. If using a gas or petroleum heater in the same room, open a door or window for adequate ventilation.
  15. Never start or stop the air conditioner by plugging or unplugging the power cord.
  16. Do not turn off the unit immediately after it has run for at least five minutes; this can damage the compressor oil return system.
  17. Do not allow children to operate this unit.
  18. Do not operate the unit with wet hands.
  19. Turn off the unit or cut off the power supply before cleaning to prevent electric shock or injury.
  20. Never spray or flush water directly at the unit, as this may cause malfunction or electric shock.
  21. Do not expose the unit to wet or corrosive environments.
  22. Turn power on to the unit 8 hours before startup. If the unit will be turned off for a short period (e.g., overnight), do not turn off the power. If power is turned off, it must be turned back on 8 hours before the next startup to allow the compressor to warm up.
  23. Volatile liquids like paint thinner or gasoline can damage the unit's appearance. Clean the outer casing with a soft cloth and mild detergent only.
  24. In cooling mode, avoid setting the room temperature too low. Maintain a temperature difference of no more than 5°C (9°F) between indoor and outdoor units.
  25. If abnormal conditions occur (e.g., burning smell), immediately power off the unit and cut off the main power supply. Contact a qualified service technician. Continued operation of a malfunctioning unit can lead to further damage, electric shock, or fire.
  26. Users are not permitted to repair the unit. Faulty repairs can cause electric shock or fire. Contact a qualified service center for assistance.

Nortek Global HVAC is not responsible for personal injury or equipment damage resulting from improper installation, commissioning, unauthorized service, or failure to follow the instructions in this manual.

2 Product Introduction

The Flex Match System employs inverter compressor technology, enabling stepless capacity regulation within a 15%-120% range by adjusting compressor displacement. Multiple product combinations are available, offering a capacity range from 30K Btu to 42K Btu.

2.1 Parts List

The outdoor unit components are labeled as follows:

Models include: GXH30(8.8)FMK4DH, GXH36(10.6)FMK4DH, GXH42(12.3)FMK4DH.

Figure 1 illustrates the outdoor unit with labeled parts.

2.2 Combinations of outdoor and indoor units

The Flex Match Series air conditioning system allows one outdoor unit to operate with up to five indoor units, which can be cassette type, duct type, wall-mounted, or floor ceiling type. The outdoor unit operates when any indoor unit receives a running command, and all indoor units stop when the outdoor unit is turned off.

Figure 2 shows various indoor unit types compatible with the outdoor unit.

Table 1: Energy Level and Capacity Code of the Indoor Units
Indoor unit type Model Capacity Code Outdoor unit
Wall mounted Lomo GHH09(2.6)LUK4DH 09 GXH30(8.8)FMK4DH;
GXH36(10.6)FMK4DH;
GXH42(12.3)FMK4DH
GHH12(3.5)LUK4DH 12
GHH18(5.3)LUK4DH 18
GHH24(7.0)LUK4DH 24
Flooring ceiling GFH09(2.6)FMK4DH 09
GFH12(3.5)FMK4DH 12
GFH18(5.3)FMK4DH 18
GFH24(7.0)FMK4DH 24
Duct type GDH09(2.6)FMK4DH 09
GDH12(3.5)FMK4DH 12
GDH18(5.3)FMK4DH 18
GDH21(6.2)FMK4DH 21
GDH24(7.0)FMK4DH 24
Cassette type GKH12(3.5)FMK4DH 12
GKH18(5.3)FMK4DH 18
GKH24(7.0)FMK4DH 24
Console GCH09(2.6)FMK4DH 09
GCH12(3.5)FMK4DH 12
GCH18(5.3)FMK4DH 18

2.3 Rated working condition

Table 2: Rated Working Conditions
Indoor side state Outdoor side state
Dry bulb temp. °F Wet bulb temp. °F Dry bulb temp. °F Wet bulb temp. °F
Rating cooling 80.06 66.92 95 75.02
Rating Heating 69.98 60.08 47 43.00

NOTICE:

2.4 The range of production working temperature

Table 3: Working Temperature Ranges
Condition Temperature Range
Cooling Working range Outdoor temperature 0~118°F
Heating Working range Outdoor temperature -4~86°F

3 Preparation before Installation

3.1 Standard parts

The following standard parts are supplied by GREE:

Table 4: Parts of Outdoor Unit
Number Name Picture Quantity Remark
1 Owner's manual [Image: Owner's Manual cover page] 1
2 Tube connector subassy [Image: Tube connector assembly] 8

3.2 Selecting installation site

WARNING

When the outdoor unit is surrounded by walls, maintain appropriate clearances as shown in Figure 3.

Figure 3 illustrates recommended clearances around the outdoor unit.

3.3 Piping Connection

The maximum pipe length is detailed in the following table. Deviating from these ranges may affect normal unit operation.

Table 5: Piping Connection and Maximum Height Difference
Model Connecting Pipe (inch) Max. Pipe length(ft) Max. Height Difference between Indoor Unit and Outdoor Unit (ft)
Liquid Gas
GXH30(8.8)FMK4DH Φ 1/4 Φ 3/8 225 When the outdoor unit is above, max height difference is up to 50ft; When the indoor unit is above, max height difference is up to 50ft.
GXH36(10.6)FMK4DH Φ 1/4 Φ 3/8 250 When the outdoor unit is above, max height difference is up to 50ft; When the indoor unit is above, max height difference is up to 50ft.
GXH42(12.3)FMK4DH Φ 1/4 Φ 3/8 250 When the outdoor unit is above, max height difference is up to 50ft; When the indoor unit is above, max height difference is up to 50ft.

NOTICE:

4 Installation Instruction

4.1 Outline and dimension of the outdoor unit

GXH30(8.8)FMK4DH

Figure 4 shows the outline dimensions and mounting holes for the GXH30(8.8)FMK4DH model.

GXH36(10.6)FMK4DH & GXH42(12.3)FMK4DH

Figure 5 shows the outline dimensions and mounting holes for the GXH36(10.6)FMK4DH and GXH42(12.3)FMK4DH models.

4.2 Installation of the Connection Pipe

Connecting piping for indoor and outdoor units is done in a manifold mode, as illustrated in Figure 6.

4.2.1 Piping between the Indoor and Outdoor Units

Figure 7 illustrates the process of connecting pipes and the required tools.

Table 6: Tightening Torque for Copper Tube Connections
Pipe diameter Thickness of copper tube Tightening torque [NOTE: Convert back to N/M]
Φ1/4 inch ≥0.0315 inch 11~22 ft·lbf
Φ3/8 inch ≥0.0315 inch 26~29 ft·lbf
Φ1/2 inch ≥0.0315 inch 33~37 ft·lbf
Φ5/8 inch ≥0.0394 inch 44~48 ft·lbf

CAUTION:

4.2.2 Allowable pipe length and drop height between indoor and outdoor units

No additional refrigerant is needed if the total refrigerant pipe length (liquid pipe) is less than the value in Table 6.

Table 7: Total Liquid Pipe Length
Model Total Liquid Pipe Length (a+b+c+d+e)
GXH30(8.8)FMK4DH 130ft
GXH36(10.6)FMK4DH 130ft
GXH42(12.3)FMK4DH 130ft

Table 8 provides allowable lengths and height differences for the refrigerant pipe. Figure 8 illustrates the pipe length and height difference measurements.

Table 8: Allowable Length and Height Fall of the Refrigerant Pipe
Allowable Value Fitting Pipe
GXH30(8.8)FMK4DH GXH36(10.6)FMK4DH, GXH42(12.3)FMK4DH
Total length (actual length) of fitting pipe 225ft 250ft L1+L2+...+LM (M ≤5)
Length of farthest fitting pipe (ft) 82ft 82ft Lx (X=1, 2, 3, 4, 5)
Height difference between outdoor unit and indoor unit Outdoor unit at upper 50ft 50ft H1
Outdoor unit at lower 50ft 50ft H3
Height difference between indoor units (m) 25ft 25ft H2

4.2.3 Installation of the Protection Layer for Refrigerant Pipe

Figure 9 shows the thermal insulating layer required for the joints.

CAUTION: After protection, do not bend the pipe sharply, as it may break.

CAUTION: Do not wrap the pipe too tightly, as this weakens the insulation effect. Ensure the drain hose is separated from the pipe.

4.2.4 Support and protection for pipeline

Support hanging connection pipes. The distance between supports should not exceed 1m (3 ft).

4.3 Air Purging and Refrigerant Charge

4.3.1 Air purging

Figure 10 illustrates the vacuum pump connection for refrigerant removal.

4.3.2 Additional refrigerant charging

The GXH30, 36, and 42 models are factory charged for a minimum of 130 feet. For longer runs, calculate additional refrigerant at 0.2 ounces per foot. The maximum lineset length is 225 feet for GXH30 and 250 feet for GXH 36 and 42. The total additional refrigerant charge should not exceed 28 ounces.

4.4 Electric Wiring

4.4.1 Wiring precautions

Table 9: Electrical Specifications
Models Power Supply Circuit Breaker (A) Recommended Wire Size AWG
GXH30(8.8)FMK4DH 208/230V~60Hz 32 14
GXH36(10.6)FMK4DH 208/230V~60Hz 32 14
GXH42(12.3)FMK4DH 208/230V~60Hz 32 14

4.4.2 Grounding Requirements

4.4.3 Electrical Cable Connection

CAUTION:

4.4.4 Wiring of the Power Cord

CAUTION: If the supply cord is damaged, it must be replaced by a qualified person to avoid hazards.

Figure 13 shows the power cord connection points.

5 Troubleshooting

WARNING:

Check before Contacting Service Center

Table 10: Troubleshooting Checklist
Check Items Conditions Might Happen Check
Has the unit been securely mounted? The unit may fall, shake, or emit noise.
Have you done the gas leakage test? It may cause poor cooling/heating performance.
Did the unit get proper thermal insulation? It may cause condensation and dripping.
Does the condensate drain well? It may cause dripping.
Does the voltage match the rated voltage specified on the nameplate? It may cause malfunction or damage.
Is the electric wiring and piping connection installed correctly and securely? It may cause malfunction or damage.
Has the unit been grounded securely? It may cause electrical shock.
Is the power cord properly installed? It may cause malfunction or damage.
Are the inlet or outlet blocked? It may cause poor cooling/heating performance.

NOTICE! If the air conditioner continues to run abnormally after performing these checks, contact the maintenance serviceman at the local appointed service center and provide a description of the error and the model number.

6 Common malfunctions and troubleshooting.

Please check the following before calling for service.

Table 11: Malfunctions and Causes
Conditions Causes
The unit does not run The unit will not restart after it has stopped. The overload protection switch requires a three-minute delay.
As soon as power is turned on. Standby operation lasts for about 1 minute.
The unit blows out mist When the cooling operation starts. If the ambient air is high temperature and humidity, mist will be produced as air is cooled.
The unit blows out mist When the cooling operation starts. If the ambient air is high temperature and humidity, mist will be produced as air is cooled.
The unit generates noise The unit "clatters" as soon as it starts running. It is the sound of the initialization of the electronic expansion valve.
The unit "swishes" during the cooling operation. It is the sound of refrigerant gas running through the coil.
The unit "swishes" when it is started or stopped. It is the sound when the refrigerant gas stops running.
The unit "swishes" when it is in and after the running. It is the sound of the draining system.
The unit "squeaks” will running or after stopping. It is the sound of plastic cover or other parts expanding/contracting due to temperature change.
The unit blows out dust. When the unit restarts after it is not used for a long time. The dust inside the unit is blown out again.
The unit emits odors. When the unit is running. Odors absorbed in the unit or filter are recirculated into the room.

NOTICE! If problems cannot be solved after checking the above items, please contact a qualified service technician. The following circumstances are not malfunctions:

Table 12: Malfunctions and Reasons
Malfunction Reason
Indoor unit still runs after set temperature is reached After indoor unit receives "stop" signal, fan will keep running. Indoor fan motor will keep running 20-70s to take advantage of residual cooling or heating effect from coil.
Mode conflict COOL or HEAT mode cannot be operated. When the indoor operating mode conflicts with that of the outdoor unit, an indoor fault indicator will flash and the conflict will be shown on the wired controller after 5 minutes. Indoor unit stops to run. Outdoor operating mode changes to match the indoor unit's mode, and the unit will return to normal.

7 Troubleshooting

Error codes will be displayed on the wired controller and the outdoor unit's main board. Refer to Table 13 for error code meanings.

Table 13: Error Codes and Indicator Display
Name of malfunction The indicator display
Yellow light Red light Green light
Compressor runs Flash once
Defrost Flash twice
Anti-freezing protection Flash 3 times
IPM protection Flash 4 times
AC over-current protection Flash 5 times
Over-burden protection Flash 6 times
Compressor exhaust high temperature protection Flash 7 times
Compressor overload protection Flash 8 times
Power protection Flash 9 times
EEPROM reads and write protection Flash 11 times
Low PN voltage protection Flash 12 times
Over voltage protection for PN Flash 13 times
PFC protection Flash 14 times
PFC module temperature protection Flash 15 times
Low pressure protection Flash 17 times
High pressure protection Flash 18 times
Limit/decline frequency(electric current) Flash 1 times
Frequency limit(exhaust) Flash 2 times
Frequency limit(Over-burden) Flash 3 times
Outdoor ambient sensor malfunction Flash 6 times
Outdoor tube sensor malfunction Flash 5 times
Exhaust sensor malfunction Flash 7 times
Attain the temperature of switch on Flash 8 times
Frequency limit(power) Flash 13 times
Outdoor fan malfunction Flash 14 times
Frequency limit(PFC module temperature) Flash 15 times
PFC module sensor malfunction Flash 16 times
Liquid pipe temperature sensor malfunction of A Flash 17 times
Gas pipe temperature sensor malfunction of A Flash 18 times
Liquid pipe temperature sensor malfunction of B Flash 19 times
Gas pipe temperature sensor malfunction of B Flash 20 times
Liquid pipe temperature sensor malfunction of C Flash 21 times
Gas pipe temperature sensor malfunction of C Flash 22 times
Liquid pipe temperature sensor malfunction of D Flash 23 times
Gas pipe temperature sensor malfunction of D Flash 24 times
Liquid pipe temperature sensor malfunction of E Flash 25 times
Gas pipe temperature sensor malfunction of E Flash 26 times
Exit of the condenser tube sensor malfunction Flash 27 times
Communication is normal Flash n times (n=indoor unit number)
Communication failure between indoor unit and outdoor unit Often bright (indoor unit all Communication failure)

8 Maintenance

Regular checks, maintenance, and care by professional personnel will prolong the unit's lifespan.

8.1 Outdoor heat exchanger

Clean the outdoor heat exchanger every two months using a vacuum cleaner with a nylon brush to remove dust and debris. Compressed air can be used if available. Do not use water to wash the heat exchanger.

8.2 Drain Pipe

Regularly check the drain pipe for clogs to ensure proper condensate drainage.

8.3 Preseason Checklist

8.4 Post-Season Checklist

8.5 Parts Replacement

Purchase parts from an authorized service center or dealer.

NOTICE! During airtight and leakage tests, do not mix oxygen, ethane, or other dangerous gases into the refrigeration circuit. Use nitrogen for leak testing.

9 After-sales Service

For any quality issues or inquiries regarding the air-conditioning unit, please contact the installer or authorized distributor.

Warranty claims must meet the following requirements:

Specifications and illustrations are subject to change without notice or incurring obligations.

© Nortek Global HVAC, LLC 2016. All Rights Reserved. 563E-0616

PDF preview unavailable. Download the PDF instead.

Flex Match ODU 30K-42K Owners Manual (563E) Microsoft Office Word 2007

Related Documents

Preview Nortek GDH09(2.6)FMK4DH Flex Match System Duct Type Indoor Unit Replacement Parts List
Detailed replacement parts list for the Nortek GDH09(2.6)FMK4DH Flex Match System Duct Type Indoor Unit. Includes component descriptions, part codes, and Nortek part numbers for HVAC system maintenance and repair.
Preview Nortek Global HVAC Flex Match Series Floor and Ceiling Type Indoor Unit Owner's Manual
This manual provides installation instructions and operation details for the Nortek Global HVAC Flex Match Series Floor and Ceiling Type Indoor Unit Heat Pump. It covers safety precautions, unit outlines, remote controller operation, installation procedures, troubleshooting, and maintenance.
Preview Nortek Global HVAC Mini Split Heat Pump Systems Owner's Manual and Installation Instructions
This manual provides comprehensive owner's and installation instructions for Nortek Global HVAC Mini Split Heat Pump Systems, Outdoor Units, including safety precautions, parts identification, installation procedures, testing, and troubleshooting.
Preview Nortek Global HVAC Single Package Cooling Unit & Heat Pump User Manual
Comprehensive user manual for Nortek Global HVAC single package cooling units and heat pumps. Covers safety, operation, maintenance, troubleshooting, and warranty information for efficient home comfort.
Preview R104GD Series Gas/Electric Packaged Units: Technical Specifications & Performance Data
Detailed technical specifications, dimensions, electrical data, and performance ratings for Nortek Global HVAC's R104GD Series Single Packaged Gas/Electric Units. Covers models from 2 to 5 tons, featuring R-410A refrigerant and Copeland Scroll compressors.
Preview H8HK Series Electric Heater Kit Installation Instructions
Comprehensive installation guide for the H8HK Series Electric Heater Kit, detailing installation procedures, safety precautions, electrical specifications, and wiring diagrams for various air handler models. Suitable for qualified installers.
Preview User's Manual: Single Package Cooling Unit or Heat Pump Unit
Comprehensive user manual for Nortek Global HVAC Single Package Cooling Units and Heat Pump Units, covering safety, operation, maintenance, and troubleshooting for optimal performance and energy efficiency.
Preview User Manual: Single Package Cooling Unit or Heat Pump Unit
This user manual provides essential safety, operating, and maintenance instructions for the Single Package Cooling Unit or Heat Pump Unit by Nortek Global HVAC. Learn about system features, thermostat operation, troubleshooting tips, and warranty information.