Nortek Global HVAC, LLC - Flex Match Series System-Outdoor Unit
Model: GXH30(8.8)FMK4DH, GXH36(10.6)FMK4DH, GXH42(12.3)FMK4DH
Preface
The Flex Match System utilizes advanced manufacturing. Please read this manual carefully before installation and operation. Key points include:
- Unit complies with UL1995 standards.
- Flex Match System conforms to ARI 210-240-2008 design standards.
- Strict adherence to all instructions in this manual is required.
- The total capacity of simultaneously operating indoor units must not exceed the outdoor unit's capacity to ensure sufficient cooling/heating effects.
Model | GXH30(8.8)FMK4DH | GXH36(10.6)FMK4DH | GXH42(12.3)FMK4DH |
---|---|---|---|
Minimum connectable indoor units | 2 | 2 | 2 |
Maximum connectable indoor units | 4 | 5 | 5 |
Minimum capacity of connectable indoor units | 18K Btu | 18K Btu | 18K Btu |
Maximum capacity of connectable indoor units | 42K Btu | 48K Btu | 51K Btu |
Additional operational notes:
- Switch the main power on 8 hours before starting the unit.
- The indoor unit fan may continue to run for 20-70 seconds after receiving a "stop" signal to utilize residual heat.
- Conflicts between indoor and outdoor unit modes will be indicated on the wired controller, and the units will harmonize modes. Cooling mode is compatible with dehumidifying mode; fan mode can run with any mode. If power fails during operation, the unit will restart automatically 3 minutes after power recovery.
- Cautions for Debugging and Maintenance Personnel: The compressor heating belt must be energized for at least eight hours before startup. Once started, the compressor must run continuously for at least 30 minutes to prevent damage.
User Notice
Individuals with reduced mental, sensory, or physical capabilities should not operate or maintain this equipment. Children should not play with the appliance.
If the power cord is damaged, it must be replaced with an equivalent cord by a qualified professional to prevent damage or fire hazards.
Installation should be performed by expert or trained users.
DISPOSAL: Do not dispose of this product as unsorted household waste. Please dispose or recycle responsibly.
Contents
- Safety Precautions
- Product Introduction
- Preparation before Installation
- Installation Instruction
- Troubleshooting
- Common malfunctions and troubleshooting
- Troubleshooting
- Maintenance
- After-sales Service
1 Safety Precautions
WARNING: Failure to comply with warning notices may result in property damage, serious personal injury, or death.
CAUTION: Failure to comply with caution notices may result in property damage or personal injury.
NOTICE: Failure to comply with notices may result in property damage.
WARNING
- Installation and use instructions are provided by the manufacturer and should be kept for future reference.
- Installation must comply with NEC and CEC requirements and be performed by authorized personnel only.
- Verify power supply requirements against the unit's nameplate before installation. Ensure power safety.
- Ensure the unit is properly and securely grounded to prevent electric shock. Do not connect the ground wire to gas pipes, water pipes, lightning rods, or telephone lines.
- Use only approved accessories and parts to prevent water leakage, electric shock, or fire.
- In case of refrigerant leakage during installation, ventilate immediately. Refrigerant gas can produce toxic fumes when exposed to flame.
- Ensure the power cord is adequately sized. Replace damaged cords with approved cable.
- Secure the electric box cover after connecting the power cord to prevent accidents.
- Always comply with nitrogen charge requirements. Charge with nitrogen during pipe welding.
- Never short-circuit or bypass the pressure switch, as this can damage the unit.
- Connect the wired controller before turning on the power to avoid damage to the controller.
- Before use, verify correct piping and wiring to prevent water leakage, refrigerant leakage, electric shock, or fire.
- Do not insert fingers or objects into the air outlet/inlet grille.
- If using a gas or petroleum heater in the same room, open a door or window for adequate ventilation.
- Never start or stop the air conditioner by plugging or unplugging the power cord.
- Do not turn off the unit immediately after it has run for at least five minutes; this can damage the compressor oil return system.
- Do not allow children to operate this unit.
- Do not operate the unit with wet hands.
- Turn off the unit or cut off the power supply before cleaning to prevent electric shock or injury.
- Never spray or flush water directly at the unit, as this may cause malfunction or electric shock.
- Do not expose the unit to wet or corrosive environments.
- Turn power on to the unit 8 hours before startup. If the unit will be turned off for a short period (e.g., overnight), do not turn off the power. If power is turned off, it must be turned back on 8 hours before the next startup to allow the compressor to warm up.
- Volatile liquids like paint thinner or gasoline can damage the unit's appearance. Clean the outer casing with a soft cloth and mild detergent only.
- In cooling mode, avoid setting the room temperature too low. Maintain a temperature difference of no more than 5°C (9°F) between indoor and outdoor units.
- If abnormal conditions occur (e.g., burning smell), immediately power off the unit and cut off the main power supply. Contact a qualified service technician. Continued operation of a malfunctioning unit can lead to further damage, electric shock, or fire.
- Users are not permitted to repair the unit. Faulty repairs can cause electric shock or fire. Contact a qualified service center for assistance.
Nortek Global HVAC is not responsible for personal injury or equipment damage resulting from improper installation, commissioning, unauthorized service, or failure to follow the instructions in this manual.
2 Product Introduction
The Flex Match System employs inverter compressor technology, enabling stepless capacity regulation within a 15%-120% range by adjusting compressor displacement. Multiple product combinations are available, offering a capacity range from 30K Btu to 42K Btu.
2.1 Parts List
The outdoor unit components are labeled as follows:
- 1: Motor
- 2: Fan
- 3: Electric Box
- 4: Gas valve assembly
- 5: Liquid valve assembly
Models include: GXH30(8.8)FMK4DH, GXH36(10.6)FMK4DH, GXH42(12.3)FMK4DH.
Figure 1 illustrates the outdoor unit with labeled parts.
2.2 Combinations of outdoor and indoor units
The Flex Match Series air conditioning system allows one outdoor unit to operate with up to five indoor units, which can be cassette type, duct type, wall-mounted, or floor ceiling type. The outdoor unit operates when any indoor unit receives a running command, and all indoor units stop when the outdoor unit is turned off.
Figure 2 shows various indoor unit types compatible with the outdoor unit.
Indoor unit type | Model | Capacity Code | Outdoor unit |
---|---|---|---|
Wall mounted Lomo | GHH09(2.6)LUK4DH | 09 | GXH30(8.8)FMK4DH; GXH36(10.6)FMK4DH; GXH42(12.3)FMK4DH |
GHH12(3.5)LUK4DH | 12 | ||
GHH18(5.3)LUK4DH | 18 | ||
GHH24(7.0)LUK4DH | 24 | ||
Flooring ceiling | GFH09(2.6)FMK4DH | 09 | |
GFH12(3.5)FMK4DH | 12 | ||
GFH18(5.3)FMK4DH | 18 | ||
GFH24(7.0)FMK4DH | 24 | ||
Duct type | GDH09(2.6)FMK4DH | 09 | |
GDH12(3.5)FMK4DH | 12 | ||
GDH18(5.3)FMK4DH | 18 | ||
GDH21(6.2)FMK4DH | 21 | ||
GDH24(7.0)FMK4DH | 24 | ||
Cassette type | GKH12(3.5)FMK4DH | 12 | |
GKH18(5.3)FMK4DH | 18 | ||
GKH24(7.0)FMK4DH | 24 | ||
Console | GCH09(2.6)FMK4DH | 09 | |
GCH12(3.5)FMK4DH | 12 | ||
GCH18(5.3)FMK4DH | 18 |
2.3 Rated working condition
Indoor side state | Outdoor side state | |||
---|---|---|---|---|
Dry bulb temp. °F | Wet bulb temp. °F | Dry bulb temp. °F | Wet bulb temp. °F | |
Rating cooling | 80.06 | 66.92 | 95 | 75.02 |
Rating Heating | 69.98 | 60.08 | 47 | 43.00 |
NOTICE:
- Cooling/heating capacity and sound levels are tested before shipment.
- Parameters are tested under rated working conditions. Refer to the nameplate for any changes.
- Heating capacity parameters exclude auxiliary electric heating power.
- Performance parameters are tested according to ANSI/AHRI 1230-2010.
2.4 The range of production working temperature
Condition | Temperature Range |
---|---|
Cooling Working range | Outdoor temperature 0~118°F |
Heating Working range | Outdoor temperature -4~86°F |
3 Preparation before Installation
3.1 Standard parts
The following standard parts are supplied by GREE:
Number | Name | Picture | Quantity | Remark |
---|---|---|---|---|
1 | Owner's manual | [Image: Owner's Manual cover page] | 1 | |
2 | Tube connector subassy | [Image: Tube connector assembly] | 8 |
3.2 Selecting installation site
WARNING
- Verify that the support structure has sufficient load-carrying capacity and can be securely mounted.
- Protect the unit from direct sunlight, rainfall, dust, strong wind, and earthquakes.
- Keep the unit away from combustible, inflammable, corrosive materials, or exhaust gases.
- Ensure adequate clearance around the unit for service and maintenance.
- Position indoor and outdoor units as close as possible to minimize pipe length and bends.
- Keep children away from the unit during installation and operation.
When the outdoor unit is surrounded by walls, maintain appropriate clearances as shown in Figure 3.
Figure 3 illustrates recommended clearances around the outdoor unit.
3.3 Piping Connection
The maximum pipe length is detailed in the following table. Deviating from these ranges may affect normal unit operation.
Model | Connecting Pipe (inch) | Max. Pipe length(ft) | Max. Height Difference between Indoor Unit and Outdoor Unit (ft) | |
---|---|---|---|---|
Liquid | Gas | |||
GXH30(8.8)FMK4DH | Φ 1/4 | Φ 3/8 | 225 | When the outdoor unit is above, max height difference is up to 50ft; When the indoor unit is above, max height difference is up to 50ft. |
GXH36(10.6)FMK4DH | Φ 1/4 | Φ 3/8 | 250 | When the outdoor unit is above, max height difference is up to 50ft; When the indoor unit is above, max height difference is up to 50ft. |
GXH42(12.3)FMK4DH | Φ 1/4 | Φ 3/8 | 250 | When the outdoor unit is above, max height difference is up to 50ft; When the indoor unit is above, max height difference is up to 50ft. |
NOTICE:
- Use water-proof insulating pipe.
- Pipe wall thickness: 0.019-0.039 inch; bearing pressure: 3.0MPa.
- Longer connection pipes may reduce cooling and heating capacity.
4 Installation Instruction
4.1 Outline and dimension of the outdoor unit
GXH30(8.8)FMK4DH
Figure 4 shows the outline dimensions and mounting holes for the GXH30(8.8)FMK4DH model.
GXH36(10.6)FMK4DH & GXH42(12.3)FMK4DH
Figure 5 shows the outline dimensions and mounting holes for the GXH36(10.6)FMK4DH and GXH42(12.3)FMK4DH models.
4.2 Installation of the Connection Pipe
Connecting piping for indoor and outdoor units is done in a manifold mode, as illustrated in Figure 6.
4.2.1 Piping between the Indoor and Outdoor Units
- If liquid and gas stop valves (A, B, C, D, or E) are not connected to indoor units, remove the caps with a wrench.
- Refer to Figure 7 for torque requirements.
- Align the flare end of the copper pipe with the screw and tighten by hand.
- Subsequently, tighten the screw with a torque wrench until it clicks (as shown in Figure 7).
- Use a pipe bender to bend the pipe. Bending the pipe too sharply may cause it to break.
- Wrap exposed refrigerant pipes and joints with sponge and secure with plastic tape.
Figure 7 illustrates the process of connecting pipes and the required tools.
Pipe diameter | Thickness of copper tube | Tightening torque [NOTE: Convert back to N/M] |
---|---|---|
Φ1/4 inch | ≥0.0315 inch | 11~22 ft·lbf |
Φ3/8 inch | ≥0.0315 inch | 26~29 ft·lbf |
Φ1/2 inch | ≥0.0315 inch | 33~37 ft·lbf |
Φ5/8 inch | ≥0.0394 inch | 44~48 ft·lbf |
CAUTION:
- When installing pipe lines, avoid pulling forcefully on pipes or connections, as this can cause damage and refrigerant leaks.
- Support refrigerant pipes with brackets; the units should not bear the weight of the pipes.
- If the outdoor unit's piping connection size differs from the indoor unit's, use an adapter joint.
- Label each pipe for easier and more accurate connections in the Flex Match system.
4.2.2 Allowable pipe length and drop height between indoor and outdoor units
No additional refrigerant is needed if the total refrigerant pipe length (liquid pipe) is less than the value in Table 6.
Model | Total Liquid Pipe Length (a+b+c+d+e) |
---|---|
GXH30(8.8)FMK4DH | 130ft |
GXH36(10.6)FMK4DH | 130ft |
GXH42(12.3)FMK4DH | 130ft |
Table 8 provides allowable lengths and height differences for the refrigerant pipe. Figure 8 illustrates the pipe length and height difference measurements.
Allowable Value | Fitting Pipe | |||
---|---|---|---|---|
GXH30(8.8)FMK4DH | GXH36(10.6)FMK4DH, GXH42(12.3)FMK4DH | |||
Total length (actual length) of fitting pipe | 225ft | 250ft | L1+L2+...+LM (M ≤5) | |
Length of farthest fitting pipe (ft) | 82ft | 82ft | Lx (X=1, 2, 3, 4, 5) | |
Height difference between outdoor unit and indoor unit | Outdoor unit at upper | 50ft | 50ft | H1 |
Outdoor unit at lower | 50ft | 50ft | H3 | |
Height difference between indoor units (m) | 25ft | 25ft | H2 |
4.2.3 Installation of the Protection Layer for Refrigerant Pipe
- The refrigerant pipe should be insulated with insulating material and plastic tape to prevent condensation.
- Joints of the indoor unit should be wrapped with insulating material without gaps, as shown in Figure 9.
Figure 9 shows the thermal insulating layer required for the joints.
CAUTION: After protection, do not bend the pipe sharply, as it may break.
- Wrap the pipe with tape:
- Bundle refrigerant pipes and electric wires together with tape, separating them from the drain pipe to prevent condensate overflow.
- Wrap the pipe from the bottom of the outdoor unit upwards, overlapping each layer of tape by half its width.
- Secure the wrapped pipe to the wall with clamps.
CAUTION: Do not wrap the pipe too tightly, as this weakens the insulation effect. Ensure the drain hose is separated from the pipe.
- Seal wall openings to prevent wind and rain entry.
4.2.4 Support and protection for pipeline
Support hanging connection pipes. The distance between supports should not exceed 1m (3 ft).
4.3 Air Purging and Refrigerant Charge
4.3.1 Air purging
- Refrigerant is pre-charged into the outdoor unit before shipment. Additional refrigerant may be needed during installation.
- Ensure the liquid and gas valves of the outdoor unit are fully closed.
- Use a vacuum pump to remove refrigerant from the indoor unit and refrigerant pipe, as shown in Figure 10.
- When the compressor is not running, charge R410A refrigerant into the pipe via the liquid valve of the outdoor unit (not the gas valve).
Figure 10 illustrates the vacuum pump connection for refrigerant removal.
4.3.2 Additional refrigerant charging
The GXH30, 36, and 42 models are factory charged for a minimum of 130 feet. For longer runs, calculate additional refrigerant at 0.2 ounces per foot. The maximum lineset length is 225 feet for GXH30 and 250 feet for GXH 36 and 42. The total additional refrigerant charge should not exceed 28 ounces.
4.4 Electric Wiring
4.4.1 Wiring precautions
- Installation must comply with national wiring regulations.
- Use only a power cord with the correct voltage rating and a dedicated circuit for the air conditioning.
- Do not pull the unit by its power cord.
- Electrical installation must follow local laws, regulations, and this manual.
- Ensure the power cord diameter is sufficiently sized. Replace damaged cords with appropriate ones.
- Grounding must be secure and performed by a qualified technician. The circuit breaker must have adequate capacity and include both magnetic and thermal tripping functions for short circuit and overload protection.
Models | Power Supply | Circuit Breaker (A) | Recommended Wire Size AWG |
---|---|---|---|
GXH30(8.8)FMK4DH | 208/230V~60Hz | 32 | 14 |
GXH36(10.6)FMK4DH | 208/230V~60Hz | 32 | 14 |
GXH42(12.3)FMK4DH | 208/230V~60Hz | 32 | 14 |
4.4.2 Grounding Requirements
- The air conditioner is a Class I appliance and requires reliable grounding.
- The yellow-green wire is the ground line and must not be cut, removed, or tampered with, as this could cause electric shock.
- A reliable ground terminal must be provided. Do not connect the ground wire to water pipes, coal gas pipes, sewage pipes, or other unreliable objects.
4.4.3 Electrical Cable Connection
CAUTION:
- Faulty connections can lead to malfunction. Ensure wires are not taut after connection.
- Connect piping and wiring as described in this manual.
- Electrical installation must be performed by a technician following local laws, regulations, and this manual.
- Install the unit in a dry location, protected from direct sunlight and strong winds.
- A circuit breaker must be installed to shut off the main power supply for the entire system.
4.4.4 Wiring of the Power Cord
- Open the side plate.
- Connect the power cord to terminals “L1”, “L2”, and the grounding bolt. Connect wiring terminals “N(1),2,3” of the indoor unit to the outdoor unit accordingly. Use the green bonding screw for the grounding cord, as shown in Figure 13.
- Secure the power cord with wire clips.
- Lead the power cord through the rubber ring.
CAUTION: If the supply cord is damaged, it must be replaced by a qualified person to avoid hazards.
Figure 13 shows the power cord connection points.
5 Troubleshooting
WARNING:
- In case of abnormal conditions (e.g., strong or burning smell), immediately shut off the main power supply and contact qualified service personnel. Continued use of a malfunctioning unit can damage the air conditioner and cause electric shock or fire hazards.
- Users should not attempt to repair the air conditioner. Contact professionally skilled personnel, as faulty repairs can lead to electric shock or fire hazards.
Check before Contacting Service Center
Check Items | Conditions Might Happen | Check |
---|---|---|
Has the unit been securely mounted? | The unit may fall, shake, or emit noise. | |
Have you done the gas leakage test? | It may cause poor cooling/heating performance. | |
Did the unit get proper thermal insulation? | It may cause condensation and dripping. | |
Does the condensate drain well? | It may cause dripping. | |
Does the voltage match the rated voltage specified on the nameplate? | It may cause malfunction or damage. | |
Is the electric wiring and piping connection installed correctly and securely? | It may cause malfunction or damage. | |
Has the unit been grounded securely? | It may cause electrical shock. | |
Is the power cord properly installed? | It may cause malfunction or damage. | |
Are the inlet or outlet blocked? | It may cause poor cooling/heating performance. |
NOTICE! If the air conditioner continues to run abnormally after performing these checks, contact the maintenance serviceman at the local appointed service center and provide a description of the error and the model number.
6 Common malfunctions and troubleshooting.
Please check the following before calling for service.
Conditions | Causes |
---|---|
The unit does not run | The unit will not restart after it has stopped. The overload protection switch requires a three-minute delay. |
As soon as power is turned on. Standby operation lasts for about 1 minute. | |
The unit blows out mist | When the cooling operation starts. If the ambient air is high temperature and humidity, mist will be produced as air is cooled. |
The unit blows out mist | When the cooling operation starts. If the ambient air is high temperature and humidity, mist will be produced as air is cooled. |
The unit generates noise | The unit "clatters" as soon as it starts running. It is the sound of the initialization of the electronic expansion valve. |
The unit "swishes" during the cooling operation. It is the sound of refrigerant gas running through the coil. | |
The unit "swishes" when it is started or stopped. It is the sound when the refrigerant gas stops running. | |
The unit "swishes" when it is in and after the running. It is the sound of the draining system. | |
The unit "squeaks” will running or after stopping. It is the sound of plastic cover or other parts expanding/contracting due to temperature change. | |
The unit blows out dust. | When the unit restarts after it is not used for a long time. The dust inside the unit is blown out again. |
The unit emits odors. | When the unit is running. Odors absorbed in the unit or filter are recirculated into the room. |
NOTICE! If problems cannot be solved after checking the above items, please contact a qualified service technician. The following circumstances are not malfunctions:
Malfunction | Reason |
---|---|
Indoor unit still runs after set temperature is reached | After indoor unit receives "stop" signal, fan will keep running. Indoor fan motor will keep running 20-70s to take advantage of residual cooling or heating effect from coil. |
Mode conflict | COOL or HEAT mode cannot be operated. When the indoor operating mode conflicts with that of the outdoor unit, an indoor fault indicator will flash and the conflict will be shown on the wired controller after 5 minutes. Indoor unit stops to run. Outdoor operating mode changes to match the indoor unit's mode, and the unit will return to normal. |
7 Troubleshooting
Error codes will be displayed on the wired controller and the outdoor unit's main board. Refer to Table 13 for error code meanings.
Name of malfunction | The indicator display | ||
---|---|---|---|
Yellow light | Red light | Green light | |
Compressor runs | Flash once | ||
Defrost | Flash twice | ||
Anti-freezing protection | Flash 3 times | ||
IPM protection | Flash 4 times | ||
AC over-current protection | Flash 5 times | ||
Over-burden protection | Flash 6 times | ||
Compressor exhaust high temperature protection | Flash 7 times | ||
Compressor overload protection | Flash 8 times | ||
Power protection | Flash 9 times | ||
EEPROM reads and write protection | Flash 11 times | ||
Low PN voltage protection | Flash 12 times | ||
Over voltage protection for PN | Flash 13 times | ||
PFC protection | Flash 14 times | ||
PFC module temperature protection | Flash 15 times | ||
Low pressure protection | Flash 17 times | ||
High pressure protection | Flash 18 times | ||
Limit/decline frequency(electric current) | Flash 1 times | ||
Frequency limit(exhaust) | Flash 2 times | ||
Frequency limit(Over-burden) | Flash 3 times | ||
Outdoor ambient sensor malfunction | Flash 6 times | ||
Outdoor tube sensor malfunction | Flash 5 times | ||
Exhaust sensor malfunction | Flash 7 times | ||
Attain the temperature of switch on | Flash 8 times | ||
Frequency limit(power) | Flash 13 times | ||
Outdoor fan malfunction | Flash 14 times | ||
Frequency limit(PFC module temperature) | Flash 15 times | ||
PFC module sensor malfunction | Flash 16 times | ||
Liquid pipe temperature sensor malfunction of A | Flash 17 times | ||
Gas pipe temperature sensor malfunction of A | Flash 18 times | ||
Liquid pipe temperature sensor malfunction of B | Flash 19 times | ||
Gas pipe temperature sensor malfunction of B | Flash 20 times | ||
Liquid pipe temperature sensor malfunction of C | Flash 21 times | ||
Gas pipe temperature sensor malfunction of C | Flash 22 times | ||
Liquid pipe temperature sensor malfunction of D | Flash 23 times | ||
Gas pipe temperature sensor malfunction of D | Flash 24 times | ||
Liquid pipe temperature sensor malfunction of E | Flash 25 times | ||
Gas pipe temperature sensor malfunction of E | Flash 26 times | ||
Exit of the condenser tube sensor malfunction | Flash 27 times | ||
Communication is normal | Flash n times (n=indoor unit number) | ||
Communication failure between indoor unit and outdoor unit | Often bright (indoor unit all Communication failure) |
8 Maintenance
Regular checks, maintenance, and care by professional personnel will prolong the unit's lifespan.
8.1 Outdoor heat exchanger
Clean the outdoor heat exchanger every two months using a vacuum cleaner with a nylon brush to remove dust and debris. Compressed air can be used if available. Do not use water to wash the heat exchanger.
8.2 Drain Pipe
Regularly check the drain pipe for clogs to ensure proper condensate drainage.
8.3 Preseason Checklist
- Check if the indoor/outdoor unit inlet/outlet is blocked.
- Check the ground wire.
- Check if the remote wireless controller battery needs replacement.
- Verify the filter screen is properly set.
- After prolonged shutdown, turn on the main power switch 8 hours before re-operation to preheat the compressor crankcase.
- Check if the outdoor unit is securely mounted. Contact an appointed qualified service center if any abnormalities are found.
8.4 Post-Season Checklist
- Turn off the main power supply to the unit.
- Clean the filter screen and both indoor and outdoor units.
- Remove dust and debris from the indoor and outdoor units.
- In case of rust, apply anti-rust paint to prevent its spread.
8.5 Parts Replacement
Purchase parts from an authorized service center or dealer.
NOTICE! During airtight and leakage tests, do not mix oxygen, ethane, or other dangerous gases into the refrigeration circuit. Use nitrogen for leak testing.
9 After-sales Service
For any quality issues or inquiries regarding the air-conditioning unit, please contact the installer or authorized distributor.
Warranty claims must meet the following requirements:
- Installation and startup must be performed by professional personnel.
- Only approved accessories should be used on the machine.
- All instructions in this manual must be followed.
- Warranty will be void if any of the above conditions are not met.
Specifications and illustrations are subject to change without notice or incurring obligations.
© Nortek Global HVAC, LLC 2016. All Rights Reserved. 563E-0616
Related Documents
![]() |
Nortek GDH09(2.6)FMK4DH Flex Match System Duct Type Indoor Unit Replacement Parts List Detailed replacement parts list for the Nortek GDH09(2.6)FMK4DH Flex Match System Duct Type Indoor Unit. Includes component descriptions, part codes, and Nortek part numbers for HVAC system maintenance and repair. |
![]() |
Nortek Global HVAC Flex Match Series Floor and Ceiling Type Indoor Unit Owner's Manual This manual provides installation instructions and operation details for the Nortek Global HVAC Flex Match Series Floor and Ceiling Type Indoor Unit Heat Pump. It covers safety precautions, unit outlines, remote controller operation, installation procedures, troubleshooting, and maintenance. |
![]() |
Nortek Global HVAC Mini Split Heat Pump Systems Owner's Manual and Installation Instructions This manual provides comprehensive owner's and installation instructions for Nortek Global HVAC Mini Split Heat Pump Systems, Outdoor Units, including safety precautions, parts identification, installation procedures, testing, and troubleshooting. |
![]() |
Nortek Global HVAC Single Package Cooling Unit & Heat Pump User Manual Comprehensive user manual for Nortek Global HVAC single package cooling units and heat pumps. Covers safety, operation, maintenance, troubleshooting, and warranty information for efficient home comfort. |
![]() |
R104GD Series Gas/Electric Packaged Units: Technical Specifications & Performance Data Detailed technical specifications, dimensions, electrical data, and performance ratings for Nortek Global HVAC's R104GD Series Single Packaged Gas/Electric Units. Covers models from 2 to 5 tons, featuring R-410A refrigerant and Copeland Scroll compressors. |
![]() |
H8HK Series Electric Heater Kit Installation Instructions Comprehensive installation guide for the H8HK Series Electric Heater Kit, detailing installation procedures, safety precautions, electrical specifications, and wiring diagrams for various air handler models. Suitable for qualified installers. |
![]() |
User's Manual: Single Package Cooling Unit or Heat Pump Unit Comprehensive user manual for Nortek Global HVAC Single Package Cooling Units and Heat Pump Units, covering safety, operation, maintenance, and troubleshooting for optimal performance and energy efficiency. |
![]() |
User Manual: Single Package Cooling Unit or Heat Pump Unit This user manual provides essential safety, operating, and maintenance instructions for the Single Package Cooling Unit or Heat Pump Unit by Nortek Global HVAC. Learn about system features, thermostat operation, troubleshooting tips, and warranty information. |