Aspen AFL Series Hydronic Heat Furnace

Multi-Position Air Handler

Application Versatility

The AFL Series is designed for upflow, downflow, horizontal left, or horizontal right installations as shipped. For compliance with A2L refrigerants, a Refrigerant Detection System (RDS) is required, and factory-installed RDS are available on A2L refrigerant-ready air handlers, meeting UL 60335 standards. The units are ETL listed for R22 and R410A, and also for R454B and R32 when equipped with an RDS.

Motor

The X-13 motor features 5 speed taps, with variable speed options available through special wiring. Motors are pre-programmed at the factory for ease of use.

Modular Hydronic Heat Kits

Standard heat kits are available with either circuit breakers or terminal blocks, and can be easily installed in the field or ordered factory-installed. A freeze stat is standard and wired into the circulating pump control circuit. Controls are accessible from the front for convenient servicing. Electrical connections can be made from the top or left. A fan time delay relay is standard for enhanced efficiency. Heat kits are offered with or without a circulating pump and check valve. Units include an auxiliary relay for remote pump operation. Schrader ports are standard on the water-out manifold, with a hose bib available as an option.

Blower

Direct drive multi-speed blowers provide quiet and efficient air circulation, allowing for precise air volume selection. Five motor speeds can be easily set via motor terminals. Blowers are mounted on rails for straightforward removal during service.

Cabinet

The sturdy, galvanized steel cabinet features painted front panels. The cabinet is fully insulated with 1/2" micro mat non-hygroscopic insulation to prevent sweating, encapsulate glass fibers, and provide excellent R-value. Stick pins ensure the insulation remains securely in place. Units are shipped with a disposable filter in the filter rack.

Warranty

A five-year limited parts warranty is provided with product registration. See the warranty information section on Aspen's official website for full terms and conditions.

Helpful Links

Performance and Electrical Data

The following tables detail the heating/cooling performance and electrical data for various AFL Series models, including different speed taps, coil configurations, and capacities. Electrical data includes Minimum Circuit Ampacity (MCA) and Maximum Breaker or Fuse Size (MFU).

MODEL SPEED TAP HEATING COIL HYDRONIC COIL A P. HEATING @ 3.5 GPM CAPACITY (BTU/HR @ 3.5 GPM) ELECTRICAL DATA MIN. CIRCUIT AMPACITY MAX. BREAKER OR FUSE SIZE
ROW SLAB SIZE FT. WATER 120° 140° 160° 180° MCA MFU
WC2SP222.8177002490032300396006.715
WC2SP122.8202002850036900454006.715
WC3SP232.1216003050039400484006.715
WC3SP132.1250003530045800563006.715
WC2SR225.6187002640034100419008.315
WC2SR125.6216003050039500485008.315
WC3SR234.2229003230041700512008.315
WC3SR134.2269003800049100603008.315
WC2SP222.8221003130040500499009.2
WC2SP122.8237003350043500536009.2
WC3SP232.1277003910050700624009.2
WC3SP132.1298004210054700673009.2
WC4SP241.1310004390057000701009.2
WC4SP141.1335004740061500758009.2
WC2SR225.62390033800437005380010.820
WC2SR125.62580036500473005820010.8
WC3SR234.23010042500551006770010.8
WC3SR134.23280046300600007370010.8
WC4SR242.23400048000623007660010.8
WC4SR142.23720052600681008380010.8
WC2LP323.63020042600553006800014.3
WC2LP223.63170044800580007140014.3
WC2LP123.63290046600604007440014.3
WC3LP331.73630051400667007660014.3
WC3LP231.73820054000701008060014.3
WC3LP131.73970056200730008400014.3
WC4LP341.14360061600799009290014.3
WC4LP241.14590064900842009800014.3
WC4LP141.147800676008770010220014.3
WC2LR327.23320046800606007450015.830
WC2LR227.23500049400640007870015.8
WC2LR127.23660051800671008250015.8
WC3LR333.44050057300742008440015.8
WC3LR233.44290060700786008950015.8
WC3LR133.44500063600825009400015.8
WC4LR342.249000693008970010360015.8
WC4LR242.252200738009560011040015.8
WC4LR142.2550007770010080011630015.8

Air Handler Chassis Nomenclature

AFL CABINET SIZE & NOM. TON. OPTION CODE
S
120V ECM MOTOR LOW BOY HYDRONIC FURNACE S (SMALL) 18 & 24
M (MEDIUM) 30 & 36
L (LARGE) 42, 48 & 60
-001
OPTION CODE

X-13 Blower Data

The following table shows the Cubic Feet per Minute (CFM) output of the X-13 blower at various external static pressures (0.1" to 0.5") for different speed taps (T1 to T5).

MODEL SPEEDTAP CFM VS EXTERNAL STATIC* (DRY COIL)
0.1 0.2 0.3 0.4 0.5
AFLS+ WC2SR WC3SRT1900855800740675
T2670650615600550
T3460445420400385
T4900855800740675
T5350335315300280
AFLM+ WC2SR WC3SR WC4SRT11200113010851030985
T2114010901030975910
T3905870835800740
T4760730695650605
T5475450425400375
AFLL+ WC2LR WC3LR WC4LRT118751800173016901625
T217051660160015301480
T314951460143014001365
T413401295125512001140
T5910875840800745

*Dry coil with filter in place.

Physical Data

MODEL TRANSFORMER VOLTAGE FILTER SIZE WHEEL (DIA. x WIDTH) MOTOR HP MOTOR F.L.A. NOM. CFM RANGE PUMP VOLTAGE PUMP HP PUMP AMPS PUMP VOLTAGE PUMP HP PUMP AMPS
AFLS AFLLM AFLL
120V - 60Hz16x20x19 x 61/34.8800-3001151/40.52
10 x 81/26.81200 - 4001151/81.8
12 x 9110.91800-800

Hydronic Heat Kit Nomenclature

HEAT KIT SERIES POWER CONNECTION CABINET SIZE & NOM. TONNAGE PUMP TYPE
W C ROWS
MULTI-POSITION HYDRONIC HEAT C = CIRCUIT BREAKER
T = TERMINAL BLOCK
2
3
4
S (SMALL) 18/24
M (MEDIUM) 30 & 36
L (LARGE) 42, 48 & 60
P = No Pump
P = Standard Taco 006 Pump w/ Check Valve (factory-installed)
R = Taco 008 Pump High Head (factory-installed)
R = Taco 009 Pump High Head (to be mounted external to all units except for multi-position units)

Cabinet Installation Clearances

CLEARANCE AREA OPERATION SERVICE
TOP00
FRONT3030
SIDES00
REAR300

Dimensions and Shipping Specifications

MODEL A B DUCT OPENING BOTTOM OPENING FILTER SHIPPING INFO
C D E WEIGHT SKID QTY
AFLS213018-3/41218-1/216X2083
AFLM213018-3/41218-1/216X20858
AFLL24-1/23322-1/414-1/222-1/420X20110

PDF preview unavailable. Download the PDF instead.

AFL-SS-AH-013 Adobe PDF Library 17.0 Adobe InDesign 20.4 (Macintosh)

Related Documents

Preview Aspen Manufacturing DE Series Cased Multi-Position Coils - Technical Specifications
Explore the features, specifications, and customization options for Aspen Manufacturing's DE Series cased multi-position coils, designed for R-410A, R-22, R-454B, and R-32 refrigerants.
Preview Aspen AAW Series Electric Heat Air Handler - Vertical Wall Mount Specifications
Detailed specifications, features, and performance data for the Aspen AAW Series Vertical Wall Mount Electric Heat Air Handler. Includes information on A2L refrigerant compatibility, PSC motors, and dimensions.
Preview Aspen Manufacturing CP Series Horizontal Plenum Coils - Product Specifications and Data
Detailed specifications, features, warranty information, and dimensional data for Aspen Manufacturing's CP Series dedicated horizontal copper coils with plenums. Includes performance data and cabinet dimensions for various models.
Preview Aspen ABM Series Hydronic Air Handler - Multi-Position HVAC Unit
Discover the Aspen ABM Series Hydronic Air Handler, a versatile multi-position unit designed for efficient heating and cooling. Featuring A2L refrigerant compatibility (R32, R454B), robust construction, and detailed performance specifications for various HVAC applications.
Preview Aspen A2L ABM AFM Series Air Handler Installation and Operation Manual
Comprehensive installation and operation guide for the Aspen A2L ABM AFM Series Multi-Position, Hydronic Heat Copper Coil Air Handlers. Covers safety instructions, installation procedures, wiring, system charging, and maintenance.
Preview Aspen Manufacturing ABW Series Hydronic Air Handlers - Technical Specifications
Detailed specifications, features, and performance data for Aspen Manufacturing's ABW Series Hydronic Air Handlers, designed for versatile HVAC applications with various refrigerant options and modular heat kits.
Preview Aspen AFW & ABW Series Vertical Wall Mount Air Handler Installation Guide
Comprehensive installation guide for Aspen AFW & ABW Series Vertical Wall Mount Air Handlers with Hydronic Heat, covering safety instructions, preparation, installation steps, ductwork, metering devices, refrigerant lines, electrical installation, system charging, start-up procedures, operation, maintenance, and troubleshooting.
Preview Aspen A2L Refrigerant Multi-Position Air Handlers Installation Guide & Operation Manual
This manual provides comprehensive installation and operation instructions for Aspen's A2L refrigerant multi-position air handlers, including the AAM, AEM, LAM, and LEM series. It covers safety precautions, general information, installation procedures, electrical wiring, system charging, and leak detection systems.