Aspen AFL Series Hydronic Heat Furnace
Multi-Position Air Handler
Application Versatility
The AFL Series is designed for upflow, downflow, horizontal left, or horizontal right installations as shipped. For compliance with A2L refrigerants, a Refrigerant Detection System (RDS) is required, and factory-installed RDS are available on A2L refrigerant-ready air handlers, meeting UL 60335 standards. The units are ETL listed for R22 and R410A, and also for R454B and R32 when equipped with an RDS.
Motor
The X-13 motor features 5 speed taps, with variable speed options available through special wiring. Motors are pre-programmed at the factory for ease of use.
Modular Hydronic Heat Kits
Standard heat kits are available with either circuit breakers or terminal blocks, and can be easily installed in the field or ordered factory-installed. A freeze stat is standard and wired into the circulating pump control circuit. Controls are accessible from the front for convenient servicing. Electrical connections can be made from the top or left. A fan time delay relay is standard for enhanced efficiency. Heat kits are offered with or without a circulating pump and check valve. Units include an auxiliary relay for remote pump operation. Schrader ports are standard on the water-out manifold, with a hose bib available as an option.
Blower
Direct drive multi-speed blowers provide quiet and efficient air circulation, allowing for precise air volume selection. Five motor speeds can be easily set via motor terminals. Blowers are mounted on rails for straightforward removal during service.
Cabinet
The sturdy, galvanized steel cabinet features painted front panels. The cabinet is fully insulated with 1/2" micro mat non-hygroscopic insulation to prevent sweating, encapsulate glass fibers, and provide excellent R-value. Stick pins ensure the insulation remains securely in place. Units are shipped with a disposable filter in the filter rack.
Warranty
A five-year limited parts warranty is provided with product registration. See the warranty information section on Aspen's official website for full terms and conditions.
Helpful Links
- VIEW PRODUCT ONLINE: For full warranty terms and conditions, please refer to the Warranty Information section on Aspen's official website.
- AHRI QUICK MATCH TOOL: Identify the correct AHRI-certified match for any Aspen coil, air handler, or Aspen PRO air handler. Available on the Resources page.
Performance and Electrical Data
The following tables detail the heating/cooling performance and electrical data for various AFL Series models, including different speed taps, coil configurations, and capacities. Electrical data includes Minimum Circuit Ampacity (MCA) and Maximum Breaker or Fuse Size (MFU).
MODEL | SPEED TAP | HEATING COIL | HYDRONIC COIL A P. | HEATING @ 3.5 GPM CAPACITY (BTU/HR @ 3.5 GPM) | ELECTRICAL DATA | MIN. CIRCUIT AMPACITY | MAX. BREAKER OR FUSE SIZE | |||
---|---|---|---|---|---|---|---|---|---|---|
ROW | SLAB SIZE | FT. WATER | 120° | 140° | 160° | 180° | MCA | MFU | ||
WC2SP | 2 | 2 | 2.8 | 17700 | 24900 | 32300 | 39600 | 6.7 | 15 | |
WC2SP | 1 | 2 | 2.8 | 20200 | 28500 | 36900 | 45400 | 6.7 | 15 | |
WC3SP | 2 | 3 | 2.1 | 21600 | 30500 | 39400 | 48400 | 6.7 | 15 | |
WC3SP | 1 | 3 | 2.1 | 25000 | 35300 | 45800 | 56300 | 6.7 | 15 | |
WC2SR | 2 | 2 | 5.6 | 18700 | 26400 | 34100 | 41900 | 8.3 | 15 | |
WC2SR | 1 | 2 | 5.6 | 21600 | 30500 | 39500 | 48500 | 8.3 | 15 | |
WC3SR | 2 | 3 | 4.2 | 22900 | 32300 | 41700 | 51200 | 8.3 | 15 | |
WC3SR | 1 | 3 | 4.2 | 26900 | 38000 | 49100 | 60300 | 8.3 | 15 | |
WC2SP | 2 | 2 | 2.8 | 22100 | 31300 | 40500 | 49900 | 9.2 | ||
WC2SP | 1 | 2 | 2.8 | 23700 | 33500 | 43500 | 53600 | 9.2 | ||
WC3SP | 2 | 3 | 2.1 | 27700 | 39100 | 50700 | 62400 | 9.2 | ||
WC3SP | 1 | 3 | 2.1 | 29800 | 42100 | 54700 | 67300 | 9.2 | ||
WC4SP | 2 | 4 | 1.1 | 31000 | 43900 | 57000 | 70100 | 9.2 | ||
WC4SP | 1 | 4 | 1.1 | 33500 | 47400 | 61500 | 75800 | 9.2 | ||
WC2SR | 2 | 2 | 5.6 | 23900 | 33800 | 43700 | 53800 | 10.8 | 20 | |
WC2SR | 1 | 2 | 5.6 | 25800 | 36500 | 47300 | 58200 | 10.8 | ||
WC3SR | 2 | 3 | 4.2 | 30100 | 42500 | 55100 | 67700 | 10.8 | ||
WC3SR | 1 | 3 | 4.2 | 32800 | 46300 | 60000 | 73700 | 10.8 | ||
WC4SR | 2 | 4 | 2.2 | 34000 | 48000 | 62300 | 76600 | 10.8 | ||
WC4SR | 1 | 4 | 2.2 | 37200 | 52600 | 68100 | 83800 | 10.8 | ||
WC2LP | 3 | 2 | 3.6 | 30200 | 42600 | 55300 | 68000 | 14.3 | ||
WC2LP | 2 | 2 | 3.6 | 31700 | 44800 | 58000 | 71400 | 14.3 | ||
WC2LP | 1 | 2 | 3.6 | 32900 | 46600 | 60400 | 74400 | 14.3 | ||
WC3LP | 3 | 3 | 1.7 | 36300 | 51400 | 66700 | 76600 | 14.3 | ||
WC3LP | 2 | 3 | 1.7 | 38200 | 54000 | 70100 | 80600 | 14.3 | ||
WC3LP | 1 | 3 | 1.7 | 39700 | 56200 | 73000 | 84000 | 14.3 | ||
WC4LP | 3 | 4 | 1.1 | 43600 | 61600 | 79900 | 92900 | 14.3 | ||
WC4LP | 2 | 4 | 1.1 | 45900 | 64900 | 84200 | 98000 | 14.3 | ||
WC4LP | 1 | 4 | 1.1 | 47800 | 67600 | 87700 | 102200 | 14.3 | ||
WC2LR | 3 | 2 | 7.2 | 33200 | 46800 | 60600 | 74500 | 15.8 | 30 | |
WC2LR | 2 | 2 | 7.2 | 35000 | 49400 | 64000 | 78700 | 15.8 | ||
WC2LR | 1 | 2 | 7.2 | 36600 | 51800 | 67100 | 82500 | 15.8 | ||
WC3LR | 3 | 3 | 3.4 | 40500 | 57300 | 74200 | 84400 | 15.8 | ||
WC3LR | 2 | 3 | 3.4 | 42900 | 60700 | 78600 | 89500 | 15.8 | ||
WC3LR | 1 | 3 | 3.4 | 45000 | 63600 | 82500 | 94000 | 15.8 | ||
WC4LR | 3 | 4 | 2.2 | 49000 | 69300 | 89700 | 103600 | 15.8 | ||
WC4LR | 2 | 4 | 2.2 | 52200 | 73800 | 95600 | 110400 | 15.8 | ||
WC4LR | 1 | 4 | 2.2 | 55000 | 77700 | 100800 | 116300 | 15.8 |
Air Handler Chassis Nomenclature
AFL | CABINET SIZE & NOM. TON. | OPTION CODE |
---|---|---|
S | ||
120V ECM MOTOR LOW BOY HYDRONIC FURNACE | S (SMALL) 18 & 24 M (MEDIUM) 30 & 36 L (LARGE) 42, 48 & 60 |
-001 OPTION CODE |
X-13 Blower Data
The following table shows the Cubic Feet per Minute (CFM) output of the X-13 blower at various external static pressures (0.1" to 0.5") for different speed taps (T1 to T5).
MODEL | SPEEDTAP | CFM VS EXTERNAL STATIC* (DRY COIL) | |||||
---|---|---|---|---|---|---|---|
0.1 | 0.2 | 0.3 | 0.4 | 0.5 | |||
AFLS+ WC2SR WC3SR | T1 | 900 | 855 | 800 | 740 | 675 | |
T2 | 670 | 650 | 615 | 600 | 550 | ||
T3 | 460 | 445 | 420 | 400 | 385 | ||
T4 | 900 | 855 | 800 | 740 | 675 | ||
T5 | 350 | 335 | 315 | 300 | 280 | ||
AFLM+ WC2SR WC3SR WC4SR | T1 | 1200 | 1130 | 1085 | 1030 | 985 | |
T2 | 1140 | 1090 | 1030 | 975 | 910 | ||
T3 | 905 | 870 | 835 | 800 | 740 | ||
T4 | 760 | 730 | 695 | 650 | 605 | ||
T5 | 475 | 450 | 425 | 400 | 375 | ||
AFLL+ WC2LR WC3LR WC4LR | T1 | 1875 | 1800 | 1730 | 1690 | 1625 | |
T2 | 1705 | 1660 | 1600 | 1530 | 1480 | ||
T3 | 1495 | 1460 | 1430 | 1400 | 1365 | ||
T4 | 1340 | 1295 | 1255 | 1200 | 1140 | ||
T5 | 910 | 875 | 840 | 800 | 745 |
*Dry coil with filter in place.
Physical Data
MODEL | TRANSFORMER | VOLTAGE | FILTER SIZE | WHEEL (DIA. x WIDTH) | MOTOR HP | MOTOR F.L.A. | NOM. CFM RANGE | PUMP VOLTAGE | PUMP HP | PUMP AMPS | PUMP VOLTAGE | PUMP HP | PUMP AMPS |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AFLS | AFLLM | AFLL | |||||||||||
120V - 60Hz | 16x20x1 | 9 x 6 | 1/3 | 4.8 | 800-300 | 115 | 1/40 | .52 | |||||
10 x 8 | 1/2 | 6.8 | 1200 - 400 | 115 | 1/8 | 1.8 | |||||||
12 x 9 | 1 | 10.9 | 1800-800 |
Hydronic Heat Kit Nomenclature
HEAT KIT SERIES | POWER CONNECTION | CABINET SIZE & NOM. TONNAGE | PUMP TYPE | |
---|---|---|---|---|
W | C | ROWS | ||
MULTI-POSITION HYDRONIC HEAT | C = CIRCUIT BREAKER T = TERMINAL BLOCK |
2 3 4 |
S (SMALL) 18/24 M (MEDIUM) 30 & 36 L (LARGE) 42, 48 & 60 |
P = No Pump P = Standard Taco 006 Pump w/ Check Valve (factory-installed) R = Taco 008 Pump High Head (factory-installed) R = Taco 009 Pump High Head (to be mounted external to all units except for multi-position units) |
Cabinet Installation Clearances
CLEARANCE AREA | OPERATION | SERVICE |
---|---|---|
TOP | 0 | 0 |
FRONT | 30 | 30 |
SIDES | 0 | 0 |
REAR | 30 | 0 |
Dimensions and Shipping Specifications
MODEL | A | B | DUCT OPENING | BOTTOM OPENING | FILTER | SHIPPING INFO | ||
---|---|---|---|---|---|---|---|---|
C | D | E | WEIGHT | SKID QTY | ||||
AFLS | 21 | 30 | 18-3/4 | 12 | 18-1/2 | 16X20 | 83 | |
AFLM | 21 | 30 | 18-3/4 | 12 | 18-1/2 | 16X20 | 85 | 8 |
AFLL | 24-1/2 | 33 | 22-1/4 | 14-1/2 | 22-1/4 | 20X20 | 110 |
Related Documents
![]() |
Aspen Manufacturing DE Series Cased Multi-Position Coils - Technical Specifications Explore the features, specifications, and customization options for Aspen Manufacturing's DE Series cased multi-position coils, designed for R-410A, R-22, R-454B, and R-32 refrigerants. |
![]() |
Aspen AAW Series Electric Heat Air Handler - Vertical Wall Mount Specifications Detailed specifications, features, and performance data for the Aspen AAW Series Vertical Wall Mount Electric Heat Air Handler. Includes information on A2L refrigerant compatibility, PSC motors, and dimensions. |
![]() |
Aspen Manufacturing CP Series Horizontal Plenum Coils - Product Specifications and Data Detailed specifications, features, warranty information, and dimensional data for Aspen Manufacturing's CP Series dedicated horizontal copper coils with plenums. Includes performance data and cabinet dimensions for various models. |
![]() |
Aspen ABM Series Hydronic Air Handler - Multi-Position HVAC Unit Discover the Aspen ABM Series Hydronic Air Handler, a versatile multi-position unit designed for efficient heating and cooling. Featuring A2L refrigerant compatibility (R32, R454B), robust construction, and detailed performance specifications for various HVAC applications. |
![]() |
Aspen A2L ABM AFM Series Air Handler Installation and Operation Manual Comprehensive installation and operation guide for the Aspen A2L ABM AFM Series Multi-Position, Hydronic Heat Copper Coil Air Handlers. Covers safety instructions, installation procedures, wiring, system charging, and maintenance. |
![]() |
Aspen Manufacturing ABW Series Hydronic Air Handlers - Technical Specifications Detailed specifications, features, and performance data for Aspen Manufacturing's ABW Series Hydronic Air Handlers, designed for versatile HVAC applications with various refrigerant options and modular heat kits. |
![]() |
Aspen AFW & ABW Series Vertical Wall Mount Air Handler Installation Guide Comprehensive installation guide for Aspen AFW & ABW Series Vertical Wall Mount Air Handlers with Hydronic Heat, covering safety instructions, preparation, installation steps, ductwork, metering devices, refrigerant lines, electrical installation, system charging, start-up procedures, operation, maintenance, and troubleshooting. |
![]() |
Aspen A2L Refrigerant Multi-Position Air Handlers Installation Guide & Operation Manual This manual provides comprehensive installation and operation instructions for Aspen's A2L refrigerant multi-position air handlers, including the AAM, AEM, LAM, and LEM series. It covers safety precautions, general information, installation procedures, electrical wiring, system charging, and leak detection systems. |