Controls for 37MU(R,H)A & Crossover Applications

37MU(R,H)A & Crossover Applications

General Installation Notes:

Product Compatibility:

Air Handlers Gas Furnaces C / B
FE5B 59MN7C / 987M
FT5 59TN6C / 926S
FJ5 59CU5B / 986T
FG5 59TP6C / 926T
F55 59SP6B / 926S
FMA5X 59SC6A / 916S
FMU(C)5X 59SC2E / 912S
FMU(C)5Z 59SU5 / 935S
FMA5L 58TN0B / 880TB
Coils 58CU0B / 830CB
CVAVA 58TP0B / 821TB
CVAMA 58SP0B / 820SB
CAAMP 58SC0B / 800SB
CSAHP 58SB0B / 912S
58SU0B / 830SB
Oil Furnaces Hi (M) / Lowboy (L)
OVM / OVL
OBM / OBL

Note: Single Fan ODU height varies by capacity.

Outdoor units models include: 37MURA* 18, 24, 30, 36, 48, 60K and 37MUHA* 18, 24, 30, 36, 48K, 37MUHA 60K.

37MU(R,H)A & Crossover Application Thermostat Choices

Most 24-Volt thermostats will work for Crossover Applications. Refer to the Application/Installation instructions for specific details for the model installing.

It is strongly recommended that these systems are always wired as a Heat Pump, not Conventional.

NOTE: Dual Fuel Crossover Applications require the thermostat to sense outside temperature to operate correctly.

Thermostat Options:

Attention: Thermostat must sense Outdoor temp for Dual Fuel Applications.

37MU(R,H)A – Applications Requiring Defrost or Error Signal from Outdoor Unit ODU

An R wire from the Indoor Unit to the Outdoor would be required only in applications where a Defrost (D-terminal ODU) or Error (L-terminal ODU) signal is needed.

Applications would include:

Outdoor Unit MU(R,H)A Wiring:

Set S1-2 to ON at ODU for 24-Volt Connections.

Terminal connections:

Res. Indoor Coil Dissipation Board Overview

Main components:

Dissipation Board Wiring (Example):

PIN COLOR 1-Stage Label 2-Stage Label
1 Red to Furnace SEC1 to Furnace SEC1
2 Grn/Vio to Furnace G to Furnace G
3 White to TSTAT W to TSTAT W1
4 Yel/Vio to OD unit Y to OD unit Y1
5 Yellow to Furnace Y to Furnace Y1
6 Green to TSTAT G to TSTAT G
7 White/Vio to Furnace W to Furnace W1
8 Black to Furnace C to Furnace C

See Installation Instructions For Specific Details.

Model Number: 350110-701 REV. C

Dissipation Board Overview

Sensor connection

Main harness connection

Flash Code Chart:

Yellow (LED) Mode Status
Solid Normal Operation Normal Operation
Flashing 1 Compressor Lockout Normal Operation
Flashing 2 Sensor Open Normal Operation
Flashing 3 Defrost Mode Normal Operation
Flashing 4 Defrost Mode Normal Operation
Flashing 5 Feed with All Light Sensor Normal Operation
Flashing 6 Feed with All Light Sensor Normal Operation
Flashing 7 Y1/Y2 to Compressor Normal Operation
Flashing 8 Y1/Y2 to Compressor Normal Operation

Dissipation Board Overview

Wire connections:

Wiring Diagram:

Stat connections

Furnace transformer

Furnace control connections

37MU(R,H)A & 1-Stage Furnace - Dual Fuel Applications

Includes Carrier/Bryant 2-Stage Gas Furnaces utilizing Comfort Heat Technology® or Adaptive Mode.

When setting up the thermostat, make sure to disable furnace and heat pump running at the same time.

Thermostat Notes:

System Notes:

Wiring Diagram:

Thermostat Connections: W2, W1, O/B, Y2, Y1, G, C, Rc

Dissipation Board Connections: W-IN, Y-IN, B, G-IN, Y-Out

Single Stage Furnace Connections: R, C, G, Y1/Y2, W

Outdoor Unit MU(R,H)A Connections: B, Y2, Y1, W, C, R, D

Note: Y1 Terminal at ODU can be utilized instead of Y2 for slower ramp up rate.

Attention: Thermostat must have Outdoor temp sensor for Dual Fuel Applications.

Outdoor Unit Wiring: Set S1-2 to ON at ODU for 24-Volt Connections.

37MU(R,H)A & FT5 / FTG / F55 Fan Coils

Thermostat Notes:

System Notes:

Wiring Diagram:

Thermostat Connections: W2, W1, O/B, Y2, Y1, G, C, Rc

Dissipation Board Connections: W-IN, Y-IN, W-OUT, Y1

Fan Coil Connections: R, C, G, Y1/Y2, W/W1, W2

Outdoor Unit MU(R,H)A Connections: B, Y1, Y2, W, C, R, D

Note: Y1 Terminal at ODU can be utilized instead of Y2 for slower ramp up rate.

Recommendation: Recommend “HP-EFF” setting on Easy Select Board during initial set up.

Outdoor Unit Wiring: Set S1-2 to ON at ODU for 24-Volt Connections.

37MU(R,H)A & FT5 / FTG / F55 Fan Coils (7-wire configuration)

Thermostat Notes:

System Notes:

Wiring Diagram:

Thermostat Connections: W2, W1, O/B, Y2, Y1, G, C, Rc

Dissipation Board Connections: W-IN, Y-IN, W-OUT, Y1

Fan Coil Connections: R, C, G, Y1/Y2, W/W1, W2

Outdoor Unit MU(R,H)A Connections: B, Y1, Y2, W, C, R, D

Note: Y1 Terminal at ODU can be utilized instead of Y2 for slower ramp up rate.

Recommendation: Recommend “HP-EFF” setting on Easy Select Board during initial set up.

Outdoor Unit Wiring: Set S1-2 to ON at ODU for 24-Volt Connections.

37MU(R,H)A & F55 Fan Coils (7-wire configuration)

Thermostat Notes:

System Notes:

Wiring Diagram:

Thermostat Connections: W2, W1, O/B, Y2, Y1, G, C, Rc

Dissipation Board Connections: W-IN, Y-IN, W-OUT, Y1

Fan Coil Connections: R, C, G, Y1/Y2, W/W1, W2

Outdoor Unit MU(R,H)A Connections: B, Y1, Y2, W, C, R, D

Note: Y1 Terminal at ODU can be utilized instead of Y2 for slower ramp up rate.

Recommendation: Recommend “HP-EFF” setting on Easy Select Board during initial set up.

Outdoor Unit Wiring: Set S1-2 to ON at ODU for 24-Volt Connections.

37MU(R,H)A & FJ5 Fan Coils

Thermostat Notes:

System Notes:

Wiring Diagram:

Thermostat Connections: W1, O/B, Y1, Y2, G, C, Rc

Dissipation Board Connections: W-OUT, W-IN, Y-IN, Y-OUT

Fan Coil Connections: R, C, G, E, W2, W3

Outdoor Unit MU(R,H)A Connections: B, Y2, Y1, W, C, R, D

Note: Y1 Terminal at ODU can be utilized instead of Y2 for slower ramp up rate.

Outdoor Unit Wiring: Set S1-2 to ON at ODU for 24-Volt Connections.

37MU(R,H)A & Multi-family Indoor Units FMA5L(X) / FMC5X(Z) / FMU5X(Z) Fan Coils

Notes:

Wiring Diagram:

Thermostat Connections: W1, O/B, Y2, Y1, G, C, Rc

Fan Coil Connections: R, C, G, Y1, O/B, W, Y, O/B, C

Outdoor Unit MU(R,H)A Connections: B, Y2, Y1, W, C, R, D

Note: Y1 Terminal at ODU can be utilized instead of Y2 for slower ramp up rate.

Outdoor Unit Wiring: Set S1-2 to ON at ODU for 24-Volt Connections.

Ductless systems and Residential systems can talk without wires

Cielo's Linked feature can talk through the Cielo App. Decisions can change the other based on outdoor temp or state of other system and more.

As you work your way through the decision-making process, it takes a few screens, but in the end a "Link conditions" screen shows you the rule. Think of it as "If this, then that". The rule can be toggled ON and OFF.

Thermostat Options:

Cielo App Features:

Models: 60K, 18, 24, 30, 36, 48, 60K, 18, 24, 30, 36, 48K, 37MUHA Ductless Mini Split Heat Pump, 37MUHA, Ductless Mini Split Heat Pump, Mini Split Heat Pump, Split Heat Pump, Heat Pump

PDF preview unavailable. Download the PDF instead.

37MURHA-Crossover-Applications-6.11.2025 Adobe PDF Library 25.1.250

Related Documents

Preview Carrier Evaporator Coils: Enhanced Durability, Comfort, and Peace of Mind
Explore Carrier's high-efficiency aluminum evaporator coils, designed for enhanced durability, comfort, and peace of mind. Featuring Vertex™ Technology and Puron Advance™ refrigerant, these coils offer superior performance and environmental benefits for your HVAC system.
Preview Carrier Fan Coils: Efficiency and Comfort for Reliable Operation
Carrier's Infinity, Performance, and Comfort Series fan coils offer advanced features for optimal indoor comfort and energy savings. Learn about their efficiency, durability, humidity management, and environmental benefits, including Puron Advance™ refrigerant.
Preview Carrier FT5, FG5 Fan Coil Installation Instructions for R-454B Refrigerant
Comprehensive installation guide for Carrier FT5 and FG5 Fan Coil units designed for Puron Advance™ R-454B refrigerant. Covers safety, unit mounting, electrical connections, airflow adjustments, and troubleshooting for various configurations including upflow, horizontal, and downflow installations.
Preview Carrier FMA5L FMA5X Multifamily Wall-Hung Fan Coils Product Data & Specifications
Detailed product data, specifications, performance charts, electrical information, and accessories for Carrier FMA5L and FMA5X multifamily wall-hung fan coil units using Puron Advance refrigerant.
Preview Carrier FT5 Fan Coil: Performance, Efficiency, and InteliSense™ Technology
Explore the Carrier FT5 Fan Coil, featuring InteliSense™ technology, Puron Advance® refrigerant, and a variable speed ECM motor for superior comfort, efficiency, and environmental responsibility. View detailed specifications, performance data, and model information for residential and light commercial HVAC applications.
Preview Carrier FT5/FG5 Fan Coil Installation Instructions
Comprehensive installation manual for Carrier FT5 and FG5 Fan Coil units, detailing setup, safety, wiring, and troubleshooting for Puron Advance™ refrigerant systems. Covers various installation types and system configurations.
Preview Carrier Cool Cash Rebates: Save on Home Comfort Systems
Explore Carrier's Cool Cash promotion offering rebates up to $2,100 on qualified home comfort systems, including heat pumps, air conditioners, and furnaces. Learn about flexible financing and available models.
Preview Carrier NAVA4 Accessory Coil Installation Instructions
This document provides detailed installation instructions for the Carrier NAVA4 Accessory Coil, designed for FEV fan units. It covers safety precautions, procedures for downflow and upflow applications, refrigerant tubing, condensate drain setup, unit start-up, and maintenance. Includes wiring diagrams and airflow performance data for R-410A systems.