Schneider Electric REL52132 Easergy P3 Product Data Sheet
Characteristics
REL52132
Easergy P3T32 6CT 3lo ringlug 4VT 6DI 10DO 110-230V DI110V 2OBIO 5ARC RS485 RJ45 ANSI
Product availability: Stock - Normally stocked in distribution facility
Price*: 6155.69 USD
Main
Range of Product | Easergy P3 |
---|---|
Product or Component Type | Protection relay |
Relay application | Transformer |
Device short name | P3T32-CCG1A-DA1FA-BBAAB |
Device mounting | Flush |
[Us] rated supply voltage | 48...230 V AC/DC |
Input type | 6 1/5 A CT phase current 2 5/1 A CT residual current 1 1/0.2 A CT residual current 4 100 V/110 V VT voltage |
Number of sensors | 0 temperature |
Digital input number | 0 arc |
Number of Outputs | 6.0 |
Analogue input number | 10 DO |
Analogue output number | 1 watchdog |
Integrated connection type | 0 0 Front USB port 1 Rear RJ45 1 Rear RS485 1 |
Communication port protocol | IEC 61850 ed. 1 IEC 61850 ed. 2 IEC 60870-5-101 DNP3 TCP Modbus TCP EtherNet/IP IEC 60870-5-103 DNP3 Modbus RTU DeviceNet SPAbus |
Cybersecurity | Password protection Port hardening |
Protection type
- Overfluxing (V/Hz) 24
- Synchro-check 25
- Undervoltage 27
- Directional active underpower 37P
- Negative sequence overcurrent 46
- Thermal overload protection 49
- Earth fault overcurrent 50N/51N
- Phase overcurrent 50/51
- Breaker failure 50BF
- Switch ON to fault (SOTF)
- Capacitor bank unbalance 51C
- Capacitor overvoltage 59C
- Overvoltage 59
- Earth fault overvoltage 59N
- Restricted earth fault 64REF
- Directional phase overcurrent 67
- Directional earth fault 67N
- H2 detection 68H2
- H5 detection 68H5
- Underfrequency 81/81N
- Rate of change of frequency 81R
- Lockout relay 86
- Two-winding transformer differential 87T
- Programmable stages 99
- Programmable curve
- Cold load pick-up
Arc flash protection
Yes
Relay Type
Differential current relay
Type of measurement
- Current 3-phase
- Current zero sequence
- Current positive sequence
- Current negative sequence
- Current ratio of negative and positive
- Voltage phase to earth
- Voltage phase to phase
- Voltage zero sequence
- Voltage positive sequence
- Voltage negative sequence
- Voltage ratio of negative and positive
- Short circuit fault reactance
- Fault location current
- Earth fault reactance
- Frequency
- Active power
- RMS active power
- Reactive power
- RMS reactive power
- Apparent power
- RMS apparent power
- Active energy
- Reactive energy
- Cos φ
- Tan φ
- Power angle
- Power factor
- Voltage phasor diagram view
- Current phasor diagram view
- Current 2nd, 15th harmonics with THD
- Voltage 2nd, 15th harmonics with THD
- Condition monitoring CB wear
- Voltage interruption
Control type
- Switchgear control and monitoring
- Programmable switchgear interlocking
- Local control on single-line diagram
- Local control with I/O keys
- Local/Remote control
- 2 function keys
- Mobile application with Easergy SmartApp
- Web-server
Single line diagram
3 controlled + 5 displayed
Setting
4
Monitoring function
- Trip circuit supervision 74
- Circuit breaker monitoring
- Relay self-monitoring
- Event recording
- Disturbance recording
- Tripping context
Network and machine diagnosis type
CT/VT supervision
Switchgear diagnosis type
Trip circuit supervision TCS
Connections - terminals
- Screw removable (digital input/output)
- Ring lugs fixed (current transformer)
- Pin removable (voltage transformer)
Complementary
Operating threshold | 110 V AC/DC |
---|---|
Time synchronisation protocol | SNTP |
Web server | Embedded HTTP server |
Display type | LCD LCD |
Number of key | 2 customizable |
Local signalling | 2 LEDs 16 LEDs programmable |
Height | 6.93 In (176 mm) |
Width | 10.63 In (270 mm) |
Depth | 9.06 In (230 mm) |
Net weight | 9.26 Lb(US) (4.2 kg) maximum |
Environment
Electromagnetic compatibility
Emission tests IEC/EN 60255-26 ed. 3
Emission tests class A CISPR 11
Emission tests class A CISPR 22
EMC immunity IEC/EN 60255-26 ed. 3
EMC immunity EN/IEC 61000-4-18
EMC immunity IEC 60255-22-1
EMC immunity level 4 EN/IEC 61000-4-2
EMC immunity IEC 60255-22-2
EMC immunity level 3 EN/IEC 61000-4-3
EMC immunity IEC 60255-22-3
EMC immunity level 4 EN/IEC 61000-4-4
EMC immunity IEC 60255-22-4
EMC immunity level 3 EN/IEC 61000-4-5
EMC immunity IEC 60255-22-5
EMC immunity level 3 EN/IEC 61000-4-6
EMC immunity IEC 60255-22-6
EMC immunity EN/IEC 61000-4-8
EMC immunity level 5 EN/IEC 61000-4-9
EMC immunity EN/IEC 61000-4-29
EMC immunity EN/IEC 61000-4-11
EMC immunity EN/IEC 61000-4-17
EMC immunity IEC 60255-27
EMC immunity class III IEC 60255-5
EMC immunity EN/IEC 60255-1
Mechanical robustness
Vibrations class II) IEC 60255-21-1
VibrationsFc IEC 60068-2-6
Shocks class II) IEC 60255-21-2
ShocksEa IEC 60068-2-27
Seismic tests method A class II) IEC 60255-21-3
Environmental characteristic
Exposure to dry heat Bd EN/IEC 60068-2-2
Exposure to cold Ad EN/IEC 60068-2-1
Exposure to damp heat in service Db EN/IEC 60068-2-30
Exposure to damp heat in service Cab EN/IEC 60068-2-78
Ambient air temperature for operation | -40...149 °F (-40...65 °C) |
---|---|
Ambient Air Temperature for Storage | -40...158 °F (-40...70 °C) |
IP degree of protection | IP54 conforming to IEC 60529 |
Relative humidity | 0...95%, without condensation |
Operating altitude
6561.68 ft (2000 m)
Protective treatment
Conformal coating
Ordering and shipping details
Category | 11405-EASERGY P3 PROTECTIVE RELAYS |
---|---|
Discount Schedule | PL1S |
GTIN | 3606481465665 |
Returnability | No |
Country of origin | US |
Packing Units
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 13.00 In (33.02 cm) |
Package 1 Width | 13.00 In (33.02 cm) |
Package 1 Length | 16.50 In (41.91 cm) |
Package 1 Weight | 13.29 Lb(US) (6.03 kg) |
Product Life Status
Commercialised
Related Documents
![]() |
Schneider Electric Easergy P3U REL52052 Protection Relay Datasheet Technical data sheet for the Schneider Electric Easergy P3U REL52052 protection relay, detailing its characteristics, main features, protection types, control types, environmental specifications, and ordering information. |
![]() |
Easergy P3G30 and P3G32 Generator Protection User Manual | Schneider Electric Comprehensive user manual for Schneider Electric Easergy P3G30 and P3G32 generator protection relays, detailing machine differential protection, installation, configuration, and operational features. |
![]() |
Easergy P3 Quick Start Guide: Installation and Operation This guide provides essential information for the quick start, installation, and operation of Schneider Electric's Easergy P3 protection relays, including models P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, and P3G32. It covers safety precautions, product identification, wiring, energizing, front panel operations, and configuration. |
![]() |
Schneider Electric Sepam 49RMS Thermal Overload Protection for Transformers and Motors A comprehensive technical overview of the Schneider Electric Sepam 49RMS thermal overload protection function, detailing its application for transformers and motors, including operational principles, thermal models, parameter settings, and practical examples. |
![]() |
Schneider Electric Easergy P3M32 Protective Relay (REL52121) - Data Sheet Detailed data sheet for the Schneider Electric Easergy P3M32 protective relay, covering its main characteristics, protection functions, measurement capabilities, communication protocols, environmental specifications, and ordering information. Features include motor protection, IEC 61850, Modbus TCP, and RS485 communication. |
![]() |
Easergy MiCOM P64x Transformer Protection Relay Technical Manual This technical manual provides comprehensive instructions for the installation, commissioning, and operation of the Easergy MiCOM P64x series transformer protection relays, including models P642, P643, and P645. It covers safety information, technical data, settings, operation, application notes, and troubleshooting. |
![]() |
Easergy MiCOM P54x Current Differential Protection Relay Technical Manual Comprehensive technical manual for Schneider Electric's Easergy MiCOM P54x series of current differential protection relays, covering installation, operation, technical specifications, and safety information for models P543, P544, P545, and P546. |
![]() |
Easergy MiCOM P34x & P391 Generator Protection Relay Technical Manual Comprehensive technical manual for Schneider Electric's Easergy MiCOM P34x and P391 series generator protection relays. Covers installation, operation, technical data, safety information, and more. |