Samsung AM048NXMDCR/AA DVM S Eco Series Heat Recovery Condensing Unit Submittal

Samsung AM048NXMDCR/AA DVM S Eco Series Heat Recovery Condensing Unit Submittal

This document provides detailed specifications and dimensional information for the Samsung AM048NXMDCR/AA DVM S Eco Series Heat Recovery Condensing Unit, designed for efficient heating and cooling applications.

System Specifications

US Ton (nominal) 4
Capacity (Btu/h) Nominal Cooling1 48,000
Capacity (Btu/h) Nominal Heating1 54,000
System Modulation down to (Btu/h) 5,700
SEER Ducted/Non-Ducted 17.2 / 21.0
EER Ducted / Non-Ducted 10.2 / 11.5
HSPF Ducted / Non-Ducted 10.4 / 10.7
Voltage (Ø/V/Hz) 1 / 208-230 / 60
Maximum Circuit Breaker (MCCB/ELB/ELCB) 50
Minimum Circuit Ampacity (MCA) 29
Total Capacity (%) 50 - 130% Of Outdoor Capacity
Maximum Indoor Unit Quantity 8
Compressor Type Twin BLDC Rotary X 1
Compressor RLA 22.1
Refrigerant Type R410A
Factory Charge lbs. 7.1
Pipe Connections Liquid X Suction X HP Gas (braze) 3/8 X 3/4 X 5/8
Installation Limitation2 Max. Distance - ODU to IDU (feet) 492 (574 equivalent)
Installation Limitation2 Vertical Separation ODU to IDU3 (feet) 164 / 131
Installation Limitation2 Highest/Lowest IDU 49
Installation Limitation2 Total Refrigerant Pipe (feet) 984
Condenser Fan Type Propeller X 2
Condenser Fan Output (CFM) 3,885
Condenser Fan Motor Type BLDC
Condenser Fan Motor Output (W) / FLA (A) 125 X 2 / 0.6
Dimensions W X H X D Inches 37 X 47 5/8 X 13
Weight lbs. 213.8
Sound Level dB (A) Max. (cooling / heating) 51 / 53
Operating Temperature Range Cooling4 °F 0 - 118
Operating Temperature Range Heating °F -13 - 75

1 Certified in accordance with the AHRI Unitary Small Air-Source Heat Pumps (USHP) Certification Program which is based on the latest edition of AHRI Standard 210/240.

2 Other pipe restrictions and requirements exist. Please consult installation manuals or technical data book for full details.

3 Vertical separation: 131' when outdoor unit is lower than the indoor units, 164' when the outdoor unit is higher than the indoor units.

4 When cooling in outside temperatures between 0°F ~ 23°F, wind baffles are required. When outside temperature is between 0°F ~ 23°F, 50% operating capacity should be maintained to ensure reliability while in cooling mode.

Accessories

  • Wind Baffles: Front (WBF-1M2), Back (WBB-2M)
  • Wi-Fi Adapter (MIM-H03UN)
  • Base Pan Heater Kit (MHC-015EE)
  • External contact control interface module (operation and error output, night silent mode manual activation) (MIM-B14)

Safety Certifications & Protection Devices

Certifications: ETL (UL 1995)

Protection Devices: Intelligent logic to ensure proper operation within unit design limitations and operational parameters. Includes high pressure sensor, low pressure sensor, over-voltage protection, compressor over-current protection, current transformer, fan motor voltage protection, fan motor thermal protection, and high voltage fuses.

Compatibility

Only compatible with Samsung DVM S indoor units (AM****N***H***) that are equal to or less than 60,000 Btu/h and the MCM-D211UN Universal Communication Kit.

Construction

The unit shall be galvanized steel with a baked on powder coated finish.

Heat Exchanger

The heat exchanger shall be mechanically bonded fin to copper tube. The aluminum fins of the heat exchanger shall have a protective coating. Salt spray test method: ASTM-B117-18 - the heat exchanger showed no unusual rust or corrosion development to 2,280 hours.

Controls

The unit shall be operated via NASA Protocol with controls provided by Samsung. The outdoor unit shall have a removable EEPROM that stores unit serial number, startup information, system settings, system tag/name, and other information. Controls shall integrate with Samsung central controllers without additional interface modules. Control wiring shall be 16 AWG X 2 shielded wire.

Refrigerant System

The compressor shall be Samsung hermetically sealed, inverter driven, twin BLDC Rotary type. The condenser shall be able to provide simultaneous heating and cooling operation. Refrigerant flow shall be controlled by EEV (electronic expansion valve) throughout the system. A flat plate subcooler device will improve capacity at extreme system refrigerant pipe lengths and reduce refrigerant noise. Installation of an HR Changer (MCU-R4NEK0N) is mandatory. If additional Mode Control Unit(s) are needed, the HR Changer must be installed between the outdoor unit and addtional MCU's. Please refer to the installation manual for compatible MCU models. Indoor units that will be used for cooling only year-round may be piped direct to the liquid and suction pipes after the HR Changer and bypassing MCU connection.

Other Features

  • Advanced oil recovery cycle logic to ensure adequate oil level is maintained in the compressor. Oil recovery operation shall not interrupt heating or cooling operation.
  • Optional night quiet modes to reduce outdoor unit sound (4 levels) with automatic activation or manual activation (with MIM-B14).
  • Optional snow blowing logic to prevent snow accumulation on idle outdoor units.
  • Maximum current control of outdoor unit(s) to limit current (50% - 100% of design current) adjustable at outdoor unit or central control devices: DMS 2 (MIM-D00AN), DMS 2.5 (MIM-D01AUN), BACnet Gateway (MIM-B17N, MIM-B17BUN), LON Gateway (MIM-B18N, MIM-B18BUN).
  • Energy savings options to reduce system energy consumption in heating mode when average indoor room temperatures are greater than average indoor set temperatures.

Dimensional Drawing Description

The document includes dimensional drawings illustrating the unit's physical layout and connection points. The dimensions are provided in inches.

Overall Unit Dimensions:

  • Top: 37 inches
  • Depth (Top to Bottom): 12 5/16 inches
  • Height: 47 5/8 inches
  • Width (Front View): 24 3/8 inches
  • Side View Depth: 15 1/8 inches
  • Side View Height: 47 5/8 inches
  • Rear View Depth: 17 5/8 inches
  • Front View Depth (without cover): 20 11/16 inches

Connection Points and Features:

NO Name Description
1 Refrigerant liquid pipe 3/8"
2 Refrigerant gas pipe 3/4"
3 Knockout hole for pipe intake Front / Side / Rear / Bottom
4 Power wiring conduits Front / Side / Rear, 1 3/8"
5 Communication wiring conduits Front / Side / Rear, 7/8"
6 Drain holes Connect with the provided drain plug

PDF preview unavailable. Download the PDF instead.

AM048NXMDCR AA Submittal DVM S Eco HR 04022019

Related Documents

Preview Samsung DVM S Eco: Compact and Efficient HVAC Solutions
Explore the Samsung DVM S Eco, a compact and efficient HVAC system offering high performance heating and cooling for light commercial and residential applications. Learn about its versatile indoor unit compatibility, cost-saving features, and advanced control options.
Preview Samsung Commercial Air Conditioning Product Line-Up 2018
A comprehensive overview of Samsung's commercial air conditioning product line for 2018, featuring VRF systems, chillers, and indoor units, with detailed specifications and performance data.
Preview Samsung HVAC E210 Error Code Troubleshooting Guide
Comprehensive troubleshooting steps for Samsung DVM Heat Recovery and ECO Heat Recovery systems experiencing E210 MCU Communication Error. Includes wiring checks, setup procedures, and PCB replacement guidance.
Preview Samsung AJ024TXJ3CH/AA FJM Series 3 Port Condensing Unit Submittal
Submittal data sheet for the Samsung AJ024TXJ3CH/AA FJM Series 3 Port Condensing Unit, detailing performance, specifications, dimensions, and wiring.
Preview Samsung VMDD007S6-5P VRF Medium Static Ducted Indoor Unit Submittal Data
Technical specifications and features for the Samsung VMDD007S6-5P VRF Medium Static Ducted Indoor Unit, including performance data, dimensions, and accessories.
Preview Samsung AC009BNJDCH/AA Console Split System: Technical Specifications and Overview
Detailed submittal document for the Samsung AC009BNJDCH/AA (CNH09JDB) and AC009BXADCH/AA (CXH09ADB) single-zone console split system air conditioner, including performance, dimensions, and operational specifications.
Preview Samsung WindFree 4-Way Cassette AC048BN4DCH/AA Split System Submittal
Submittal document for the Samsung WindFree 4-Way Cassette, Single Zone, Split System, model AC048BN4DCH/AA (CNH484DB) and AC048BXADCH/AA (CXH48ADB). Includes specifications, dimensions, general information, and optional accessories.
Preview Samsung DVM CHILLER E448 Error Code: Fan Motor Troubleshooting Guide
Troubleshooting steps for Samsung DVM CHILLER units experiencing an E448 error code, indicating a locked fan motor. Covers procedures for condensers with one or two fans, including wiring checks and resistance measurements.