Samsung AM048NXMDCR/AA DVM S Eco Series Heat Recovery Condensing Unit Submittal
This document provides detailed specifications and dimensional information for the Samsung AM048NXMDCR/AA DVM S Eco Series Heat Recovery Condensing Unit, designed for efficient heating and cooling applications.
System Specifications
US Ton (nominal) | 4 |
Capacity (Btu/h) Nominal Cooling1 | 48,000 |
Capacity (Btu/h) Nominal Heating1 | 54,000 |
System Modulation down to (Btu/h) | 5,700 |
SEER Ducted/Non-Ducted | 17.2 / 21.0 |
EER Ducted / Non-Ducted | 10.2 / 11.5 |
HSPF Ducted / Non-Ducted | 10.4 / 10.7 |
Voltage (Ø/V/Hz) | 1 / 208-230 / 60 |
Maximum Circuit Breaker (MCCB/ELB/ELCB) | 50 |
Minimum Circuit Ampacity (MCA) | 29 |
Total Capacity (%) | 50 - 130% Of Outdoor Capacity |
Maximum Indoor Unit Quantity | 8 |
Compressor Type | Twin BLDC Rotary X 1 |
Compressor RLA | 22.1 |
Refrigerant Type | R410A |
Factory Charge lbs. | 7.1 |
Pipe Connections Liquid X Suction X HP Gas (braze) | 3/8 X 3/4 X 5/8 |
Installation Limitation2 Max. Distance - ODU to IDU (feet) | 492 (574 equivalent) |
Installation Limitation2 Vertical Separation ODU to IDU3 (feet) | 164 / 131 |
Installation Limitation2 Highest/Lowest IDU | 49 |
Installation Limitation2 Total Refrigerant Pipe (feet) | 984 |
Condenser Fan Type | Propeller X 2 |
Condenser Fan Output (CFM) | 3,885 |
Condenser Fan Motor Type | BLDC |
Condenser Fan Motor Output (W) / FLA (A) | 125 X 2 / 0.6 |
Dimensions W X H X D Inches | 37 X 47 5/8 X 13 |
Weight lbs. | 213.8 |
Sound Level dB (A) Max. (cooling / heating) | 51 / 53 |
Operating Temperature Range Cooling4 °F | 0 - 118 |
Operating Temperature Range Heating °F | -13 - 75 |
1 Certified in accordance with the AHRI Unitary Small Air-Source Heat Pumps (USHP) Certification Program which is based on the latest edition of AHRI Standard 210/240.
2 Other pipe restrictions and requirements exist. Please consult installation manuals or technical data book for full details.
3 Vertical separation: 131' when outdoor unit is lower than the indoor units, 164' when the outdoor unit is higher than the indoor units.
4 When cooling in outside temperatures between 0°F ~ 23°F, wind baffles are required. When outside temperature is between 0°F ~ 23°F, 50% operating capacity should be maintained to ensure reliability while in cooling mode.
Accessories
- Wind Baffles: Front (WBF-1M2), Back (WBB-2M)
- Wi-Fi Adapter (MIM-H03UN)
- Base Pan Heater Kit (MHC-015EE)
- External contact control interface module (operation and error output, night silent mode manual activation) (MIM-B14)
Safety Certifications & Protection Devices
Certifications: ETL (UL 1995)
Protection Devices: Intelligent logic to ensure proper operation within unit design limitations and operational parameters. Includes high pressure sensor, low pressure sensor, over-voltage protection, compressor over-current protection, current transformer, fan motor voltage protection, fan motor thermal protection, and high voltage fuses.
Compatibility
Only compatible with Samsung DVM S indoor units (AM****N***H***) that are equal to or less than 60,000 Btu/h and the MCM-D211UN Universal Communication Kit.
Construction
The unit shall be galvanized steel with a baked on powder coated finish.
Heat Exchanger
The heat exchanger shall be mechanically bonded fin to copper tube. The aluminum fins of the heat exchanger shall have a protective coating. Salt spray test method: ASTM-B117-18 - the heat exchanger showed no unusual rust or corrosion development to 2,280 hours.
Controls
The unit shall be operated via NASA Protocol with controls provided by Samsung. The outdoor unit shall have a removable EEPROM that stores unit serial number, startup information, system settings, system tag/name, and other information. Controls shall integrate with Samsung central controllers without additional interface modules. Control wiring shall be 16 AWG X 2 shielded wire.
Refrigerant System
The compressor shall be Samsung hermetically sealed, inverter driven, twin BLDC Rotary type. The condenser shall be able to provide simultaneous heating and cooling operation. Refrigerant flow shall be controlled by EEV (electronic expansion valve) throughout the system. A flat plate subcooler device will improve capacity at extreme system refrigerant pipe lengths and reduce refrigerant noise. Installation of an HR Changer (MCU-R4NEK0N) is mandatory. If additional Mode Control Unit(s) are needed, the HR Changer must be installed between the outdoor unit and addtional MCU's. Please refer to the installation manual for compatible MCU models. Indoor units that will be used for cooling only year-round may be piped direct to the liquid and suction pipes after the HR Changer and bypassing MCU connection.
Other Features
- Advanced oil recovery cycle logic to ensure adequate oil level is maintained in the compressor. Oil recovery operation shall not interrupt heating or cooling operation.
- Optional night quiet modes to reduce outdoor unit sound (4 levels) with automatic activation or manual activation (with MIM-B14).
- Optional snow blowing logic to prevent snow accumulation on idle outdoor units.
- Maximum current control of outdoor unit(s) to limit current (50% - 100% of design current) adjustable at outdoor unit or central control devices: DMS 2 (MIM-D00AN), DMS 2.5 (MIM-D01AUN), BACnet Gateway (MIM-B17N, MIM-B17BUN), LON Gateway (MIM-B18N, MIM-B18BUN).
- Energy savings options to reduce system energy consumption in heating mode when average indoor room temperatures are greater than average indoor set temperatures.
Dimensional Drawing Description
The document includes dimensional drawings illustrating the unit's physical layout and connection points. The dimensions are provided in inches.
Overall Unit Dimensions:
- Top: 37 inches
- Depth (Top to Bottom): 12 5/16 inches
- Height: 47 5/8 inches
- Width (Front View): 24 3/8 inches
- Side View Depth: 15 1/8 inches
- Side View Height: 47 5/8 inches
- Rear View Depth: 17 5/8 inches
- Front View Depth (without cover): 20 11/16 inches
Connection Points and Features:
NO | Name | Description |
---|---|---|
1 | Refrigerant liquid pipe | 3/8" |
2 | Refrigerant gas pipe | 3/4" |
3 | Knockout hole for pipe intake | Front / Side / Rear / Bottom |
4 | Power wiring conduits | Front / Side / Rear, 1 3/8" |
5 | Communication wiring conduits | Front / Side / Rear, 7/8" |
6 | Drain holes | Connect with the provided drain plug |