Samsung WindFree™ 4-Way Cassette, Single Zone, Split System
Specifications
| Job Name | Location | ||||
| Purchaser | Engineer | ||||
| Submitted to | Reference | Approval | Construction | Schedule # | |
| Unit Designation | |||||
| Indoor Unit Model Number (US Code) | AC048BN4DCH/AA (CNH484DB) | ||||
| Outdoor Unit Model Number (US Code) | AC048BXADCH/AA (CXH48ADB) | ||||
| Nominal Capacity¹ Cooling / Heating (Btu/h) | 48,000/54,000 | ||||
| Cooling (Btu/h) | 12,000- 52,000 | ||||
| Capacity Range | Heating (Btu/h) | ||||
| SEER/EER | 17.2/8.3 | ||||
| COP (nominal heating) | 3.10 | ||||
| HSPF | 10.0 | ||||
| AHRI Certification Number | 207465436 | ||||
| Voltage | Ø/V/Hz | 1/208-230/60 | |||
| Working Voltage Range (VAC) | 176-254 (max. 3% deviation from each) | ||||
| Operating Current Cooling (A) | (min./std./max.) | 5.0/25.6/28.8 | |||
| Heating (A) | 3.7/22.7/32.0 | ||||
| Max. Breaker Amps | 40 | ||||
| Min. Circuit Ampacity (A) | 29.5 | ||||
| Dimensions | WXHXD (in.) | Indoor Unit: 33 1/16 X 11 3/8 X 33 1/16 Outdoor Unit: 37 X 47 11/16 X 13 |
|||
| Weight (lbs.) | Indoor Unit: 45.6 Outdoor Unit: 191.8 |
||||
| Sound Pressure Level | Indoor Unit dB(A) L/M/H | 35/40/45 | |||
| Outdoor Unit dB(A) Cooling / Heating (high) | 56/58 | ||||
| Operating Temperatures | Indoor | 23~122°F (-5~50°C) | |||
| Outdoor Cooling | 0~122°F (-18~50°C) W/Baffle | ||||
| Outdoor Heating | -4~75°F (-20~24°C) | ||||
| Indoor & Outdoor | T≤ 80°F (27°C) | 61~90°F (16~32°C) | |||
| Pipe Connections | Maximum (ft.) | 246 | |||
| Maximum Vertical Separation (ft.) | 98.4 | ||||
| High side (flare) | 3/8" | ||||
| Low side (flare) | 5/8" | ||||
| Condensate Connection | Type | 1 1/4" OD, 1" ID | |||
| Refrigerant | Type | R410A | |||
| Factory Charge lbs. | 7.50 | ||||
| Charged for Additional Refrigerant | 25 ft | 0.11 oz./ft. over 24.6 ft | |||
| Manufacturer | Samsung | ||||
| Compressor Type | Inverter Driven, Twin BLDC Rotary | ||||
| RLA Amps | 20.9 | ||||
| Type | BLDC (1) With Turbo Type Fan (1) | ||||
| Evaporator Air Volume | CFM (L/M/H) | 749/996/1289 | |||
| Fan Output Watts | 97 X 1 | ||||
| Condenser Motor Fan | FLA/Watts / CFM (max.) | BLDC With Axial Type Fan (2) 1.25 A/125 W/ 3,532 CFM |
|||
| Fascia Panel | LXWXH (in.) | 37 3/8 X 37 3/8 X 2 1/2 | |||
| Safety Certifications | Weight (lbs.) | 13.9 | |||
| Devices | ETL (UL 1995) PCB fuses, indoor unit terminal block thermal fuse, current transformer, over-voltage protection, crankcase heating, temperature limit protection logic, compressor overload sensing |
||||
¹Certified in accordance with the AHRI Unitary Small Air-Source Heat Pumps (USHP) Certification Program which is based on the latest edition of AHRI Standard 210/240.
* The WindFree™ unit delivers an air current that is under 0.15 m/s while in WindFree™ mode. Air velocity that is below 0.15 m/s is considered "still air" as defined by ASHRAE (American Society of Heating, Refrigerating, and Air-Conditioning Engineers).
Samsung HVAC maintains a policy of ongoing development, specifications are subject to change without notice.
General Information
- The indoor unit shall feature WindFree™ mode. In cooling mode, as room temperature nears set temperature, the unit will close its louver and will disperse air into the space through thousands of micro-holes on the front of the indoor unit preventing cold air drafts on occupants.
- The outdoor unit shall supply power to indoor unit via 14 AWG X 3 power wire.
- High-voltage terminal block temperature sensor to disable unit in the event of power connection overheating.
- Auto-restart after power loss.
- Soft-start compressor minimizing current inrush.
- All heat exchangers shall be mechanically bonded aluminum fin to copper tube.
- The condensing unit heat exchanger salt spray test method: ISO-9227- The heat exchanger showed no unusual rust or corrosion development to 3,000 hours.
- Integral condensate pump with maximum 29" lift from bottom of the unit with check valve and float switch to disable unit in the event of condensate overflow.
- Knock-out for outside air capability (with booster fan connection).
Option Settings
- The outdoor unit shall have snow accumulation prevention option setting to prevent snow drifting against an idle outdoor unit.
- Night-time Quiet Mode: reduction of operational sound during (automatic or manual activation).
- Emergency Temperature Output (ETO) function: when indoor unit is in error status or when room temperature exceeds configurable temperature level, the system outputs a signal to an external source, e.g., backup system, building management system, alert device (ex: status light, warning lamp, buzzer).
- System can be configured as heating/cooling, cooling only, or heating only via outdoor unit option setting.
- Maximum Current Control configurable from 50% - 100% via outdoor unit, wired controller or central controls.
Indoor Fan
- Indoor fan is a single turbo type.
- Three fan speed settings and auto setting.
- Washable filter as standard.
- Fascia panel shall have LED display, infrared receiver, and motorized louver(s).
- The WindFree™ function will close the supply air outlet louver while in cooling mode to gently disperse cool air into the space without blowing directly onto occupants. The WindFree™ feature is optional and can be enabled using central or local control options.
- The WindFree™ indoor unit has an integral humidity sensor that will open the louver for standard cool mode when space conditions could potentially cause condensation formation on the chassis surface.
Construction
- Outdoor unit: Galvanized steel with a baked-on powder coated finish for durability.
- Indoor unit: Insulated, HIPS chassis and fascia panel certified to UL94 V0.
Controls
- Control wiring shall be 2 X 16 AWG.
- Wired controllers must be purchased separately.
- Dual set temperature support when connected to MWR-WG00UN Advanced Wired Controller or central control options.
- No additional interface modules/adapters are required when connecting to Samsung central control options.
- The unit shall be operated via a wireless or wired remote control with DDC type signal.
Refrigerant System
- The compressor shall be hermetically sealed, inverter-controlled BLDC rotary type.
- Refrigerant flow shall be controlled by an electronic expansion valve at outdoor unit.
Warranty
10 years compressor, 10 years parts, 1-year limited labor (conditions apply).
Required Accessories
| Fascia panel | WindFree™ Type | |
| PC4NUFMUN |
Optional Accessories
| Wired controller | Advanced Touchscreen | MWR-WG00UN MWR-SH11UN |
| Thermostat adapter (24vac) | MIM-A60UN | |
| Wireless controller | AR-EH04U | |
| Wi-Fi adapter | Single indoor unit | MIM-H14UN |
| 1-16 indoor units | MIM-H05UN | |
| External temperature sensor | MRW-TA | |
| External contact control | MIM-B14 | |
| Wall bracket (for outdoor unit) | CKN-250 | |
| Wind baffle | Front | WBF-1M2 |
| HGK-4 | ||
| Hail guard kit (includes back and side guards) | 25'ILS2510 50'ILS5010 |
|
| Line sets - insulated and flared, interconnect cables included |
Dimensional Drawing - Indoor Unit
Ceiling Opening: 35 1/16" - 35 13/16"
Suspension Position: 28 15/16"
Dimensions (approximate):
- Width: 33 1/16"
- Height: 11 3/8"
- Depth: 33 1/16"
Connections:
| No. | Name | Description |
| ① | Liquid Pipe Connection | Ø 3/8" Flare |
| ② | Gas Pipe Connection | Ø 5/8" Flare |
| ③ | Drain Pipe Connection | OD 1 1/4", ID 1" |
| ④ | Conduit for Power & Communication Wiring | |
| ⑤ | Air Inlet Grille | |
| ⑥ | Air Outlet Louver | Ø 4" |
| ⑦ | Fresh Air Inlet |
Proper clearance must be maintained around unit for proper operation.
Dimensional Drawing - Outdoor Unit
Dimensions (approximate):
- Width: 37"
- Height: 47 11/16"
- Depth: 13"
Connections:
| No. | Name | Description |
| 1 | Refrigerant liquid pipe | Ф 3/8 |
| 2 | Refrigerant gas pipe | Ф 5/8 |
| 3 | Drain hole | |
| 4 | Power and communication conduit openings | Connect with provided drain plug |
Related Documents
![]() |
Samsung WindFree™ Low Ambient 4-Way Cassette Split System AC Submittal & Specifications Comprehensive submittal document for Samsung's WindFree™ Low Ambient 4-Way Cassette Single Zone Split System air conditioners, models AC024BN4DCH/AA and AC024BXSCCC/AA. Includes detailed specifications, performance data, dimensions, optional accessories, and installation notes. |
![]() |
Samsung FJM Series WindFree 1-Way Cassette AC012BN1DCH/AA Submittal Specifications Submittal document detailing specifications, features, dimensions, and compatibility for the Samsung FJM Series WindFree 1-Way Cassette air conditioner, model AC012BN1DCH/AA (CNH121DB). |
![]() |
Samsung WindFree™ Low Ambient 4-Way Cassette Split System - AC018BN4DCH/AA, AC018BXSCCC/AA Submittal Technical submittal document for the Samsung WindFree™ Low Ambient 4-Way Cassette split system air conditioner, including specifications, features, accessories, and dimensional drawings for models AC018BN4DCH/AA and AC018BXSCCC/AA. |
![]() |
Samsung Multi Split WindFree™ Family Air Conditioners: Features, Specifications, and Compatibility Explore the Samsung Multi Split WindFree™ Family of air conditioners, featuring advanced cooling technology, energy efficiency, and smart controls. Find detailed specifications, compatibility guides, and model information for wall-mounted and cassette units. |
![]() |
Samsung FJM Series WindFree™ 1-Way Cassette AC009BN1DCH/AA Submittal and Specifications Submittal document detailing the technical specifications, features, dimensions, and compatibility of the Samsung FJM Series WindFree™ 1-Way Cassette indoor unit (Model AC009BN1DCH/AA, CNH091DB). |
![]() |
Samsung Climate Solutions Price List 2022 - HVAC Systems Catalog Official 2022 price list for Samsung Climate Solutions air conditioners and HVAC systems, covering residential, commercial split, VRF, chillers, and heat pumps with detailed product information and pricing. |
![]() |
Samsung AR15CSKCPWKNCV WindFree 3.0i Multi-Zone System Submittal Data Submittal document for the Samsung AR15CSKCPWKNCV (RNS15CPC) WindFree 3.0i wall-mounted multi-zone system, detailing specifications, features, construction, controls, and dimensions. |
![]() |