Samsung VMDD007S6-5P VRF Medium Static Ducted Indoor Unit

Submittal Data

General Information

Compatible with R-32 VRF air, water, and mini systems.

Features an integral condensate pump with a maximum 29" lift from the bottom of the unit, including a check valve and float switch to disable the indoor unit in case of condensate overflow.

Includes a built-in Wi-Fi adapter as standard for control and monitoring via the Samsung SmartThings app.

Construction

Constructed with insulated, galvanized steel.

Refrigerant System

Heat exchanger features a mechanically bonded aluminum fin to copper tube design.

Refrigerant flow is controlled by an electronic expansion valve within the indoor unit.

Includes an R32 alarm output plug for simple notification or interlock of third-party equipment upon R32 leak detection (requires VSTAT10P-1 accessory).

Indoor Fan

Equipped with smart pressure control that adjusts fan speed based on ESP for consistent heating and cooling power.

Features a smart-tuning function for optimized comfort, allowing users to adjust the fan CFM curve for airflow customization.

Includes automatic air volume scanning for simplified setup and optimized occupant comfort settings.

Controls

Control wiring uses 2 x 16 AWG wire.

Operation is managed via a wired remote controller (model VSTAT04P-1, purchased separately).

Supports dual set temperature when connected to supported controllers.

Wired or wireless controllers must be purchased separately.

External Heat Control

External heat control functionality allows configuration of fan operation during auxiliary heat, defrost, and emergency heat modes (requires VSTAT10P-1 accessory).

Configuration settings include: outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (requires VSTAT10P-1 accessory).

Emergency heat functionality enables continued control of the external heat source even when system errors prevent the heat pump from operating (requires VSTAT10P-1 accessory).

Convenience

Features an Emergency Temperature Output (ETO) function. When the indoor unit is in an error status or the room temperature exceeds a configurable level, the system outputs a signal to an external source (e.g., backup system, building management system, alert device like a status light, warning lamp, or buzzer).

Certifications

Certified by Intertek (ETL Listed) and AHRI (AHRI Standard 210/240 for Unitary Small HP). Certification applies only when the complete system is listed with AHRI.

Specifications

AttributeValue
Indoor Unit Model NumberVMDD007S6-5P
Nominal Capacity (Cooling)7,500 Btu/h
Nominal Capacity (Heating)8,500 Btu/h
Voltage1Ø/208-230/60 Hz
Operating Current (max.) (Cooling)0.30 A
Operating Current (max.) (Heating)0.30 A
MCA0.91 A
MOP15 A
Power TypeBLDC (1) With Sirocco Fan (2)
Consumption153 Watts
Evaporator Fan External Static Pressure (Standard)0.04 "WC
Evaporator Fan External Static Pressure (Min. / Max.)0 / 0.59 "WC
Airflow (Cooling)247 / 283 / 318 CFM
Airflow (Heating)247 / 283 / 318 CFM
Refrigerant TypeR-32
Refrigerant Leak DetectionIntegral (A2L)
Pipe Connections (Refrigerant)High side: 1/4 in., Low side: 1/2 in.
Condensate Pipe Connection1 1/4 in. OD, 1 in. ID
Dimensions (W x H x D)33 7/16 in. x 9 13/16 in. x 27 9/16 in.
Weight59.50 lbs.
Duct Connections (Supply)32 3/16 in. x 8 11/16 in.
Duct Connections (Return)32 3/16 in. x 8 11/16 in.
Sound Pressure Level (Low / Med. / High)23 / 25 / 27 dB(A)
Safety CertificationsUL 60335-2-40

Accessories

AccessoryModel Number
Filter boxV1FBX01-4P
Wired controller (Advanced)VSTAT04P-1
Wired controller (Touchscreen)VSTAT02P-1
Thermostat adapter (for connection to standard 24VAC thermostats)VSTAT09P-1
Wireless signal receiverVCTRL10P-1
Wireless signal controlVSTAT01P-1
Wireless controllerVCTRL11P-1
External temperature sensorVSTAT10P-1
External contact control interface moduleJV DB39-01263A CN83 Pigtail
CN83 Pigtail (for 12VDC VENT output)CN83 Pigtail

Dimensional Drawing

The unit is a rectangular prism designed for ducted installation. The drawing provides key dimensions and connection points. All dimensions are in inches.

Key Components and Connections:

The drawing illustrates the unit's overall dimensions, including width, height, and depth, as well as the placement of air inlets and outlets, and mounting points. Specific dimensions shown include:

PDF preview unavailable. Download the PDF instead.

sbmtl VMDD007S6-5P 2508 Adobe InDesign 20.4 (Windows) Adobe PDF Library 17.0

Related Documents

Preview Samsung Max Heat 2.0 AR24TSFABWKNCV/AR24TSFACWKXCV Submittal Data Sheet
Technical submittal data sheet for the Samsung Max Heat 2.0 wall-mounted evaporator split system, including specifications, dimensions, and optional accessories for models AR24TSFABWKNCV and AR24TSFACWKXCV.
Preview Samsung AM048NXMDCR/AA DVM S Eco Series Heat Recovery Condensing Unit Submittal
Technical specifications and dimensional data for the Samsung AM048NXMDCR/AA DVM S Eco Series Heat Recovery Condensing Unit, detailing performance, compatibility, and installation requirements.
Preview Samsung Commercial Air Conditioning Product Line-Up 2018
A comprehensive overview of Samsung's commercial air conditioning product line for 2018, featuring VRF systems, chillers, and indoor units, with detailed specifications and performance data.
Preview Samsung EHS Mono R290 Heat Pump Technical Data Book
Comprehensive technical specifications, features, benefits, and installation guidelines for the Samsung EHS Mono R290 air-to-water heat pump and integrated hydro units. Covers outdoor units, hydro units, and control kits, detailing performance data, electrical characteristics, dimensions, sound levels, operation ranges, and installation requirements.
Preview Samsung AJ024TXJ3CH/AA FJM Series 3 Port Condensing Unit Submittal
Submittal data sheet for the Samsung AJ024TXJ3CH/AA FJM Series 3 Port Condensing Unit, detailing performance, specifications, dimensions, and wiring.
Preview Samsung Air Conditioner Installation Manual
This manual provides detailed instructions for the installation of Samsung air conditioners, covering safety precautions, step-by-step installation procedures, and troubleshooting.
Preview Samsung Air Conditioner Installation Manual
Comprehensive installation manual for Samsung air conditioners, covering safety information, installation procedures, and outdoor unit placement. Includes detailed steps for preparing materials, installing the outdoor unit, and ensuring proper operation.
Preview Samsung EHS Mono R290 Heat Pump System Specifications
Detailed technical specifications for the Samsung EHS Mono R290 heat pump system, including performance, efficiency, and system configurations with ClimateHub and Control Kit options.