ifm Vibration Sensor with IO-Link Interface

Device manual

1 Preliminary note

Technical data, approvals, accessories and further information at www.ifm.com.

1.1 Explanation of symbols

2 Safety instructions

4 Installation

Screw the threaded adapter 1/4"-28 UNF / M8 (2) or the threaded adapter 1/4"-28 UNF (3) into the unit (1). Threaded adapters are supplied.

Tighten using a 3 mm Allen key. Tightening torque 8 Nm.

Drill and tap a hole at the mounting location:

The measuring direction should be in the direction of the main vibration. The main vibration is usually in radial direction to the shaft.

In case of fixed bearings with high axial force absorption or axial bearings, the recommended measuring direction is axial to the shaft.

Radial mounting

Axial mounting

Mount only in a thick housing wall and vertically to the machine surface close to the bearing or at the end shield.

Adapters of any kind have an impact on the vibration measurement. The mass, shape and stiffness of the adapter have an influence on the frequency response of the entire system. Both resonances and damping effects may occur in different frequency ranges.

For all installation types, tighten the sensor with the tightening torque indicated in the data sheet.

4.1 Prepare contact surface

Prepare a clean and smooth contact surface that is free from any coating to fix the sensor. The prepared contact surface must be a little larger than the sensor or the mounting adapter.

4.2 Types of mounting

The following table indicates the transferable measuring range of 3 different types of mounting:

Type of mounting Frequency range
Screw Up to approx. 15 kHz
Direct gluing Up to approx. 8 kHz
Magnet Up to approx. 3 kHz

4.2.1 Screw

For the permanent installation of sensors, a screw connection is the ideal and recommended method.

4.2.2 Glue

Gluing is suitable for temporary measurements or if the surface is not suitable for a screw connection.

In general, methyl-cyanoacrylate adhesives (e.g. Loctite 454) or epoxy adhesives (e.g. Loctite EA 3450) are used.

When choosing a suitable adhesive always take the materials and the environmental conditions (e.g. temperature range) into account.

4.2.3 Magnet

Using magnets is only recommended for temporary measurements and is only suitable for magnetic surfaces.

Careless fixing can result in very high g-forces which may damage the sensor.

5 Electrical connection

The unit must be connected by a qualified electrician. The national and international regulations for the installation of electrical equipment must be adhered to.

M12 Connector Pinout:

6 Function

6.1 IO-Link

This unit has an IO-Link communication interface which enables direct access to process and diagnostic data. In addition, it is possible to set the parameters of the unit while it is in operation. Operation of the unit via the IO-Link interface requires an IO-Link master.

With a PC, suitable IO-Link software and an IO-Link adapter cable, communication is possible while the system is not in operation.

The IODDs necessary for the configuration of the unit, detailed information about the two IO-Link interface descriptions (status A / status B), process data structure, diagnostic information, parameter addresses and the necessary information about the required IO-Link hardware and software can be found at www.ifm.com.

The IO-Link interface provides additional functions using suitable hardware and software. Different functions are available depending on the software status used.

VV units with status A provide the following additional functions:

VV units with status B provide the following additional functions:

6.2 Switching function

The switching output OUx changes its switching status if the value is below or above the set switching limits. Hysteresis or window function can be selected.

Adjustable switching limits of VV units with status A

Adjustable switching limits of VV units with status B

Hysteresis function

SP = set point, rP = reset point, HY = hysteresis, Hno = hysteresis NO (normally open), Hnc = hysteresis NC (normally closed)

Window function

FH = upper limit, FL = lower limit, FE = window, Fno = window NO (normally open), Fnc = window NC (normally closed)

For both switching outputs, a switch-on and switch-off delay can be set.

For VV units with status B, the two switching outputs (OU1 or OU2) can optionally be set to inactive.

6.3 Process data description

6.3.1 v-RMS

The v-RMS (effective value of the vibration velocity) measures the total load of a rotating machine. The most frequent types of overload (unbalance, alignment errors, etc.) are reflected in the v-RMS. An increased load can damage the machine in the long term (fatigue, fatigue strength) or, in extreme cases, destroy it within a short time.

6.3.2 a-RMS

The a-RMS (effective value of the acceleration) detects mechanical contact of machine components. This contact typically occurs in case of wear (faulty bearing, worn out toothed wheels, etc.) or problems with lubricants (contaminated grease, water in oil, etc.).

6.3.3 a-Peak

The a-Peak monitors the maximum value of the acceleration. Shocks in the acceleration can occur once or periodically, as in a crash, for example in the event of bearing damage. a-Peak is a measure for the forces occurring on the machine.

6.3.4 Crest factor

The crest factor is a described characteristic value of the signal analysis. It is defined as the ratio of the maximum value to the effective value (peak/RMS). In condition monitoring the characteristic value is used for the evaluation of the bearing condition. The high-frequency signals with a short pulse duration of a bearing damage generate higher peak values in relation to the effective value. This relation can be read from the crest factor.

6.4 Event counter, event history and operating hours counter

VV units with status B offer:

The event history and the event counter can be reset via system commands.

6.5 Machine monitoring

VV units with status B record the machine's uptime and switch-on operations via the process value v-RMS.

The threshold value for the operating time (mrcT) must be set. If the set threshold value is exceeded, the operating time counter (mrc) is incremented by 1 and the operating time (mot) is increased by the exceeded time (in seconds).

6.6 Marking

7 Parameter setting

The parameters can be set before installation and set-up of the unit or during operation via the IO-Link interface.

If you change parameters during operation, this will influence the function of the plant. Ensure that there will be no malfunctions in your plant.

During parameter setting the unit remains in the operating mode. It continues to monitor with the existing parameter until the parameter setting has been completed.

The following screenshot is from the ifm parameter setting software moneo Configure:

ifm moneo Configure

Connected: E30390 (USB) / Port 1 / VVB001 Status B

Parameter Value Current device value Minimum Maximum Description
Identification
Product name VVB001 Status B
Family VV
Vendor ifm electronic gmbh
Vendor ID 0x136 | 310 d | Bytes 1d 54d
Device ID 0x557 | 1367 d | Bytes 5d 87d
Serial number 000010230237
Hardware/firmware revision BA/V1.25
Description IO-Link vibration sensor, -50...50 g
Source
Parameter
Identification
Application Specific Tag 0 0 32 Application Specific Tag
Function Tag 11/3/2020 0 32 Possibility to mark a device with function-specific information.
Location Tag 11:24:10 AM 0 32 Possibility to mark a device with location-specific information.

Import parameter set Visit device page

WRITE TO DEVICE SAVE PARAMETER SET DISCARD EXIT

7.1 Parameters

The following IO-Link parameters merely provide an overview of software status B. A complete list can be found in the IODD of the unit. The parameters of software status A differ from status B.

Parameter Description Setting range
Identification
Application specific tag Free text fields, maximum 32 characters per field
Function tag
Location tag
Date of installation Installation date of the unit in the plant. This parameter is not restored after a device replacement. Enter a new installation date after replacing the unit. Setting range: yyyy-mm-dd
Parameter
Output configuration Switching characteristics hysteresis / window function Hno / Hnc / Fno / Fnc / OFF
ou1
ou2
SEL1 Process value that is evaluated at the switching output v-RMS / a-Peak / a-RMS / temperature / crest
SEL2
P-n Output function PNP / NPN
Digital output 1/2 Switch-on delay dS1/2 0...50 s
Switch-off delay dr1/2 0...50 s
Temperature Temperature Set the set point SP1/2
Set the reset point rP1/2
-28...80 °C
-30...78 °C
v-RMS (Component) fatigue Set the set point SP1/2
Set the reset point rP1/2
0.0002... 0.0450 m/s
0.0000... 0.0448 m/s
a-Peak Impact Set the set point SP1/2
Set the reset point rP1/2
2.0...490.3 m/s²
0.0...488.3 m/s²
a-RMS Friction Set the set point SP1/2
Set the reset point rP1/2
2.0...490.3 m/s²
0.0...488.3 m/s²
Crest Set the set point SP1/2
Set the reset point rP1
20...500
10...490
Memory Temperature Saves and displays the minimum (Lo.T) and maximum (Hi.T) temperature value -30.0...80.0 °C
v-RMS Saves and displays the maximum value 0.0000...0.0495 m/s
a-Peak 0.0...490.3 m/s²
a-RMS 0.0...490.3 m/s²
Crest 1.0...50.0
Standard command Reset command for saved values
Signal Different filters for the internal signal processing
Filter DC High-pass Filter for the DC component (static acceleration) - for the calculation of all characteristic values 2 / 10 Hz
Filter A Bypass / high-pass / low-pass filter for characteristic acceleration values 1 / 3 / 5 kHz
Filter V Low-pass Filter for the characteristic vibration velocity values 1 kHz
Error configuration
Output 1-2 Output behaviour in case of an error OFF
ON
OU (output behaviour is only determined by the process value)
FOU1...2
Display setting Set physical unit m/s; mm/s; inch/s
m/s²; g; mg
°C; °F
uni - v-RMS
uni - a-Peak, a-RMS
uni.T
Basic settings
Standard command Restore factory settings
Standard command Start self-test
Self-test result Loading of results
MDC Loading of results
BLOB ID ID of the BLOB just sent
Diagnostics
Device status Displays the current device and diagnostic status
Event history Displays a list of the last 20 events
Event counter Increments how often the respective event has occurred
Machine monitoring Display of the machine operating time (mot) and display of the number of times the threshold value (mrc) is exceeded based on the process value v-RMS
Switch-on operations Number of switch-on operations of the sensor since delivery
Operating hours counter Operating hours counter of the sensor since delivery
Internal temperature Output of the internal temperature of the sensor by index
File transfer (BLOB) Transfer of binary file

7.2 Reading of raw data (BLOB)

A raw data block of the sensor can be read via the IO-Link BLOB mechanism. This raw data block has a recording length of 4 seconds with a sampling rate of 25 kHz. The individual samples have a bit width of 16 bits and the signed integer format. This results in a total size of the BLOB data set of 200000 bytes.

A raw data block can be recorded by means of 4 different mechanisms:

  1. Recording via BLOB ID
    For VV units with status A and status B, raw data can be recorded via the BLOB ID. (-4096)
  2. Triggered recording via a system command
    For VV units with status B, raw data can be recorded via a system command. This raw data can be accessed via the BLOB ID (-4097). If no system command has been sent before the query, 0 bytes of data are transmitted.
  3. Event-based recording
    VV units with status B have an internal mechanism that is coupled to switching output 1. If an event occurs at switching output 1, the raw data is recorded. This raw data can be accessed via the BLOB ID (-4098). If no switching event has taken place before the query, 0 bytes of data are transmitted.
  4. Triggered recording via PdOut
    VV units with status B can record raw data via a bit (no. 4) in the PdOut data flow. Raw data can be recorded via a rising edge of the corresponding bit with valid PdOut data. This raw data can be accessed via the BLOB ID (-4099). If no PdOut trigger has been set before the query, 0 bytes of data are transmitted.

The raw data block is recorded and transmitted from the start moment of the BLOB mechanism. The transmission takes at least 7 minutes depending on the cycle time of the master and the use of COM2 or COM3. Raw data transmission with COM3 takes approx. 2 minutes.

To obtain samples scaled to "1g" the data needs to be divided by a scaling factor of 216/125 = 524.288 (manual calculation required).

VV units with status B provide a memory area for raw data recording regardless of the recording method. This memory is always filled with the last event and the existing memory is overwritten.

The raw data is transmitted in binary format and saved as a *.bin file. The raw data can be imported and analysed in the parameter setting software VES004 (> version 2.07.00).

7.3 Application examples for filter setting and signal evaluation

7.3.1 Filter a - evaluation of the signal components between 2...1000 Hz

Settings

DC filter: 2 Hz, high-pass
a filter: 1 kHz, low-pass

Frequency response graph:

7.3.2 Filter a - evaluation of the signal components > 3000 Hz

Settings

DC filter: 2 Hz, high-pass
a filter: 3 kHz, high-pass

Frequency response graph:

7.3.3 Filter a - evaluation of the signal components > 10 Hz

Settings

DC filter: 10 Hz, high-pass
a filter: bypass

Frequency response graph:

7.3.4 Filter v - evaluation of the signal components between 2...1000 Hz

Settings

DC filter: 2 Hz, high-pass
v filter: 1 kHz, low-pass (fixed)

Frequency response graph:

7.3.5 Filter v - evaluation of the signal components between 10...1000 Hz

Settings

DC filter: 10 Hz, high-pass
v filter: 1 kHz, low-pass (fixed)

Frequency response graph:

8 Maintenance, repair and disposal

The operation of the unit is maintenance-free. It is not possible to repair the unit. Dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations when it is no longer used.

9 Factory setting

9.1 General configuration

Output configuration ou1 ou2 P-n
Hnc Hnc PnP
Digital output 1 dS1 dr1 0
Digital output 2 dS2 dr2 0
Error configuration FOU1 FOU2 OFF
OFF OFF
Display settings uni - v-RMS uni - a-Peak, a-RMS uni.T
m/s m/s² °C

9.2 Specific configuration

Output configuration VVB001 VVB010 VVB011 VVB020 VVB021
SEL1 v-RMS v-RMS v-RMS v-RMS v-RMS
SEL2 v-RMS a-RMS a-RMS a-RMS a-RMS
v-RMS [m/s]
SP1 - v-RMS 0.0045 0.0045 0.0045 0.0028 0.0028
rP1 - v-RMS 0.0043 0.0043 0.0043 0.0026 0.0026
SP2 - v-RMS 0.0071 0.0071 0.0071 0.0045 0.0045
rP2 - v-RMS 0.0069 0.0069 0.0069 0.0043 0.0043
a-Peak [m/s²]
SP1 - a-Peak 19.6 19.6 19.6 9.8 9.8
rP1 - a-Peak 17.6 17.6 17.6 7.8 7.8
SP2 - a-Peak 29.4 29.4 29.4 19.6 19.6
rP2 - a-Peak 27.4 27.4 27.4 17.6 17.6
a-RMS [m/s²]
SP1 - a-RMS 9.8 3.4 3.4 2.4 2.4
rP1 - a-RMS 7.8 1.4 1.4 0.4 0.4
SP2 - a-RMS 19.6 5.4 5.4 4.4 4.4
rP2 - a-RMS 17.6 3.4 3.4 2.4 2.4
Crest
SP1 - CREST 5 5 5 5 6
rP1 - CREST 4 4 4 4 4
SP2 - CREST 7 7 7 7 7
rP2 - CREST 6 6 6 6 6
Temperature
SP1 - TEMP 60 60 60 60 60
rP1 - TEMP 58 58 58 58 58
SP2 - TEMP 80 80 80 80 80
rP2 - TEMP 78 78 78 78 78
Filter DC
FILT-DC. FCUTOFF 10 10 2 10 2
FILT-DC. Type High-pass High-pass High-pass High-pass High-pass
Filter v
FILT-V. FCUTOFF 1000 1000 1000 1000 1000
FILT-V. Type Low-pass Low-pass Low-pass Low-pass Low-pass
Filter a
FILT-A. FCUTOFF 5000 5000 5000 5000 5000
FILT-A. Type Bypass Low-pass Low-pass Low-pass Low-pass
Models: VVB020, Vibration Sensor, VVB020 Vibration Sensor

File Info : application/pdf, 19 Pages, 380.16KB

PDF preview unavailable. Download the PDF instead.

80298004UK Adobe PDF Library 16.0

Related Documents

Preview SA5000 Flow Sensor - Technical Specifications and Operation
Detailed technical specifications, application information, electrical data, and operating conditions for the ifm SA5000 flow sensor. Includes information on media compatibility, temperature and pressure ratings, output signals, and interface protocols.
Preview ifm Industrial Sensors and Controls Catalog
Explore ifm's comprehensive range of industrial automation sensors and controls, featuring IO-Link technology, photoelectric sensors, inductive sensors, and more. Discover high-quality solutions for enhanced productivity and efficiency.
Preview ifm ZZ1060 IO-Link Master with USB Interface: Setup and Operation Guide
Comprehensive guide for setting up and operating the ifm ZZ1060 IO-Link master with USB interface, including connection, parameter setting with ifm moneo|configure free, and process data monitoring.
Preview ifm O1D100/O1D120 Optical Distance Sensor Operating Instructions
Comprehensive operating instructions for the ifm O1D100 and O1D120 optical distance sensors, covering installation, electrical connection, operation, menu structure, parameter settings, and troubleshooting.
Preview ifm O1D100 Optical Distance Sensor Operating Instructions
Comprehensive operating instructions for the ifm O1D100 optical distance sensor, covering installation, functions, parameter settings, and troubleshooting.
Preview SA5000 Flow Sensor: Technical Specifications and Features
Comprehensive technical data, features, and application details for the IFM SA5000 flow sensor, including electrical, mechanical, and environmental specifications.
Preview ifm SM2001 Magnetic-Inductive Flow Meter Technical Specification
Detailed technical specifications, features, and application data for the ifm SM2001 magnetic-inductive flow meter, including electrical, mechanical, and output characteristics, accuracy, and interface information.
Preview ifm DTI600 RF Identification System Read/Write Head Installation Instructions
Comprehensive installation guide for the ifm DTI600 RF identification system read/write head, detailing safety precautions, product functions, installation procedures, electrical connections, indicator meanings, technical specifications, and regulatory approvals.