Little Giant VCMA-PRO Series Condensate Pumps
Product Overview and Technical Specifications
Applications
Designed for automatic collection and removal of condensate from air conditioning, refrigeration, and dehumidification equipment when gravity drainage is not possible or practical. Also suitable for high efficiency oil and gas-fired condensing furnace and condensing boiler equipment.
Features
- External test/run lever
- Slim footprint
- Vertical centrifugal pump design
- Stainless steel motor shaft
- Automatic start and stop operation
- Galvanized steel “quick install” wall mount bracket
- Some models equipped with external, float activated switch for automatic high-level water detection (overflow detection switch)
- For models with overflow detection switch: dual function NO and NC operation (set to NO from factory for equipment shut down connection)
- Models equipped with overflow detection switch include two 5" switch lead wires
- 3/8" O.D. barbed ¼-turn quick release, locking discharge adapter with built-in check valve
- Rubber feet for vibration/noise dampening
- “Anti-sweat” tank sleeve included on select models and available separately for all others
- 3 - 1-1/8" diameter inlet openings, two fitted with removable cap plug (3 + 1 inlet openings for models without overflow detection switch)
- Recessed tank sump
- Oil resistant tank and check valve
- Thermally protected, fan cooled motor
- Maximum water temperature: 140 °F
- 6', 3-conductor cable with grounded 3-prong plug
- Some models include 20' x 3/8" I.D. vinyl discharge tubing
- 3-year warranty
Series Specifications: VCMA-20-PRO
Item No. | Model | HP | Input Voltage | Hz | Amps | Watts | Discharge Size | Check Valve | Overflow Detection Switch | Performance GPH (LPH) @ 1' | Performance GPH (LPH) @ 5' | Performance GPH (LPH) @ 10' | Performance GPH (LPH) @ 15' | Performance GPH (LPH) @ 20' | Shut-Off Ft. | PSI | Cord | Weight (lbs) |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
554620 | VCMA-20UL-PRO | 1/30 | 115 | 60 | 1.5 | 93 | 3/8" (9.5 mm) | 3/8" (9.5 mm) | No | 84 (318.4) | 75 (284.3) | 60 (227.4) | 42 (159.2) | 10 (37.9) | 21 (6.4 m) | 9.1 | 6' (1.8 m) | 5.5 (2.5 Kg) |
554621 | VCMA-20UL-PRO | 1/30 | 230 | 50/60 | 0.7/0.6 | 75 | 3/8" (9.5 mm) | 3/8" (9.5 mm) | No | 80 (302.2) | 69 (261.5) | 54 (204.7) | 36 (136.4) | 0 (0) | 20 (6.1 m) | 8.6 | 6' (1.8 m) | 5.5 (2.5 Kg) |
554630 | VCMA-20ULS-PRO | 1/30 | 115 | 60 | 1.5 | 93 | 3/8" (9.5 mm) | 3/8" (9.5 mm) | Yes | 84 (318.4) | 75 (284.3) | 60 (227.4) | 42 (159.2) | 10 (37.9) | 21 (6.4 m) | 9.1 | 6' (1.8 m) | 5.5 (2.5 Kg) |
554631 | VCMA-20ULS-PRO | 1/30 | 230 | 50/60 | 0.7/0.6 | 75 | 3/8" (9.5 mm) | 3/8" (9.5 mm) | Yes | 80 (302.2) | 69 (261.5) | 54 (204.7) | 36 (136.4) | 0 (0) | 20 (6.1 m) | 8.6 | 6' (1.8 m) | 5.5 (2.5 Kg) |
Series Specifications: VCMA-20-PRO with Tubing
Item No. | Model | HP | Input Voltage | Hz | Amps | Watts | Discharge Size | Check Valve | Overflow Detection Switch | Performance GPH (LPH) @ 1' | Performance GPH (LPH) @ 5' | Performance GPH (LPH) @ 10' | Performance GPH (LPH) @ 15' | Performance GPH (LPH) @ 20' | Shut-Off Ft. | PSI | Cord | Weight (lbs) |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
554650 | VCMA-20ULST-PRO | 1/30 | 115 | 60 | 1.5 | 93 | 3/8" (9.5 mm) | 3/8" (9.5 mm) | Yes | 84 (318.4) | 75 (284.3) | 60 (227.4) | 42 (159.2) | 10 (37.9) | 21 (6.4 m) | 9.1 | 6' (1.8 m) | 5.5 (2.5 Kg) |
554651 | VCMA-20ULST-PRO | 1/30 | 230 | 50/60 | 0.7/0.6 | 75 | 3/8" (9.5 mm) | 3/8" (9.5 mm) | Yes | 80 (303.2) | 69 (261.5) | 54 (204.7) | 36 (136.4) | 0 (0) | 20 (6.1 m) | 8.6 | 6' (1.8 m) | 5.5 (2.5 Kg) |
Series Specifications: VCMA-20-PRO with Anti-Sweat Sleeve
Item No. | Model | HP | Input Voltage | Hz | Amps | Watts | Discharge Size | Check Valve | Overflow Detection Switch | Performance GPH (LPH) @ 1' | Performance GPH (LPH) @ 5' | Performance GPH (LPH) @ 10' | Performance GPH (LPH) @ 15' | Performance GPH (LPH) @ 20' | Shut-Off Ft. | PSI | Cord | Weight (lbs) |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
554642 | VCMA-20ULS-C-PRO | 1/30 | 115 | 60 | 1.5 | 93 | 3/8" (9.5 mm) | 3/8" (9.5 mm) | Yes | 84 (318.4) | 75 (284.3) | 60 (227.4) | 42 (159.2) | 10 (37.9) | 21 (6.4 m) | 9.1 | 6' (1.8 m) | 5.5 (2.5 Kg) |
Replacement Parts & Kits
Item | Part Number |
---|---|
Tank (4 pack, 554620, 554630, 554650, 554651, 554621, 554642) | 154390 |
Feet, Rubber | 925047 |
Cover, Motor | 10000013577 |
Overflow Detection Switch Assembly (554630, 554631, 554650, 554651, 554642) | 10000014115, 10000014117 |
Anti-sweat Sleeve and Bracket (554642) | 10000014026 |
Bracket, Tank (554620, 554630, 554650, 554651, 554621, 664631) | 154483 |
Engineering Data
Diagram showing the pump with dimensions labeled A, B, C, and D. The diagram illustrates the side profile and top view of the pump unit.
Model | A | B | C | D |
---|---|---|---|---|
VCMA-20UL-PRO | 6.5" (165.1mm) | 10.2" (259.1 mm) | 4.8" (121.9 mm) | 3.4" (86.4 mm) |
VCMA-20ULS-PRO | 6.5" (165.1mm) | 10.2" (259.1 mm) | 4.8" (121.9 mm) | 3.4" (86.4 mm) |
VCMA-20ULST-PRO | 6.5" (165.1mm) | 10.2" (259.1 mm) | 4.8" (121.9 mm) | 3.4" (86.4 mm) |
VCMA-20ULS-C-PRO | 6.8" (172.7mm) | 10.3" (261.6 mm) | 5.1" (129.5 mm) | 3.4" (86.4 mm) |
Performance Data
A line graph illustrating performance data. The X-axis represents Flow in Gallons/Hour (and Liters/Hour), and the Y-axis represents Head in Feet (and Meters). Two lines are shown: one for 115V, 60 Hz, and another for 230V, 60 Hz, indicating the GPH/LPH output at various head levels. The graph shows that flow rate decreases as head increases for both voltage configurations.
Construction
Component | Material |
---|---|
Housing/Tank Cover | ABS |
Motor Cover | ABS |
Volute | ABS |
Tank | Polypropylene |
Impeller | Polypropylene |
Switch Float | ABS |
Check Valve | Acetal |