40G, 100G, 400G and 800G Cabling Reference Guide

This document serves as a guide to select the best Corning Optical Communications bill-of-materials (BOM) for your structured cabling application (scenario).

Arista Transceiver Connector Types

This cabling guide provides component information necessary to work with 40G, 100G, and 400G transceivers and breakout options within the same rack or row and across data center scenarios. Arista optical transceiver modules have different connector types (refer to the Arista Transceiver and Cable Guide). With the introduction of 400G, new form factors have been released, including multimode 16-F MPO angled and single-mode CS® and SN® connectors. Corning's EDGE8® solution is designed to support both single-mode and multimode optical interfaces based on the use of two, eight, and 16 fibers.

The following is a partial list of Arista transceivers by connector type:

MPO-16 Angled MPO-8/12 LC Duplex CS and SN Twin MPO-8/12 APC Interface (OSFP/QSFP-DD) LC Duplex UPC Interface (OSFP/QSFP-DD)
Multimode QDD-400G-SR8
OSFP-400G-SR8
Multimode QDD-400G-VSR4
QDD-400G-SRBD
QSFP-100G-SR4
QSFP-40G-SR4
Single-Mode OSFP-400G-DR4
QDD-400G-DR4
QSFP-100G-PSM4
QSFP-40G-PLR4
QSFP-40G-PLR4
CN: Single-mode
OSFP-400G-XDR4-S
QDD-400G-XDR4-S
OSFP-400G-PLR4-S
QDD-400G-PLR4-S
Twin MPO-8/12 APC Interface (OSFP/QSFP-DD)
QDD-800G-2XDR4
QDD-800G-2FR4
QDD-800G-2PLR4
QDD-800G-2LR4
OSFP-800G-2XDR4
OSFP-800G-2FR4
OSFP-800G-2PLR4
OSFP-800G-2LR4
LC Duplex UPC Interface (OSFP/QSFP-DD)
Single-mode
OSFP-400G-DR4
QDD-400G-DR4
QSFP-100G-PSM4
QSFP-40G-PLR4
QSFP-40G-PLR4
Multimode QSFP-100G-SWDM4
QSFP-40G-SRBD
QSFP-40G-UNIV
SFP-25G-SR
SFP-10G-SR
Single-Mode OSFP-400G-FR4
QDD-400G-FR4
QSFP-100G-CWDM4
QSFP-100G-LR4
QSFP-100G-ERL4
QSFP-100G-DR
QSFP-100G-FR
QSFP-100G-LR
QSFP-40G-LR4
QSFP-40G-ER4
SN: Single-mode
OSFP-400G-XDR4-S
QDD-400G-XDR4-S
OSFP-400G-PLR4-S
QDD-400G-PLR4-S

Note: Single-mode fiber type: Corning® SMF-28® Ultra Optical Fiber. Multimode fiber type: Corning® ClearCurve® OM4.

To review a more comprehensive list of transceiver breakout options, please refer to each cabling scenario or visit arista.com.

Scenario 1: MPO-8/12 to MPO-8/12 Local

Diagram illustrating an MPO-8/12 transceiver connecting locally to another MPO-8/12 transceiver.

Item OS2 Part Number (Americas) OS2 Part Number (EMEA and APJ) OM4 Part Number (Americas) OM4 Part Number (EMEA and APJ) Description
1 JE8E808GE8-NBxxxF JE8E808GEZ-NBxxxM JE6E608QE8-NBxxxF JE6E608QEZ-NBxxxM EDGE8®, 8-F Jumper, MTP® (unpinned) to MTP (unpinned), Type-B polarity, xxxF (feet) or xxxM (meters)

Note: Americas uses plenum cable and EMEA/APJ uses LSZH™/CPR Rated cable. Lengths in meters are also available for the Americas.

Scenario 2: MPO-8/12 to MPO-8/12 Across DC with Trunk

Diagram illustrating an MPO-8/12 transceiver connecting across a data center via a trunk cable to another MPO-8/12 transceiver.

Item OS2 Part Number (Americas) OS2 Part Number (EMEA and APJ) OM4 Part Number (Americas) OM4 Part Number (EMEA and APJ) Description
1 JE8E808GE8-NBxxxF JE8E808GEZ-NBxxxM JE6E608QE8-NBxxxF JE6E608QEZ-NBxxxM EDGE8®, MTP® (non-pinned) to MTP (non-pinned) 8-F Jumper, TIA-568 Type-B polarity, xxxF (feet) or xxxM (meters)
2 EDGE8-CP32-V1 EDGE8-CP32-V1 EDGE8-CP32-V3 EDGE8-CP32-V3 EDGE8 32-F MTP Adapter Panel, (4-port)
3 GE7E732GPNDDUxxxF* GE7E732GLZDDUxxxM* GE5E532QPNDDUxxxF* GE5E532QLZDDUxxxM* EDGE8, MTP Trunk, 32 F, MTP (pinned) to MTP (pinned), 33-in (840-mm) legs, Type-B polarity, pulling grip on first end only, xxxF (feet) or xxxM (meters)
4 EDGE8-xxU EDGE8-xxU EDGE8-xxU EDGE8-xxU Please refer to Annex 1 to choose the best option for your application

Note: Americas uses plenum cable and EMEA/APJ uses LSZH™/CPR Rated cable. *Trunks are available in fiber counts of 8 to 288 fibers or higher. Lengths in meters are also available for the Americas.

Scenario 3: MPO-8/12 to LC Duplex Local

Diagram illustrating an MPO-8/12 transceiver connecting locally to LC Duplex transceivers.

Item OS2 Part Number (Americas) OS2 Part Number (EMEA and APJ) OM4 Part Number (Americas) OM4 Part Number (EMEA and APJ) Description
1 ECM8-04E8-GE8B-xxxF* ECM8-04E8-GEZB-xxxM* ECM8-05E6-QE8B-xxxF* ECM8-05E6-QEZB-xxxM EDGE8® Port Breakout Module, LC Duplex to MTP® (unpinned), 8 F, universal polarity, xxxF (feet) or xxxM (meters)*
2 787802GD120xxxF E787802GNZ20xxxM 797902QD120xxxF E797902QNZ20xxxM EDGETM LC Uniboot to LC Uniboot Duplex Jumper, 2.0 mm cable, xxxF (feet) or xxxM (meters)
3 EDGE8-xxU EDGE8-xxU EDGE8-xxU EDGE8-xxU Please refer to Annex 1 to choose the best option for your application

Note: Americas uses plenum/riser cable and EMEA/APJ uses LSZH™/CPR Rated cable. *The EDGE8 port breakout module has a tail length of maximum 75 ft (25 m). Lengths in meters are also available for the Americas.

Scenario 4: MPO-8/12 to LC Duplex Across DC with Trunk

Diagram illustrating an MPO-8/12 transceiver connecting across a data center via a trunk cable to LC Duplex transceivers.

Item OS2 Part Number (Americas) OS2 Part Number (EMEA and APJ) OM4 Part Number (Americas) OM4 Part Number (EMEA and APJ) Description
1 JE8E808GE8-NAxxxF JE8E808GEZ-NAxxxM JE6E608QE8-NAxxxF JE6E608QEZ-NAxxxM EDGE8®, 8-F Jumper, MTP® (unpinned) to MTP (unpinned), Type-A polarity, xxxF (feet) or xxxM (meters)
2 EDGE8-CP32-V1 EDGE8-CP32-V1 EDGE8-CP32-V3 EDGE8-CP32-V3 EDGE8 4-Port MTP Connector Panel
3 GE7E732GPNDDUxxxF* GE7E732GLZDDUxxxM* GE5E532QPNDDUxxxF* GE5E532QLZDDUxxxM* EDGE8, MTP Trunk, 32 F, MTP (pinned) to MTP (pinned), 33-in (840-mm) legs, Type-B polarity, pulling grip on first end only, xxxF (feet) or xxxM (meters)
4 ECM8-UM08-04-E8G-ULL ECM8-UM08-04-E8G-ULL ECM8-UM08-05-E6Q-ULL ECM8-UM08-05-E6Q-ULL EDGE8 Ultra-Low-Loss Module, LC Duplex to MTP (unpinned), 8 F, universal polarity
5 787802GD120xxxF E787802GNZ20xxxM 797902QD120xxxF E797902QNZ20xxxM EDGETM LC Uniboot to LC Uniboot Duplex Jumper, 2.0 mm cable, xxxF (feet) or xxxM (meters)
6 EDGE8-xxU EDGE8-xxU EDGE8-xxU EDGE8-xxU Please refer to Annex 1 to choose the best option for your application

Note: Americas uses plenum/riser cable and EMEA/APJ uses LSZH™/CPR Rated cable. *Trunks available in fiber counts of 8 to 288 fibers or higher. Lengths in meters are also available for the Americas.

Scenario 5: MPO-16 Angled to MPO-16 Angled Local

Diagram illustrating an MPO-16 Angled transceiver connecting locally to another MPO-16 Angled transceiver.

Item OM4 Part Number (Americas) OM4 Part Number (EMEA and APJ) Description
1 JC3C316QPH-NBxxxF JC3C316QLZ-NBxxxM 16-F Jumper, MTP®-16 Angled (unpinned) to MTP-16 Angled (unpinned), Type-B polarity, xxxF (feet) or xxxM (meters)

Note: Americas uses plenum cable and EMEA/APJ uses LSZH™/CPR Rated cable. Lengths in meters are also available for the Americas.

Scenario 6: MPO-16 Angled to MPO-16 Angled Across DC with Trunk

Diagram illustrating an MPO-16 Angled transceiver connecting across a data center via a trunk cable to another MPO-16 Angled transceiver.

Item OM4 Part Number (Americas) OM4 Part Number (EMEA and APJ) Description
1 HC3E616QPH-LBxxxF HC3E616QLZ-LBxxxM 16-F Y-Harness, MTP®-16 Angled (unpinned) to two 8-F (unpinned) MTPs, 36-in (910-mm) breakout leg length, Type-B polarity, xxxF (feet) or xxxM (meters)
2 EDGE8-CP32-V3 EDGE8-CP32-V3 EDGE8® 32-F MTP Adapter MM/OM4 Panel, 4-port
3 GE5E532QPNDDUxxxF* GE5E532QLZDDUxxxM* EDGE8, MTP Trunk, 32 F, MTP (pinned) to MTP (pinned), 33-in (840-mm) legs, Type-B polarity, pulling grip on first end only, xxxF (feet) or xxxM (meters)
4 EDGE8-xxU EDGE8-xxU Please refer to Annex 1 to choose the best option for your application

Note: Americas uses plenum cable and EMEA/APJ uses LSZH™/CPR Rated cable. *Trunks available in fiber counts of 8 to 288 fibers or higher. Lengths in meters are also available for the Americas.

Scenario 7: MPO-16 Angled to MPO-8/12 Local

Diagram illustrating an MPO-16 Angled transceiver connecting locally to MPO-8/12 transceivers.

Item OM4 Part Number (Americas) OM4 Part Number (EMEA and APJ) Description
1 HC3E616QPH-LBxxxF HC3E616QLZ-LBxxxM 16-F Y-Harness, MTP®-16 Angled (unpinned) to two 8-F (unpinned) MTPs, 36-in (910-mm) breakout leg length, Type-B polarity, xxxF (feet) or xxxM (meters)

Note: Americas uses plenum cable and EMEA/APJ uses LSZH™/CPR Rated cable. Lengths in meters are also available for the Americas.

Scenario 8: MPO-16 Angled to MPO-8/12 Across DC with Trunk

Diagram illustrating an MPO-16 Angled transceiver connecting across a data center via a trunk cable to MPO-8/12 transceivers.

Item OM4 Part Number (Americas) OM4 Part Number (EMEA and APJ) Description
1 HC3E616QPH-LBxxxF HC3E616QLZ-LBxxxM 16-F Y-Harness, MTP®-16 Angled (unpinned) to two 8-F (unpinned) MTPs, 36-in (910-mm) breakout leg length, Type-B polarity, xxxF (feet) or xxxM (meters)
2 EDGE8-CP32-V3 EDGE8-CP32-V3 EDGE8® 32-F MTP Adapter MM/OM4 Panel, 4-port
3 GE5E532QPNDDUxxxF* GE5E532QLZDDUxxxM* EDGE8, MTP Trunk, 32 F, MTP (pinned) to MTP (pinned), 33-in (840-mm) legs, Type-B polarity, pulling grip on first end only, xxxF (feet) or xxxM (meters)
4 JE6E608QE8-NBxxxF JE6E608QEZ-NBxxxM EDGE8, 8 F Jumper, MTP (unpinned) to MTP (unpinned), Type-B polarity, xxxF (feet) or xxxM (meters)
5 EDGE8-xxU EDGE8-xxU Please refer to Annex 1 to choose the best option for your application

Note: Americas uses plenum cable and EMEA/APJ uses LSZH™/CPR Rated cable. *Trunks available in fiber counts of 8 to 288 fibers or higher. Lengths in meters are also available for the Americas.

Scenario 9: MPO-16 Angled to LC Duplex Local

Diagram illustrating an MPO-16 Angled transceiver connecting locally to LC Duplex transceivers.

Item OM4 Part Number (Americas) OM4 Part Number (EMEA and APJ) Description
1 HC3E516QPH-LBxxxF HC3E516QLZ-LBxxxM 16-F Y-Harness, MTP®-16 Angled (unpinned) to two 8-F (pinned) MTPs, 36-in (910-mm) breakout leg length, Type-B polarity, xxxF (feet) or xxxM (meters)
2 ECM8-UM08-05-E6Q-ULL ECM8-UM08-05-E6Q-ULL EDGE8® Ultra-Low-Loss Module, LC Duplex to MTP (unpinned), 8 F, universal polarity
3 797902QD120xxxF E797902QNZ20xxxM EDGETM LC PC Uniboot to LC PC Uniboot Duplex Jumper, 2.0 mm cable, xxxF (feet) or xxxM (meters)
4 EDGE8-xxU EDGE8-xxU Please refer to Annex 1 to choose the best option for your application

Note: Americas uses plenum/riser cable and EMEA/APJ uses LSZH™/CPR Rated cable. Lengths in meters are also available for the Americas.

Scenario 10: MPO-16 Angled to LC Duplex Across DC with Trunk

Diagram illustrating an MPO-16 Angled transceiver connecting across a data center via a trunk cable to LC Duplex transceivers.

Item OM4 Part Number (Americas) OM4 Part Number (EMEA and APJ) Description
1 HC3E616QPH-LAxxxF HC3E616QLZ-LAxxxM 16-F Y-Harness, MTP®-16 Angled (unpinned) to two 8-F (unpinned) MTPs, 36-in (910-mm) breakout leg length, Type-A polarity, xxxF (feet) or xxxM (meters)
2 EDGE8-CP32-V3 EDGE8-CP32-V3 EDGE8® 32-F MTP Adapter MM/OM4 Panel, 4-port
3 GE5E532QPNDDUxxxF* GE5E532QLZDDUxxxM* EDGE8, MTP Trunk, 32 F, MTP (pinned) to MTP (pinned), 33-in (840-mm) legs, Type-B polarity, pulling grip on first end only, xxxF (feet) or xxxM (meters)
4 ECM8-UM08-05-E6Q-ULL ECM8-UM08-05-E6Q-ULL EDGE8 Ultra-Low-Loss Module, LC Duplex to MTP (unpinned), 8 F, universal polarity
5 797902QD120xxxF E797902QNZ20xxxM EDGETM LC PC Uniboot to LC PC Uniboot Duplex Jumper, 2.0 mm cable, xxxF (feet) or xxxM (meters)
6 EDGE8-xxU EDGE8-xxU Please refer to Annex 1 to choose the best option for your application

Note: Americas uses plenum/riser cable and EMEA/APJ uses LSZH™/CPR Rated cable. *Trunks available in fiber counts of 8 to 288 fibers or higher. Lengths in meters are also available for the Americas.

Scenario 11: CS® to CS Local

Diagram illustrating a CS transceiver connecting locally to another CS transceiver.

Item OS2 Part Number (Americas) OS2 Part Number (EMEA and APJ) Description
1 CUCU02GD120xxxF ECUCU02GNZ20xxxM 2-F Jumper, Duplex CS UPC to Duplex CS UPC, 2.0 mm cable, xxxF (feet) or xxxM (meters)

Note: Americas uses riser cable and EMEA/APJ uses LSZH™/CPR Rated cable. Lengths in meters are also available for the Americas.

Scenario 12: CS® to CS Across DC with Trunk

Diagram illustrating a CS transceiver connecting across a data center via a trunk cable to another CS transceiver.

Item OS2 Part Number (Americas) OS2 Part Number (EMEA and APJ) Description
1 78CU02GD120xxxF E78CU02GNZ20xxxM 2-F Jumper, Duplex CS UPC to LC UPC Uniboot Duplex, 2.0 mm cable, xxxF (feet) or xxxM (meters)
2 ECM8-UM08-04-E8G-ULL ECM8-UM08-04-E8G-ULL EDGE8® Ultra-Low-Loss Module, LC duplex to MTP® (unpinned), 8 F, universal polarity
3 GE7E708GPNDDUxxxF* GE7E708GLZDDUxxxM* EDGE8, MTP Trunk, 8 F, MTP (pinned) to MTP (pinned), 33-in (840-mm) legs, Type-B polarity, pulling grip on first end only, xxxF (feet) or xxxM (meters)
4 EDGE8-xxU EDGE8-xxU Please refer to Annex 1 to choose the best option for your application

Note: Americas uses plenum/riser cable and EMEA/APJ uses LSZH™/CPR Rated cable. *Trunks available in fiber counts of 8 to 288 fibers or higher. Lengths in meters are also available for the Americas.

Scenario 13: CS® to LC Duplex Local

Diagram illustrating a CS transceiver connecting locally to LC Duplex transceivers.

Item OS2 Part Number (Americas) OS2 Part Number (EMEA and APJ) Description
1 78CU02GD120xxxF E78CU02GNZ20xxxM 2-F Jumper, Duplex CS UPC to LC UPC Uniboot Duplex, 2.0 mm cable, xxxF (feet) or xxxM (meters)

Note: Americas uses riser cable and EMEA/APJ uses LSZH™/CPR Rated cable. Lengths in meters are also available for the Americas.

Scenario 14: CS® to LC Duplex Across DC with Trunk

Diagram illustrating a CS transceiver connecting across a data center via a trunk cable to LC Duplex transceivers.

Item OS2 Part Number (Americas) OS2 Part Number (EMEA and APJ) Description
1 78CU02GD120xxxF E78CU02GNZ20xxxM 2-F Jumper, Duplex CS UPC to LC UPC Uniboot Duplex, 2.0 mm cable, xxxF (feet) or xxxM (meters)
2 ECM8-UM08-04-E8G-ULL ECM8-UM08-04-E8G-ULL EDGE8® Ultra-Low-Loss Module, LC Duplex to MTP® (unpinned), 8 F, universal polarity
3 GE7E708GPNDDUxxxF* GE7E708GLZDDUxxxM* EDGE8, MTP Trunk, 8 F, MTP (pinned) to MTP (pinned), 33-in (840-mm) legs, Type-B polarity, pulling grip on first end only, xxxF (feet) or xxxM (meters)
4 787802GD120xxxF E787802GNZ20xxxM EDGETM LC UPC Uniboot to LC UPC Uniboot Duplex Jumper, 2.0 mm cable, xxxF (feet) or xxxM (meters)
5 EDGE8-xxU EDGE8-xxU Please refer to Annex 1 to choose the best option for your application

Note: Americas uses plenum/riser cable and EMEA/APJ uses LSZH™/CPR Rated cable. *Trunks available in fiber counts of 8 to 288 fibers or higher. Lengths in meters are also available for the Americas.

Scenario 15: SN® to SN Local

Diagram illustrating an SN transceiver connecting locally to another SN transceiver.

Item OS2 Part Number (Americas) OS2 Part Number (EMEA and APJ) Description
1 NUNU02GD116xxxF ENUNU02GNZ16xxxM 2-F Jumper, Duplex SN UPC to SN UPC, 1.6 mm cable, xxxF (feet) or xxxM (meters)

Note: Americas uses riser cable and EMEA/APJ uses LSZH™/CPR Rated cable. Lengths in meters are also available for the Americas.

Scenario 16: SN® to SN Across the Data Center

Diagram illustrating an SN transceiver connecting across a data center via a trunk cable to another SN transceiver.

Item OS2 Part Number (Americas) OS2 Part Number (EMEA and APJ) Description
1 78NU02GD116xxxF E78NU02GNZ16xxxM 2-F Jumper, SN UPC to LC Uniboot UPC Duplex Jumper, 1.6 mm cable, xxxF (feet) or xxxM (meters)
2 ECM8-UM08-04-E8G-ULL ECM8-UM08-04-E8G-ULL EDGE8® Ultra-Low-Loss Module, LC Duplex to MTP® (unpinned), 8 F, universal polarity
3 GE7E708GPNDDUxxxF* GE7E708GLZDDUxxxM* EDGE8, MTP Trunk, 8 F, MTP (pinned) to MTP (pinned), 33-in (840-mm) legs, Type-B polarity, pulling grip on first end only, xxxF (feet) or xxxM (meters)
4 EDGE8-xxU EDGE8-xxU Please refer to Annex 1 to choose the best option for your application

Note: Americas uses plenum/riser cable and EMEA/APJ uses LSZH™/CPR Rated cable. *Trunks available in fiber counts of 8 to 288 fibers or higher. Lengths in meters are also available for the Americas.

Scenario 17: SN® to LC Duplex Local

Diagram illustrating an SN transceiver connecting locally to LC Duplex transceivers.

Item OS2 Part Number (Americas) OS2 Part Number (EMEA and APJ) Description
1 78NU02GD116xxxF E78NU02GNZ16xxxM 2-F Jumper, SN UPC to LC Uniboot UPC Duplex Jumper, 1.6 mm cable, xxxF (feet) or xxxM (meters)

Note: Americas uses riser cable and EMEA/APJ uses LSZH™/CPR Rated cable. Lengths in meters are also available for the Americas.

Scenario 18: SN® to LC Duplex Across the Data Center

Diagram illustrating an SN transceiver connecting across a data center via a trunk cable to LC Duplex transceivers.

Item OS2 Part Number (Americas) OS2 Part Number (EMEA and APJ) Description
1 78NU02GD116xxxF E78NU02GNZ16xxxM 2-F Jumper, SN UPC to LC Uniboot UPC Duplex Jumper, 1.6 mm cable, xxxF (feet) or xxxM (meters)
2 ECM8-UM08-04-E8G-ULL ECM8-UM08-04-E8G-ULL EDGE8® Ultra-Low-Loss Module, LC Duplex to MTP® (unpinned), 8 F, universal polarity
3 GE7E708GPNDDUxxxF* GE7E708GLZDDUxxxM* EDGE8, MTP Trunk, 8 F, MTP (pinned) to MTP (pinned), 33-in (840-mm) legs, Type-B polarity, pulling grip on first end only, xxxF (feet) or xxxM (meters)
4 787802GD120xxxF E787802GNZ20xxxM EDGETM LC UPC Uniboot to LC UPC Uniboot Duplex Jumper, 2.0 mm cable, xxxF (feet) or xxxM (meters)
5 EDGE8-xxU EDGE8-xxU Please refer to Annex 1 to choose the best option for your application

Note: Americas uses plenum/riser cable and EMEA/APJ uses LSZH™/CPR Rated cable. *Trunks available in fiber counts of 8 to 288 fibers or higher. Lengths in meters are also available for the Americas.

Scenario 19: 800G and 400G – Local

Diagram illustrating 800G and 400G transceivers used in local switch-to-server applications.

Near End Optic (Left) Far End Optic (Right) Reach
OSFP-800G-2XDR4 (single-mode) OSFP-800G-2XDR4 (single-mode) 2 km
OSFP-800G-2PLR4 (single-mode) OSFP-800G-2PLR4 (single-mode) 10 km
QDD-800G-2XDR4 (single-mode) QDD-800G-2XDR4 (single-mode) 2 km
QDD-800G-2PLR4 (single-mode) QDD-800G-2PLR4 (single-mode) 10 km
OSFP-800G-2VSR4 (multimode) OSFP-800G-2VSR4 (multimode) 50 m
QDD-800G-2VSR4 (multimode) QDD-800G-2VSR4 (multimode) 50 m
OSFP-800G-2XDR4 (single-mode) OSFP-400G-DR4 (single-mode) 2 km
OSFP-800G-2PLR4 (single-mode) OSFP-400G-DR4 (single-mode) 10 km
QDD-800G-2XDR4 (single-mode) QDD-400G-DR4 (single-mode) 2 km
QDD-800G-2PLR4 (single-mode) QDD-400G-DR4 (single-mode) 10 km
OSFP-800G-2VSR4 (multimode) QSFP-400G-SR4 (multimode) 50 m
QDD-800G-2VSR4 (multimode) QSFP-400G-SR4 (multimode) 50 m

Scenario 20: 800G and 400G – Across DC with Trunk

Diagram illustrating 800G and 400G transceivers connecting across a data center via a trunk cable.

Near End Optic (Left) Far End Optic (Right) Reach
OSFP-800G-2XDR4 (single-mode) OSFP-800G-2XDR4 (single-mode) 2 km
OSFP-800G-2PLR4 (single-mode) OSFP-800G-2PLR4 (single-mode) 10 km
QDD-800G-2XDR4 (single-mode) QDD-800G-2XDR4 (single-mode) 2 km
QDD-800G-2PLR4 (single-mode) QDD-800G-2PLR4 (single-mode) 10 km
OSFP-800G-2VSR4 (multimode) OSFP-800G-2VSR4 (multimode) 50 m
QDD-800G-2VSR4 (multimode) QDD-800G-2VSR4 (multimode) 50 m
OSFP-800G-2XDR4 (single-mode) OSFP-400G-DR4 (single-mode) 2 km
OSFP-800G-2PLR4 (single-mode) OSFP-400G-DR4 (single-mode) 10 km
QDD-800G-2XDR4 (single-mode) QDD-400G-DR4 (single-mode) 2 km
QDD-800G-2PLR4 (single-mode) QDD-400G-DR4 (single-mode) 10 km
OSFP-800G-2VSR4 (multimode) QSFP-400G-SR4 (multimode) 50 m
QDD-800G-2VSR4 (multimode) QSFP-400G-SR4 (multimode) 50 m

Scenario 21: 800G and 400G – Across DC with Trunk

Diagram illustrating 800G and 400G transceivers connecting across a data center via a trunk cable.

Near End Optic (Left) Far End Optic (Right) Reach
OSFP-800G-2FR4 (single-mode) OSFP-800G-2FR4 (single-mode) 2 km
OSFP-800G-2LR4 (single-mode) OSFP-800G-2LR4 (single-mode) 10 km
QDD-800G-2FR4 (single-mode) QDD-800G-2FR4 (single-mode) 2 km
QDD-800G-2LR4 (single-mode) QDD-800G-2LR4 (single-mode) 10 km
OSFP-800G-2FR4 (single-mode) OSFP-400G-FR4 (single-mode) 2 km
OSFP-800G-2LR4 (single-mode) OSFP-400G-FR4 (single-mode) 10 km
QDD-800G-2FR4 (single-mode) QDD-400G-FR4 (single-mode) 2 km
QDD-800G-2LR4 (single-mode) QDD-400G-FR4 (single-mode) 10 km

Scenario 22: 800G and 200G – Local

Diagram illustrating 800G and 200G transceivers used in local switch-to-server applications.

Near End Optic (Left) Far End Optic (Right) Reach
OSFP-800G-2XDR4 (single-mode) QSFP-200G-FR4 (single-mode) 2 km
OSFP-800G-2PLR4 (single-mode) QSFP-200G-FR4 (single-mode) 10 km
QDD-800G-2XDR4 (single-mode) QSFP-200G-FR4 (single-mode) 2 km
QDD-800G-2PLR4 (single-mode) QSFP-200G-FR4 (single-mode) 10 km
OSFP-800G-2VSR4 (multimode) QSFP-200G-SR4 (multimode) 50 m
QDD-800G-2VSR4 (multimode) QSFP-200G-SR4 (multimode) 50 m

Scenario 23: 800G and 200G – Across DC with Trunk

Diagram illustrating 800G and 200G transceivers connecting across a data center via a trunk cable.

Near End Optic (Left) Far End Optic (Right) Reach
OSFP-800G-2XDR4 (single-mode) QSFP-200G-FR4 (single-mode) 2 km
OSFP-800G-2PLR4 (single-mode) QSFP-200G-FR4 (single-mode) 10 km
QDD-800G-2XDR4 (single-mode) QSFP-200G-FR4 (single-mode) 2 km
QDD-800G-2PLR4 (single-mode) QSFP-200G-FR4 (single-mode) 10 km
OSFP-800G-2VSR4 (multimode) QSFP-200G-SR4 (multimode) 50 m
QDD-800G-2VSR4 (multimode) QSFP-200G-SR4 (multimode) 50 m

Scenario 24: 800G and 400G – Local

Diagram illustrating 800G and 400G transceivers used in local switch-to-switch applications.

Near End Optic (Left) Far End Optic (Right) Reach
OSFP-800G-2XDR4 (single-mode) OSFP-800G-2XDR4 (single-mode) 2 km
OSFP-800G-2PLR4 (single-mode) OSFP-800G-2PLR4 (single-mode) 10 km
QDD-800G-2XDR4 (single-mode) QDD-800G-2XDR4 (single-mode) 2 km
QDD-800G-2PLR4 (single-mode) QDD-800G-2PLR4 (single-mode) 10 km
OSFP-800G-2FR4 (single-mode) OSFP-400G-FR4 (single-mode) 2 km
OSFP-800G-2LR4 (single-mode) OSFP-400G-FR4 (single-mode) 10 km
QDD-800G-2FR4 (single-mode) QDD-400G-FR4 (single-mode) 2 km
QDD-800G-2LR4 (single-mode) QDD-400G-FR4 (single-mode) 10 km

Annex 1: EDGE8® HD Housings

EDGE8® HD housings mount in 19-inch racks or cabinets and provide industry-leading ultra-high-density connectivity when combined with EDGE8 modules, panels, harnesses, trunks, and jumpers.

Part Number (Global) Maximum Number of Modules or Panels Maximum Fiber Density Height
EDGE8-01U-SP 18 LC: 144 fibers
MTP®: 576 fibers
1U
EDGE8-02U 36 LC: 288 fibers
MTP: 1,152 fibers
2U
EDGE8-04U 72 LC: 576 fibers
MTP: 2,304 fibers
4U

Annex 2: Polarity Drawings

Polarity drawings, often referred to as fiber optic polarity diagrams, are essential when designing and implementing data center links using fiber optic cabling. They play a crucial role in ensuring proper connectivity, signal integrity, and compatibility between different network components. This section covers specific polarity drawings applicable to the previously described scenarios.

(Visual diagrams illustrating polarity for various scenarios are presented in this section.)

Models: QDD-400G-SR8, OSFP-400G-DR4, OSFP-400G-FR4, QDD-400G-SR8 Data Center Transceivers and Cables, Data Center Transceivers and Cables, Center Transceivers and Cables, Transceivers and Cables, Cables

File Info : application/pdf, 37 Pages, 11.60MB

PDF preview unavailable. Download the PDF instead.

v1

References

Adobe PDF Library 17.0

Related Documents

Preview Corning EDGE8 MTP to LC Duplex Module 8F, 50 µm Multimode (OM4) - Product Specification
Detailed product specification for the Corning EDGE8 MTP to LC Duplex Module 8F, 50 µm multimode (OM4), including features, specifications, and ordering information.
Preview Corning ALTOS® 144 F LEAF® Fiber Cable - Product Specification
Detailed product specification for Corning ALTOS® Loose Tube, Gel-Free, All-Dielectric Cable with FastAccess® Technology 144 F, LEAF® fiber, Single-mode (OS2). Includes features, benefits, specifications, and dimensions.
Preview Corning Closet Connector Housing (CCH) Panel, LC Adapters Duplex, 12 F, 50 µm Multimode (OM3/4), Shuttered
Corning Closet Connector Housing (CCH) panels provide interconnect or cross-connect capability in a housing at main cross-connects, intermediate cross-connects, telecommunication rooms, or work areas. This specific panel features 12 LC duplex adapters for 50 µm multimode OM3/4 fiber, with shuttered ports for dust protection. It is designed for data center and enterprise network applications.
Preview Corning Closet Connector Housings (CCH): Features, Specifications, and Accessories
Comprehensive guide to Corning's LANscape® Pretium® Closet Connector Housings (CCH). Details features, specifications, ordering information, splice cassettes, termination cassettes, pigtailed cassettes, and various accessories for fiber optic connectivity.
Preview Corning LSZH™™ Loose Tube, Gel-Free, Single-Jacket Cable 36 F, Single-mode (OS2) Product Specification
Detailed product specification for the Corning LSZH™™ Loose Tube, Gel-Free, Single-Jacket Cable 36 F, Single-mode (OS2). Features include low-smoke, zero-halogen sheath, superior performance, and suitability for indoor/outdoor applications. Includes comprehensive technical specifications on cable design, environmental conditions, mechanical strength, and optical characteristics.
Preview Corning OptiSheath Multiport Terminal MF12-0077E4EU4SA00F Specifications
Detailed specifications for the Corning OptiSheath MF12 Multiport Terminal, Stubbed, ALTOS Cable Single-mode (OS2), 144 F, 1000 ft. Includes features, benefits, technical specifications, dimensions, and ordering information.
Preview Corning Optical Communications User Manual for dMRU
This user manual provides detailed instructions for the installation, configuration, and operation of the Corning dMRU (Digital High Power Amplifier Module). It covers fan module installation, rack and wall mounting, cable connections, grounding, antenna connection, verifying normal operation, and GUI configuration.
Preview Corning Industrial LSZH Tray-Rated Cable 144 F Single-mode OS2
Corning LSZH industrial fiber optic cables are designed for harsh environments, offering low-smoke, zero-halogen sheath and superior performance. This document details the specifications, design, and optical characteristics of the 144 F Single-mode (OS2) cable.