FUJITSU

SPLIT TYPE AIR CONDITIONER CASSETTE TYPE (50Hz)

SERVICE MANUAL

Indoor units: AUYG30LRLE, AUYG36LRLE

Outdoor units: AOYG30LETL, AOYG36LETL

Contents

  • SPECIFICATIONS

  • DIMENSIONS

  • REFRIGERANT SYSTEM DIAGRAM

  • CIRCUIT DIAGRAM

  • INDOOR PCB CIRCUIT DIAGRAM

  • OUTDOOR PCB CIRCUIT DIAGRAM

  • ERROR DETECTION

  • PARTS (DECORATION PANEL)

  • PARTS (INDOOR UNIT)

  • PARTS (OUTDOOR UNIT)

  • ACCESSORIES

SPECIFICATIONS

ELECTRICAL DATA

INDOOR UNIT OUTDOOR UNIT
TYPE Cooling & Heating
INDOOR UNIT AUYG30LRLE AUYG36LRLE
DECORATION PANEL UTG-UGYA-W
OUTDOOR UNIT AOYG30LETL AOYG36LETL
COOLING CAPACITY 8.5 kW 10.0 kW
HEATING CAPACITY 10.0 kW 11.2 kW
POWER SOURCE 230 V, 50 Hz
RUNNING CURRENT Cooling 11.6 A 13.7 A
Heating 12.2 A 13.3 A
INPUT WATTS Cooling 2.65 kW 3.12 kW
Heating 2.77 kW 3.02 kW
E.E.R Cooling 3.21 kW/kW 3.21 kW/kW
COP Heating 3.61 kW/kW 3.71 kW/kW
MOISTURE REMOVAL 2.5 L/hr 3.5 L/hr
AIRCIRCULATION INDOOR 1,600 m³/hr 1,800 m³/hr
AIRCIRCULATION OUTDOOR 3,600 m³/hr 3,800 m³/hr
MAXIMUM CURRENT Cooling 17.0 A 18.5 A
Heating 17.0 A 20.0 A
* The above data are rating at 230 V.

FAN SPEED

Discrimination INDOOR UNIT OUTDOOR UNIT
INDOOR UNIT High speed 570 r.p.m. 640 r.p.m.
Medium speed 510 r.p.m. 510 r.p.m.
Low speed 470 r.p.m. 470 r.p.m.
Quiet 420 r.p.m. 420 r.p.m.
OUTDOOR UNIT Speed 850 r.p.m. 900 r.p.m.

COMPRESSOR AND REFRIGERANT

COMPRESSOR TYPE Hermetic type, Inverter, 6 poles, DC motor, Twin Rotary
DISCRIMINATION N-TF30ND1A
WEIGHT (with oil) 15.3 kg
PRECHARGED REFRIGERANT 2,100 g
REFRIGERANT TYPE R410A
MAX PIPE LENGTH 50 m
MAX PIPE HEIGHT 30 m
FULL CHARGE Pipe length 20 m 2,100 g
30 m 2,500 g
40 m 2,900 g
ADDITIONAL CHARGE 50 m 3,300 g
40 g/m

DIMENSIONS

INDOOR UNIT H x W x D 288 x 840 x 840 mm
DECORATION PANEL H x W x D 50 x 950 x 950 mm
OUTDOOR UNIT H x W x D 830 x 900 x 330 mm

WEIGHT

INDOOR UNIT Net / Shipping 26 kg / 31 kg
DECORATION PANEL Net / Shipping 5.5 kg / 8.5 kg
OUTDOOR UNIT Net / Shipping 61 kg / 68 kg

NOISE LEVEL

INDOOR UNIT OUTDOOR UNIT
INDOOR UNIT High speed 40 dB 43 dB
Medium speed 38 dB 38 dB
Low speed 36 dB 36 dB
Quiet 32 dB 32 dB
OUTDOOR UNIT Cooling 53 dB 54 dB
Heating 55 dB 55 dB

DIMENSIONS

Diagrams illustrating the dimensions of the Indoor Unit, Decoration Panel, and Outdoor Unit are provided, with measurements in millimeters (mm). The diagrams show front, side, bottom, and top views, including details like drain pipe diameter (Inside: 20 mm, Outside: 26 mm) and hanging bolt positions.

REFRIGERANT SYSTEM DIAGRAM

The Refrigerant System Diagram illustrates the flow of refrigerant between the Outdoor Unit (containing the Condenser, Compressor, 4-way Valve, Accumulator, Strainers, and Expansion Valve) and the Indoor Unit (containing the Evaporator). It indicates refrigerant direction for Cooling and Heating modes, and shows the refrigerant pipes with their diameters (15.88mm or 5/8" and 9.52mm or 3/8"). Charging valves and a pressure check valve are also depicted.

CIRCUIT DIAGRAM

Detailed circuit diagrams are provided for both the Indoor Unit and the Outdoor Unit. These diagrams show the connections between various components such as PCBs (Main PCB, Power Supply PCB, Indicator PCB, Transistor PCB, Capacitor PCB, Filter PCB), sensors (thermistors), motors (fan motor, drain pump motor), valves (4-way valve, expansion valve), switches (float switch, high pressure switch), and power sources. Specific wire colors and connector labels are indicated.

ERROR DETECTION

This section details error detection methods for the Indoor Unit and Wired Remote Control. It provides tables listing error codes, indicated by blinking lamps on the indoor unit (Operation Lamp, Timer Lamp, Economy Lamp) or displays on the wired remote control. Each error code is associated with a specific description, such as 'Serial communication error', 'Indoor unit capacity error', 'Compressor temp. sensor error', 'Outdoor unit fan motor error', and '4-way valve error'.

SPECIAL INSTALLATION SETTING - PUMP DOWN

Instructions are provided for the 'PUMP DOWN' operation, which is a refrigerant collecting process necessary when moving the indoor or outdoor unit. The procedure involves pressing a push-button switch on the circuit board, which initiates the operation. The system indicates the start of PUMP DOWN via an LED. The operation typically lasts for about 1 minute, after which the compressor stops automatically. The 2-way and 3-way valves should be closed immediately, followed by turning off the power. A DANGER warning highlights that the choke coil generates high voltages and should not be touched.

PARTS

Detailed parts lists and exploded view diagrams are provided for the Decoration Panel, Indoor Unit, and Outdoor Unit. Each part is identified by a reference number, description, and a specific part number. These sections cover components like grilles, filters, brackets, panels, flaps, motors, fans, PCBs, thermistors, valves, compressors, and more.

Decoration Panel Parts

Ref. Description Part number
1Intake Grille Assy9378565012
2Intake Grille9378249011
3Long Life Filter9378252011
4Filter Guide9378253018
5Hook Bracket9378435018
6Grille Hook9378250017
11Decoration Panel9378242012
12Corner Panel A9378243019
13Corner Panel (FUJITSU)9378243026
14Panel Cover A9378261013
15Panel Cover B9378262010
16Drain Cover9378359017
21Flap9378254015
22Poli Slider9375541019
23Joint C9378357013
24Step motor9900467005
25Gear A9378256019
26Motor Holder9378255012
27Joint A9378258013
28Joint B9378259010
29Gear B9378257016
30Joint Shaft9378260016
31Flap Spring9378356016

Indoor Unit Parts

Ref. Description Part number
1Bell Mouth9378227019
2Terminal Wire Cover9378548015
3Hook R9378197015
4Hook L9378198012
11Float Switch Sub Assy9378593015
12Sensor Holder9378329010
13Float Switch9900465018
14Drain Pump Sub Assy9378592018
15Pump Assy9900464011
16Drain Pump Holder B9375518011
17Pump Rubber9378426016
18Drain Hose9378212015
19Drain Port9378213012
20Drain Pan Assy9378207011
-Drain Hose9379665001
-Hose Band9379757010
21Evaporator Total Assy9378580015
22Top Plate Assy9378395015
23Cabinet A Sub Assy9378594012
24Cabinet B Sub Assy9378595019
25Cabinet C Sub Assy9378570016
26Turbo Fan Assy9378228016
27Turbo Fan Washer9378394018
28Motor, DC Brushless9603373009, 9602716005
29Rubber (Motor)9378223011
31Power Supply PCB9707398366
32Main PCB (30)9709245231
32Main PCB (36)9709245248
33Terminal 3P9306489045
34Terminal 3P9703345012
35Thermistor Holder A9378206014
36Thermistor Holder B9378330016
37Room Thermistor9900445010
38Pipe Thermistor9900470012
39Remote Control9318593013

Outdoor Unit Parts

Ref. Description Part number
1Protective Net9375381011
2Thermo Holder9375211011
3Top Panel Sub Assy9374417032
4Front Panel Sub Assy9374414079
5Service Panel Sub Assy9374415052
6Emblem Rear9351355005
7Right Panel Sub Assy9374416127
8Valve Cover9374174010
9Fan Motor9602843015
10Propeller Fan Assy9366378020, 9366378037
11Base Assy9374166138
12Drain Assy9303029015
13Drain Cap313166024302
21Transistor PCB (IPM) (30)9707669077
21Transistor PCB (IPM) (36)9707669060
22ACTPM9707592016
23Choke Coil (30)9900390020
23Choke Coil (36)9900223014
24Capacitor PCB (30)9707257052
24Capacitor PCB (36)9707257045
25Main PCB (30)9707667868
25Main PCB (36)9707667875
26Filter PCB (30)9707128215
26Filter PCB (36)9707128208
27Terminal9900203023
28Heat Sink9378530010
29Thermistor (36 only)9704265012
30Discharge Thermitor9900461003
31Thermistor (Outdoor)9900463007
32Compressor Thermistor9900466015
33Heat Exchanger Thermistor9900462000
413-way Valve Assy9377958013
423-way Valve Assy9377959010
43Compressor9810135001
44Accumulator9385005006
45Solenoid9970055034
46Expansion Valve Coil9900057039
47Wire w/Terminal for comp.9707837032
51Expansion Valve Assy9370947144
52Condenser A Sub Assy9374420308
53Condenser A Assy9374433056
54Inlet Pipe (Cond) A Assy9373461067
55Outlet Pipe (Cond) A Assy9374266104
56Strainer Assy9372524015
574-way Valve Assy9374425198
584-way Valve9900164010
59Check Joint Assy9372802038
60Muffler9372369050
61Pressure Switch9900186012

ACCESSORIES

Lists of accessories for the Indoor Unit, Decoration Panel, and Outdoor Unit are provided, including quantities and applications.

Indoor Unit Accessories

Name and Shape Qty Application
Template (Carton top)1For installing indoor unit
Washer8For installing indoor unit
Coupler heat insulation2For indoor side pipe joint
Insulation1For installing drain pipe
Drain hose assy1For installing drain pipe
Hose band assy1For installing drain pipe
Drain pipe insulation1For installing drain pipe
Binder (Large)3For electrical wiring
Binder (Small)1For electrical wiring
Wired remote control1
Remote Control Cord1For connecting remote control
Tapping screw ($4 x 16)2For installing remote control

Decoration Panel Accessories

Name and Shape Qty Application
Hexagon Screw4For mounting decoration panel
Screw4For installing grille holding wire
Strap4For installing corner panel
Grille holding wire2For installing intake grille

Outdoor Unit Accessories

Name and Shape Qty Application Part number
Drain pipe1For drain piping work9303029015
Drain cap2313166024302

OPTIONAL PARTS

This section lists optional parts such as different types of remote controls (Wired, High functional wired, Simple, Wireless remote control kit), an air outlet shutter plate, wide panels, panel spacers, insulation kits, external connect sets, and fresh air intake kits, along with their applications and model numbers.

Models: AUYG36LRLE, AOYG30LETL, AOYG36LETL, AUYG30LRLE Ceiling Cassette Air Conditioner, AUYG30LRLE, Ceiling Cassette Air Conditioner, Cassette Air Conditioner, Air Conditioner, Air Conditioner AUYG30LRLE

PDF preview unavailable. Download the PDF instead.

auyg30lrle-aoyg30letl-auyg36lrle-aoyg36letl-service-manual compr Adobe Illustrator 10.0 iLovePDF

Related Documents

Preview Fujitsu Split Type Room Air Conditioner Service Manual ASYG09KXCA, ASYG12KXCA
Comprehensive service manual for Fujitsu split type room air conditioners, models ASYG09KXCA and ASYG12KXCA. Includes specifications, diagrams, error detection, parts lists, and accessories for both indoor and outdoor units.
Preview Fujitsu Split Type Room Air Conditioner Service Manual
Service manual for Fujitsu Split Type Room Air Conditioner, Wall Mounted Type, covering models ASU9RLF, ASU12RLF, ASU15RLS and AOU9RLFW, AOU12RLFW, AOU15RLS. Includes specifications, dimensions, refrigerant system diagram, circuit diagrams, error detection, parts lists, and accessories.
Preview Fujitsu ASYA18LEC / AOYR18LEC Split Type Room Air Conditioner Service Manual
This service manual provides detailed specifications, diagrams, error codes, and parts lists for the Fujitsu ASYA18LEC indoor unit and AOYR18LEC outdoor unit, split-type room air conditioners.
Preview Fujitsu Split Type Room Air Conditioner Wall Mounted Type Service Manual
This service manual provides detailed specifications, diagrams, error contents, parts lists, and accessories for Fujitsu Split Type Room Air Conditioners, Wall Mounted Type, including models ASYA07LGC, ASYA09LGC, ASYA12LGC, AOYR07LGC, AOYR09LGC, and AOYR12LGC.
Preview Fujitsu Split Type Room Air Conditioner Service Manual - ASY9USCCW, AOY9USCC, ASY9USCCW, AOY9UFCC, ASY12USCCW, AOY12USCC
This service manual provides detailed specifications, diagrams, error codes, disassembly instructions, and parts lists for Fujitsu Split Type Room Air Conditioners, Wall Mounted models ASY9USCCW, AOY9USCC, ASY9USCCW, AOY9UFCC, ASY12USCCW, and AOY12USCC.
Preview Fujitsu Split Type Room Air Conditioner Service Manual - ABY45RBA3W, AOY45RPA3L
Comprehensive service manual for Fujitsu Split Type Room Air Conditioner, Ceiling type (50Hz), models ABY45RBA3W and AOY45RPA3L. Covers specifications, diagrams, error codes, disassembly procedures, parts lists, and standard accessories.
Preview Fujitsu ASYG07LMCE/ASYG09LMCE Wall Mounted Air Conditioner Service Manual
Comprehensive service manual for Fujitsu split type wall-mounted air conditioners, models ASYG07LMCE and ASYG09LMCE. Includes specifications, dimensions, refrigerant system diagram, circuit diagrams, error detection codes, and detailed parts lists for both indoor and outdoor units.
Preview Fujitsu ASYG14LMCA / AOYG14LMCA Split Type Room Air Conditioner Service Manual
Comprehensive service manual for the Fujitsu ASYG14LMCA and AOYG14LMCA split type wall-mounted room air conditioners, covering specifications, diagrams, error detection, and parts.