Fujitsu Split Type Room Air Conditioner Service Manual

Wall Mounted Type

Models: ASYG09KXCA, ASYG12KXCA (Indoor Unit) / AOYG09KXCA, AOYG12KXCA (Outdoor Unit)

Contents

Specifications

Electrical Data

ASYG09KXCAASYG12KXCA
Power SupplySingle phase, 230 V, 50 Hz
Capacity2.50 kW3.40 kW
Power Consumption0.460 kW0.670 kW
EER5.45 kW/kW5.09 kW/kW
Operating Current2.1 A3.0 A
Max Operating Current8.5 A9.0 A
Dehumidification1.1 L/h1.2 L/h
Capacity3.60 kW5.00 kW
Power Consumption0.630 kW1.020 kW
COP5.72 kW/kW4.90 kW/kW
Operating Current2.8 A4.5 A
Max Operating Current14.0 A16.0 A

Fan Motor and Revolution

UnitDiscriminationSpeed (rpm)
Indoor Unit CoolingHigh1,310
Medium1,160
Low1,050
Quiet780
Indoor Unit HeatingHigh1,490
Medium1,300
Low1,130
Quiet830
Outdoor Unit CoolingMFE-80DVL660
Outdoor Unit HeatingMFE-80DVL610

Air Circulation

UnitSpeedAirflow (m³/h)
Indoor UnitHigh670
Medium590
Low520
Quiet350
Outdoor Unit Cooling1,975 / 2,230
Outdoor Unit Heating1,820 / 1,975

Noise Level

UnitModeNoise Level (dB)
Indoor Unit CoolingHigh46
Medium42
Low38
Quiet28
Indoor Unit HeatingHigh48
Medium43
Low39
Quiet30
Outdoor Unit CoolingHigh40
Low44
Outdoor Unit HeatingHigh41
Low43

Compressor and Refrigerant

TypeHermetic type, 6 pole, 2-cylinder rotary, DC brushless motor
Discrimination9RD138ZCA21
Weight (with oil)10.0 kg
Refrigerant TypeR32
Precharged Refrigerant1,300 g
Maximum Piping Length15 m
Maximum Piping Height Difference10 m

Dimensions

Indoor Unit

Dimensions (H x W x D): 293 mm x 786 mm x 378 mm

Drain hose length: 600 mm

Drain hose diameter: Inside 12 mm, Outside 16 mm

Outdoor Unit

Dimensions (H x W x D): 704 mm x 820 mm x 315 mm

Refrigerant System Diagram

The diagram illustrates the flow of refrigerant through the system, including the compressor, accumulators, mufflers, valves (3-way, 4-way, 2-way), distributor, and heat exchangers (indoor and outdoor units). It indicates cooling flow (solid arrow) and heating flow (dashed arrow).

Refrigerant pipe diameters: Liquid: 1/4" (6.35 mm), Gas: 3/8" (9.52 mm)

Circuit Diagram

The circuit diagram details the electrical connections within the indoor and outdoor units. It shows connections for power supply, fan motors, louvers, diffusers, sensors (thermistor, pyroelectric), switches, wireless LAN adapter, speaker, and the main PCB.

PCB Circuit Diagram

This section provides detailed diagrams of the Printed Circuit Boards (PCBs) used in the control unit, filter, wireless LAN adapter, receiver, air cleaner, switch, and power supply. It includes terminal assignments and wiring information.

Error Detection

This section lists error codes displayed on the unit or remote controller, along with their descriptions. Errors are categorized by the combination of indicator lamps (Operation, Timer, Economy) or by error codes displayed on a wired remote controller. Common errors include communication errors, sensor errors, and motor errors.

Error Display (Lamps)Error CodeDescription
(1) (1) ◇ 11Serial communication error
(1) (2) ◇ 12Wired remote controller communication error
(1) (5) ◇ 15Check run unfinished
(1) (6) ◇ 16Peripheral unit transmission PCB connection error
(1) (8) ◇ 18External communication error
(2) (1) ◇ 21Unit number or Refrigerant circuit address setting error [Simultaneous Multi]
(2) (2) ◇ 22Indoor unit capacity error
(2) (3) ◇ 23Combination error
(2) (4) ◇ 24Connection unit number error (indoor slave unit) [Simultaneous Multi]
(2) (6) ◇ 26Address setting error in wired remote controller system [Flexible Multi]
(2) (7) ◇ 27Master unit, slave unit set-up error [Simultaneous Multi]
(3) (2) ◇ 32Indoor unit PCB model information error
(3) (5) ◇ 35Manual auto switch error
(4) (1) ◇ 41Room temp. sensor error
(4) (2) ◇ 42Indoor unit Heat Ex. Middle temp. sensor error
(5) (1) ◇ 51Indoor unit fan motor 1 error detection (Main fan)
(5) (3) ◇ 53Drain pump error
(5) (4) ◇ 54Electric air cleaner reverse VDD error
(5) (5) ◇ 55Filter set error
(5) (7) ◇ 57Damper error
(5) (8) ◇ 58Intake grille error
(5) (9) ◇ 59Indoor unit fan motor 2 error (Left side fan) [Flexible Multi]
(5) (10) ◇ SAIndoor unit fan motor 3 error (Right side fan) [Flexible Multi]
(6) (2) ◇ 62Outdoor unit main PCB model information error or communication error
(6) (3) ◇ 63Inverter error
(6) (4) ◇ 64Active filter error, PFC circuit error
(6) (5) ◇ 65Trip terminal L error
(6) (10) ◇ 6ADisplay PCB microcomputers communication error
(7) (1) ◇ 71Discharge temp. sensor error
(7) (2) ◇ 72Compressor temp. sensor error
(7) (3) ◇ 73Outdoor unit Heat Ex. liquid temp. sensor error
(7) (4) ◇ 74Outdoor temp. sensor error
(7) (5) ◇ 75Suction Gas temp. sensor error
(7) (6) ◇ 762-way valve temp. sensor error / 3-way valve temp. sensor error
(7) (7) ◇ 77Heat sink temp. sensor error
(8) (2) ◇ 82Trip detection
(8) (3) ◇ 83Compressor rotor position error
(8) (4) ◇ 84Current sensor error
(8) (6) ◇ 86Discharge pressure sensor error / Suction pressure sensor error / High pressure switch error
(9) (4) ◇ 94Outdoor unit fan motor error
(9) (5) ◇ 954-way valve error
(9) (7) ◇ 97Compressor error
(9) (9) ◇ 99Branch boxes error
(10) (1) ◇ A1Discharge temp. error
(10) (3) ◇ A3Compressor temp. error
(10) (4) ◇ A4High pressure error
(10) (5) ◇ A5Low pressure error
(13) (2) ◇ 12Branch boxes error

Parts (Indoor Unit)

This section lists the part numbers for various components of the indoor unit, including the remote control, wireless LAN control, bracket panel, intake grille, diffuser, louver, wire cover, air filters, dust boxes, air cleaner cartridge, power supply, main PCBs, filter PCB, thermopiles, receiver, indicator, sensors, switches, fan motors, crossflow fans, and casing components.

Parts (Outdoor Unit)

This section lists the part numbers for various components of the outdoor unit, including protective nets, thermistor holders, top panels, front panels, emblems, cabinets, switch covers, drain assemblies, propeller fans, fan motors, terminals, heatsinks, PCB holders, main PCBs, outdoor thermistors, thermistor assemblies, condenser assemblies, expansion valve coils, pulse motor valve sub assemblies, 2-way valve assemblies, compressor assemblies, solenoids, and 4-way valve assemblies.

Accessories

Indoor Unit

Name and ShapeQ'tyName and ShapeQ'ty
Remote control1Tapping screws (Large)11
Remote control holder1Tapping screws (Small)2
Wall hook bracket1Battery2
Cloth tape1Wireless LAN adapter with cable (with attached wireless LAN label*)1

* This product has a wireless LAN adapter as accessory. Be sure to keep the wireless LAN label attached to the adapter by writing the details down or pasting it on the list in the last section of the setting manual for wireless LAN adapter.

Outdoor Unit

Name and ShapeQ'ty
Drain assy1
Models: ASYG09KXCA, AOYG09KXCA, ASYG12KXCA, AOYG12KXCA, ASYG09KXCA Split Type Room Air Conditioner, ASYG09KXCA, Split Type Room Air Conditioner, Room Air Conditioner, Air Conditioner, Conditioner

File Info : application/pdf, 24 Pages, 5.77MB

PDF preview unavailable. Download the PDF instead.

asyg09kxca-aoyg09kxca-asyg12kxca-aoyg12kxca-service-manual-fujitsu-general compr PDF reDirect v2 iLovePDF

Related Documents

PreviewFujitsu Split Type Room Air Conditioner Wall Mounted Type Service Manual
This service manual provides detailed specifications, diagrams, error contents, parts lists, and accessories for Fujitsu Split Type Room Air Conditioners, Wall Mounted Type, including models ASYA07LGC, ASYA09LGC, ASYA12LGC, AOYR07LGC, AOYR09LGC, and AOYR12LGC.
PreviewFujitsu Inverter Split Type Air Conditioner Service Manual
This service manual provides detailed specifications, diagrams, error codes, and parts lists for Fujitsu Inverter Split Type Air Conditioners, Duct Type, including models ARYF12LALU, ARYF14LALU, ARYF18LALU, AOYA12LACL, AOYA12LALL, AOYB12LACL, AOYB12LALL, AOYA14LACL, AOYA14LALL, AOYB14LACL, AOYB14LALL, AOYA18LACL, AOYA18LALL, AOYB18LACL, AOYB18LALL, ARYF18LBLU, AOYA18LALL, and AOYB18LALL.
PreviewFujitsu Split Type Room Air Conditioner Service Manual
Comprehensive service manual for Fujitsu split type room air conditioners, covering models ASY18ABAJ, ASY18RBAJ, ASY24ABAJ, ASY24RBAJ, and ASY30RBAJ, along with their corresponding outdoor units.
PreviewFujitsu Split Type Room Air Conditioner Service Manual
Comprehensive service manual for Fujitsu split type wall-mounted room air conditioners, models ASYG07LMCA, ASYG09LMCA, and ASYG12LMCA. Includes specifications, dimensions, circuit diagrams, error detection, and parts lists for both indoor and outdoor units.
PreviewFujitsu ASYA18LEC / AOYR18LEC Split Type Room Air Conditioner Service Manual
This service manual provides detailed specifications, diagrams, error codes, and parts lists for the Fujitsu ASYA18LEC indoor unit and AOYR18LEC outdoor unit, split-type room air conditioners.
PreviewFujitsu Split Type Room Air Conditioner Service Manual - ASY9USCCW, AOY9USCC, ASY9USCCW, AOY9UFCC, ASY12USCCW, AOY12USCC
This service manual provides detailed specifications, diagrams, error codes, disassembly instructions, and parts lists for Fujitsu Split Type Room Air Conditioners, Wall Mounted models ASY9USCCW, AOY9USCC, ASY9USCCW, AOY9UFCC, ASY12USCCW, and AOY12USCC.
PreviewFujitsu ASYG14LMCA / AOYG14LMCA Split Type Room Air Conditioner Service Manual
Comprehensive service manual for the Fujitsu ASYG14LMCA and AOYG14LMCA split type wall-mounted room air conditioners, covering specifications, diagrams, error detection, and parts.
PreviewFujitsu Split Type Room Air Conditioner Service Manual
Comprehensive service manual for Fujitsu split type room air conditioners, covering models ASYA14LCC, AOYR14LCC, ASYA14LCL, ASYA18LCC, AOYR18LCC, and AOYR18LCL. Includes specifications, diagrams, error codes, and parts lists.