Solplanet Three Phase Hybrid Inverter

Models: ASW05kH/06kH/08kH/10kH/12kH-T2, ASW05kH/06kH/08kH/10kH/12kH-T2-O, ASW08kH/10kH/12kH-T3, ASW08kH/10kH/12kH-T3-O

Quick Installation Guide

1 GENERAL INFORMATION

This quick installation guide does not replace the user manual. Its contents may be updated or revised due to product development and are subject to change without notice. The latest version of this document and the full manual for installation, commissioning, configuration, and decommissioning are available in PDF format at www.solplanet.net.

2 SAFETY

2.1 Intended use

The product is a transformerless hybrid inverter with 2 or 3 MPP trackers and a battery connection. It feeds the DC current from the PV array into the connected battery or converts it to grid-compliant three-phase current for the utility grid. It can also convert DC current from the battery into grid-compliant three-phase current. The product features a backup function to supply selected circuits with power from the battery or PV system during a grid fault.

The product is intended for indoor and outdoor applications. It must only be connected with PV modules of protection class II (in accordance with IEC 61730, application class A). Do not connect any other energy sources to the product.

The inverter does not have an integrated transformer, thus lacking galvanic isolation. It must not be operated with PV modules that require functional grounding of either the positive or negative PV conductors, as this can cause irreparable damage. PV modules with frames requiring protective earthing are permissible.

All components must remain within their permitted operating ranges and installation requirements at all times. Use the product only as per the user manual and applicable local standards and directives. Any other application may cause personal injury or property damage.

The product must be operated with an intrinsically safe lithium-ion battery approved by AISWEI, with its entire voltage range within the product's permissible input voltage range. It must only be used in countries approved by AISWEI and the grid operator. The type label must remain permanently attached and legible.

This document does not replace any regional, state, provincial, federal, or national laws, regulations, or standards applicable to installation, electrical safety, and product use.

2.2 Important safety instructions

The product is designed and tested according to international safety requirements. Despite careful construction, residual risks exist with all electrical devices. To prevent personal injury and property damage, and to ensure long-term operation, read this section carefully and observe all safety information.

DANGER: Danger to life due to high voltages of the PV array or the battery!

The DC cables connected to the battery or PV array may be live. Touching DC conductors or live components can cause lethal electric shocks. Disconnecting DC connectors under load may cause an electric arc, leading to electric shock and burns.

DANGER: Danger to life due to electric shock when touching live components in backup mode!

Even with the AC breaker and PV switch disconnected, system parts may remain live when the battery is in backup mode.

DANGER: Danger to life due to fire or explosion when batteries are fully discharged!

Incorrect charging of fully discharged batteries can cause fire, resulting in death or serious injury.

DANGER: Danger to life due to burns caused by electric arcs through short-circuit currents!

Short-circuit currents in the battery can cause heat accumulation and electric arcs if the battery is short-circuited or wrongly installed, leading to lethal burn injuries.

DANGER: Danger to life due to electric shock when touching live system components in case of a ground fault!

If a ground fault occurs, system parts may remain live. Touching live parts and cables can result in death or lethal injuries.

WARNING: Danger to life due to electric shock from destruction of the measuring device due to overvoltage!

Overvoltage can damage a measuring device, causing voltage to be present in its enclosure. Touching a live enclosure can result in death or lethal injuries.

CAUTION: Risk of burns due to high temperature.

Some enclosure parts can become hot during operation.

CAUTION: Risk of injury due to weight of product.

Injuries may result if the product is lifted incorrectly or dropped during transport or mounting.

2.3 Symbols on the label

Symbol: ⚠️ (Exclamation mark in triangle)

Description: Beware of a danger zone! This symbol indicates that the product must be additionally grounded if additional grounding or equipotential bonding is required at the installation site.

Symbol: ⚡ (High voltage symbol)

Description: Beware of high voltage and operating current! The inverter operates at high voltage and current. Work on the inverter must only be carried out by skilled and authorized electricians.

Symbol: ♨️ (Hot surface symbol)

Description: Beware of hot surfaces! The inverter can get hot during operation. Avoid contact during operation.

Symbol: ♻️ (WEEE symbol)

Description: WEEE designation. Do not dispose of the product with household waste; follow disposal regulations for electronic waste applicable at the installation site.

Symbol: CE (CE marking)

Description: CE marking. The product complies with the requirements of the applicable EU directives.

Symbol: TÜV (Certification mark)

Description: Certification mark. The product has been tested by TÜV and obtained the quality certification mark.

Symbol: RCM (Regulatory Compliance Mark)

Description: RCM (Regulatory Compliance Mark). The product complies with the requirements of the applicable Australian standards.

Symbol: ⚡ (Capacitor discharge symbol)

Description: Capacitor discharge. Danger to life due to high voltages in the inverter. Do not touch live parts for 10 minutes after disconnection from power sources.

Symbol: ℹ️ (Information symbol)

Description: Observe the documentation. Observe all documentation supplied with the product.

3 SYSTEM WIRING DIAGRAM

The document provides system wiring diagrams for two regions: Australia and Europe. These diagrams illustrate the connections between the inverter, battery, PV array, grid, and loads.

Australia Wiring Diagram

The diagram shows the Inverter connected to the Battery via a DC Breaker, and to the PV array. The Grid connection includes AC Breakers, CT COM, CT1, CT2, CT3, and a Main Meter with L1, L2, L3, N, PE terminals. The Load side includes a PE-N Link, PE-Bar, and RCDs feeding into Normal Loads and Backup Loads. A note specifies not to connect a particular terminal for Australian and New Zealand grid systems. An additional grounding screw hole is indicated at the lower right corner.

Europe Wiring Diagram

Similar to the Australian diagram, the European diagram shows the Inverter connected to the Battery (via DC Breaker) and PV array. The Grid connection features AC Breakers, CT COM, CT1, CT2, CT3, and a Main Meter with L1, L2, L3, N, PE terminals. The Load side includes PE-Bar and RCDs for Normal Loads and Backup Loads. The diagram also indicates an additional grounding screw hole at the lower right corner.

4 EU DECLARATION OF CONFORMITY

AISWEI Technology Co., Ltd. confirms that the products described in this document comply with the fundamental requirements and other relevant provisions of the EU directives:

The CE marking indicates compliance. The entire EU Declaration of Conformity can be found at www.solplanet.net.

5 OVERVIEW

The front panel of the inverter features several ports and indicators:

ObjectDescription
1Battery Port
2DC-switch (with ON/OFF indicators)
3PV Input (PV1, PV2, PV3)
4Ai-Dongle port
5Communication ports (RJ45-1 to RJ45-6, USB)
6AC connector
7EPS connector
8Additional grounding screw

6 SCOPE OF DELIVERY

The package includes the following items:

7 MOUNTING ENVIRONMENT

The inverter is designed for various environmental conditions. Key considerations include:

8 DIMENSIONS

The inverter dimensions are:

9 MOUNTING

Follow these steps for mounting the inverter:

  1. Step 1: Attach the wall bracket to the wall.
  2. Step 2: Drill holes using a 10 mm drill bit, maintaining a 90° angle. The drilling depth is approximately 70 mm.
  3. Step 3: Secure the bracket using appropriate screws and anchors, tightening them to 5 N·m.
  4. Step 4: Mount the inverter onto the bracket.
  5. Step 5: Ensure the inverter is securely attached to the bracket.
  6. Step 6: Slide the inverter onto the mounting bracket until it clicks into place.
  7. Step 7: Secure the inverter with M5 screws, tightening to 3 N·m.

10 SECOND PROTECTIVE GROUNDING

Follow these steps for second protective grounding:

  1. Step 1: Prepare the grounding cable. The length (L) should be E + (2-3) mm, where E is the distance between the grounding points.
  2. Step 2: Strip the ends of the grounding cable.
  3. Step 3: Crimp appropriate terminals onto the cable ends.
  4. Step 4: Connect the grounding cable to the grounding points.
  5. Step 5: Secure the grounding connection with M5 screws, tightening to 3 N·m.

11 AC CONNECTION

Follow these steps to connect the AC power:

  1. Step 1: Ensure the AC breaker is in the OFF position and locked (if applicable).
  2. Step 2: Prepare the AC cable. Strip the wires to the specified lengths (e.g., 12.5-17.5mm for conductors, 10mm for PE). Ensure conductors are 4mm² to 6mm². Identify U, V, W, N, and PE wires.
  3. Step 3: Insert the prepared wires into the AC connector terminals in the correct order (refer to markings on the connector).
  4. Step 4: Crimp the wires securely within the connector terminals.
  5. Step 5: Connect the AC connector to the inverter's AC port, ensuring correct pin assignment (L1, L2, L3, N, PE).
  6. Step 6: Push the connector until it clicks, indicating it is locked.
  7. Step 7: Connect the AC cable to the grid supply via an AC breaker.
  8. Step 8: Ensure the connection is secure.
  9. Step 9: Confirm the connection with an audible "click".
  10. Step 10: Verify the connection is properly made ("OK" indicator).

12 BACKUP LOAD CONNECTION

Follow these steps to connect the backup load:

  1. Step 1: Ensure the AC breaker for backup loads is in the OFF position and locked.
  2. Step 2: Prepare the backup load cable, similar to the AC connection, ensuring correct wire gauge (4mm² to 6mm²) and stripping lengths. Identify L1, L2, L3, N, and PE wires.
  3. Step 3: Insert the prepared wires into the backup load connector terminals in the correct order.
  4. Step 4: Crimp the wires securely within the connector terminals.
  5. Step 5: Connect the backup load connector to the inverter's backup load port, ensuring correct pin assignment (L1, L2, L3, N, PE).
  6. Step 6: Push the connector until it clicks, indicating it is locked.
  7. Step 7: Connect the backup load cable to the backup load distribution point.
  8. Step 8: Ensure the connection is secure.
  9. Step 9: Confirm the connection with an audible "click".
  10. Step 10: Verify the connection is properly made ("OK" indicator).

13 PV CONNECTION

The inverter supports two types of PV connectors:

TYPE 1 - Phoenix Contact

  1. Step 1: Prepare the PV cable. Ensure the wire gauge is 2.5-6mm² and the stripping length is approximately 12mm, with an outer diameter of 5-8mm.
  2. Step 2: Connect the PV cable to the connector, ensuring correct polarity (+/-) and a secure "click" sound. A 'X' symbol indicates an incorrect connection.
  3. Step 3: Mating the male and female connectors.
  4. Step 4: Connect the prepared PV connectors to the inverter's PV input ports.
  5. Step 5: Verify the connection is correct ("OK" indicator).

TYPE 2

  1. Step 1: Prepare the PV cable, ensuring wire gauge is 2.5-6mm² and stripping length is approximately 12mm, with an outer diameter of 5-8mm.
  2. Step 2: Assemble the connector components.
  3. Step 3: Insert the prepared wires into the connector terminals, ensuring correct polarity (+/-).
  4. Step 4: Crimp the wires securely and assemble the connector housing.
  5. Step 5: Connect the prepared PV connectors to the inverter's PV input ports.
  6. Step 6: Mating the male and female connectors.
  7. Step 7: Verify the connection is correct ("OK" indicator).

14 BATTERY CONNECTION

Follow these steps to connect the battery:

  1. Step 1: Identify the positive (+) and negative (-) battery terminals on the inverter.
  2. Step 2: Connect the battery cables to the corresponding terminals on the inverter, ensuring correct polarity.
  3. Step 3: Verify the connection is secure and correct ("OK" indicator).

15 COMMUNICATION SETUP

15.1 Communication connection

The inverter offers various communication interfaces:

RJ45 Port Pin Definitions:

ObjectDescriptionTerminal12345678
RJ45-3MonitorCOM2RS485ARS485BGNDXXXRS485ARS485B
RJ45-4BMSCOM5XGNDXCANAHCANALXRS485ARS485B

Terminal Block Pin Definitions:

ObjectDescriptionTerminal123456
Terminal-1DO1/DO24pinMultifunction Relay 1 BMultifunction Relay 1 AMultifunction Relay 2 BMultifunction Relay 2 A
Terminal-2/6pinSmart Meter RS485ASmart Meter RS485BPT100 Temperature Sensor PositivePT100 Temperature Sensor NegativeUFR Device PositiveUFR Device Negative
Terminal-3DI*4/DRM06pinRipple Control Receiver Device DI_4Ripple Control Receiver Device DI_3DRMS Device DI_2DRMS Device DI_1REF GEN/0COM LOAD/0 or GND
Terminal-4CT6pinCurrent Transformer 1 RedCurrent Transformer 1 BlackCurrent Transformer 2 RedCurrent Transformer 2 BlackCurrent Transformer 3 RedCurrent Transformer 3 Black

Current Transformer Connection:

Connect the current transformers (CTs) to the designated terminals on the inverter. The diagram shows three CTs connected to Terminal-4. The CTs should be placed around the grid conductors (U, V, W, N, PE), with the arrow pointing towards the inverter. Red and Black wires from the CTs connect to specific pins on Terminal-4.

15.3 Ai-Dongle connection

Follow these steps to connect the Ai-Dongle:

  1. Step 1: Assemble the Ai-Dongle components.
  2. Step 2: Connect the Ai-Dongle cable to the designated port on the inverter.
  3. Step 3: Ensure the cable is properly seated.
  4. Step 4: Connect the Ai-Dongle to the inverter's communication port.
  5. Step 5: Secure the connection.
  6. Step 6: Insert the Ai-Dongle into the port.
  7. Step 7: Verify correct insertion (check mark) and incorrect insertion (cross mark).
  8. Step 8: Confirm the connection is properly made ("OK" indicator).

16 CONTACT

For technical questions about Solplanet products, please contact the Service Department. Provide the following information for assistance:

Contact Information by Region:

Further information is available at: https://solplanet.net/contact-us

Models: ASW H-T2-T3-SERIE Three Phase Hybrid Inverter, ASW H-T2-T3-SERIE, Three Phase Hybrid Inverter, Phase Hybrid Inverter, Hybrid Inverter, Inverter

File Info : application/pdf, 24 Pages, 10.60MB

PDF preview unavailable. Download the PDF instead.

QG0049 ASW05-12KH-T2-T3 EN 540-300254-00 0323

References

Related Documents

Preview Solplanet Three Phase Hybrid Inverter Quick Installation Guide
A concise guide for the quick installation of Solplanet's three-phase hybrid inverters, covering safety, wiring, mounting, and connection procedures for models ASW05kH to ASW12kH (T2, T2-O, T3, T3-O).
Preview Solplanet EU Declaration of Conformity - ASW Series Inverters
Official EU Declaration of Conformity for Solplanet ASW Series hybrid inverters, confirming compliance with Radio Equipment Directive (RED) and relevant harmonized European standards for safety, electromagnetic compatibility, frequency range, and cybersecurity.
Preview Solplanet Three-Phase Hybrid Inverter User Manual
User manual for Solplanet's three-phase hybrid inverters (ASW05kH-12kH T2/T3 series). Covers installation, operation, safety, technical data, and troubleshooting for efficient solar and battery energy management.
Preview Solplanet Three Phase Hybrid Inverter User Manual
This user manual provides comprehensive instructions for the Solplanet three-phase hybrid inverter, covering installation, operation, troubleshooting, and maintenance for models ASW05kH/06kH/08kH/10kH/12kH-T2, ASW05kH/06kH/08kH/10kH/12kH-T2-O, ASW08kH/10kH/12kH-T3, and ASW08kH/10kH/12kH-T3-O.
Preview Solplanet ASW H-T2 Series: Three-Phase Hybrid Inverters (5-12 kW) Datasheet
Detailed technical specifications and features of the Solplanet ASW H-T2 Series three-phase hybrid inverters, ranging from 5 kW to 12 kW. Includes information on PV input, battery integration, AC output, safety, and general data.
Preview Solplanet ASW H-T3 Series Hybrid Inverters: 8-12 kW Technical Specifications
Detailed technical specifications for the Solplanet ASW H-T3 Series of three-phase hybrid inverters, covering models ASW08kH-T3, ASW10kH-T3, and ASW12kH-T3. Features include easy installation, safety, reliability, user-friendliness, and advanced technical data for PV input, battery input, AC output, and efficiency.
Preview Solplanet ASW Series Three Phase Hybrid Inverter User Manual
User manual for Solplanet ASW08KH-T1, ASW10KH-T1, ASW12KH-T1 three-phase hybrid inverters, covering installation, operation, safety, and troubleshooting for solar energy systems.
Preview Solplanet Three Phase Hybrid Inverter User Manual - ASW08KH-T1, ASW10KH-T1, ASW12KH-T1
Comprehensive user manual for Solplanet's three-phase hybrid inverters (models ASW08KH-T1, ASW10KH-T1, ASW12KH-T1), covering installation, operation, safety, and troubleshooting for solar energy systems.