Solplanet ASW H-T2 Series: Three-Phase Hybrid Inverters (5-12 kW)
Technical Datasheet
Key Features
Technical Datasheet
Parameter | ASW05kH-T2 | ASW06kH-T2 | ASW08kH-T2 | ASW10kH-T2 | ASW12kH-T2 |
---|---|---|---|---|---|
PV input | |||||
Max. PV array power | 7500 Wp | 9000 Wp | 12000 Wp | 15000 Wp | 18000 Wp |
Max. input voltage | 1100 V [5] | ||||
MPP voltage range / rated input voltage | 150 V to 950 V / 630 V | 200 V to 950 V / 630 V [3] | |||
Min. input voltage / start voltage | 60 V / 180 V | ||||
No. of independent MPPT trackers / strings per MPPT input | 2 / 1 | ||||
Max. input current / Max. power per MPP tracker | 20 A / 7500 W | 20 A / 9000 W | 20 A / 10000 W | 20 A / 10000 W | 20 A / 10000 W |
Max. short-circuit current per MPP tracker | 30 A | ||||
Battery input | |||||
Battery voltage range | 120 V to 600 V [5] | ||||
Max. charging / discharging power | 5000 W | 6000 W | 8000 W | 10000 W | 12000 W |
Max. charging current / Max. discharging current | 30A [5] | ||||
Battery type | LiFePO4 | ||||
AC input | |||||
Rated grid voltage | 3/N/PE, 220 V / 380 V; 230 V / 400 V; 240 V / 415 V | ||||
Rated grid frequency | 50 Hz / 60 Hz | ||||
Max. input power from grid | 10000 W | 12000 W | 16000 W | 20000 W | 24000 W |
Max. input current from grid | 14.5 A | 17.4 A | 23.2 A | 29.0 A | 34.8 A |
AC output | |||||
AC voltage range / Nominal AC voltage | 270 V to 480 V / 3/N/PE, 220 V / 380 V; 230 V / 400 V; 240 V / 415 V | ||||
Rated AC grid frequency | 50 Hz / 60 Hz | ||||
AC grid frequency range | 45 ~ 55 Hz / 55 ~ 65 Hz | ||||
Rated apparent power | 5000 VA | 6000 VA | 8000 VA | 10000 VA | 12000 VA |
Max. apparent power | 5000 VA | 6000 VA | 8000 VA | 10000 VA | 12000 VA |
Rated grid output current (@400 V) | 7.3 A | 8.7 A | 11.6 A | 14.5 A | 17.4 A |
Max. grid output current (@400 V) | 8.0 A | 9.6 A | 12.8 A | 16.0 A | 19.2 A |
Power factor at rated power / adjustable range | 1 / 0.8 [leading] to 0.8 [lagging] | ||||
Harmonics THDi (@Nominal power) | < 3 % (of nominal power) | ||||
EPS output | |||||
Nominal output voltage | 3/N/PE, 220 V / 380 V; 230 V / 400 V; 240 V / 415 V | ||||
Nominal output frequency | 50 Hz / 60 Hz | ||||
Rated apparent power | 5000 VA | 6000 VA | 8000 VA | 10000 VA | 12000 VA |
Rated current (@400 V) | 7.3 A | 8.7 A | 11.6 A | 14.5 A | 17.4 A |
Max. current (@400 V, continuous on-grid / off-grid) | 14.5 A / 7.3 A | 17.4 A / 8.7 A | 23.2 A / 11.6 A | 29.0 A / 14.5 A | 34.8 A / 17.4 A |
Max. power on each phase (@400 V, continuous on-grid / off-grid) | 3333 W / 1667 W | 4000 W / 2000 W | 5333 W / 2667 W | 6667 W / 3333 W | 8000 W / 4000 W |
Peak output apparent power (@400 V, continuous on-grid / off-grid up to 10s) | 10000 VA / 10000 VA | 12000 VA / 12000 VA | 16000 VA / 16000 VA | 20000 VA / 20000 VA | 24000 VA / 24000 VA |
Max. switch time | < 10 ms | ||||
Output THDv (@Linear load) | 2 % | ||||
Efficiency | |||||
MPPT efficiency | 99.9 % | ||||
Euro efficiency / Max. efficiency | 97.2 % / 98.0 % | 97.5 % / 98.2 % | 97.9 % / 98.4 % | ||
Safety protection | |||||
DC surge protection (Type II, according to EN/IEC 61643-11) | ● | ||||
Insulation resistance detection | ● | ||||
PV string input reverse polarity protection | ● | ||||
Battery input reverse polarity protection | ● | ||||
Ground fault monitoring | ● | ||||
Residual current monitoring unit | ● | ||||
AC short circuit protection | ● | ||||
Anti-islanding protection | ● | ||||
Arc fault circuit interrupter (AFCI) | ○ [2] | ||||
General data | |||||
Dimensions (W / H / D) | 545 / 465 / 205 mm | ||||
Weight | 24.5 kg | ||||
Operating temperature range | -25 °C … +60 °C | ||||
Cooling concept | Natural convection | ||||
Noise emission | < 35 dB | ||||
Degree of protection (as per IEC 60529) | IP66 | ||||
Max. relative humidity | 100 % | ||||
Max. operating altitude | 4000 m | ||||
Features | |||||
User interface | LED & App | ||||
BMS interface | CAN | ||||
Smart meter interface | RS485 | ||||
Communication interfaces | Dongle: WiFi (2.4 GHz) / LAN (100 Mbps) Inverter: RS485 (ModBus RTU), LAN (100 Mbps, Modbus TCP only) [4] | ||||
Digital output (dry contact) / No. of outputs | ● / 2 | ||||
Digital input (dry contact) / No. of inputs | ● / 4 | ||||
Integrated power control / export power control | ● / ● |
● standard features / ○ optional features / - not available
[1] Asymmetrical power output functionality released in August 2024, please confirm version with Solplanet's sales staff before purchase.
[2] AFCI functionality released in April 2025, please confirm version with Solplanet's sales staff before purchase.
[3] The latest optimised platform design supports MPP voltage range at 150V-950V, pending subsequent certificate updates.
[4] Modbus TCP functionality released in April 2025, please confirm version with Solplanet's sales staff before purchase.
[5] When connecting to Solplanet‘s high voltage batteries (with only 5 kWh, i.e. two modules), limitations as below apply:
1. The maximum voltage of PV shall not exceed 750V
2. The battery voltage range is reduced to 102.4 V for the particular operation
3. The maximum charging and discharging current depends on the operating point and is within the range greater than 25A, less than 30A
Contact Information
SOLPLANET INTERNATIONAL
- info@solplanet.net
- sales@solplanet.net
- service.LATAM@solplanet.net
- service.EMEA@solplanet.net
- service.APAC@solplanet.net
Scan QR code and contact your local team
www.solplanet.net