Solplanet ASW H-T2 Series: Three-Phase Hybrid Inverters (5-12 kW)

Technical Datasheet

Key Features

[?]

Easy-to-install

  • Quick and easy-to-install with standard tools
  • Compact wall mount design
  • Simple battery and smart meter interfaces for quick and secure installation

[?️]

Safe & reliable

  • Up to 150% PV array oversizing for higher yields
  • Available with or without asymmetrical power output [1]
  • UPS level switching time < 10 ms
  • IP66 rated design for indoor and outdoor use
  • Arc fault circuit interrupter (AFCI) [2]
  • ShadeSol shadow management

[?]

User-friendly

  • Smart setup, commissioning and monitoring via Solplanet App
  • Intelligent operation modes and smart battery management for DOD / Time of Use / Power setting
  • Max. 20 A input current, ideal for bifacial and large PV modules
  • Supporting parallel for on-grid and off-grid operation

Technical Datasheet

Parameter ASW05kH-T2 ASW06kH-T2 ASW08kH-T2 ASW10kH-T2 ASW12kH-T2
PV input
Max. PV array power7500 Wp9000 Wp12000 Wp15000 Wp18000 Wp
Max. input voltage1100 V [5]
MPP voltage range / rated input voltage150 V to 950 V / 630 V200 V to 950 V / 630 V [3]
Min. input voltage / start voltage60 V / 180 V
No. of independent MPPT trackers / strings per MPPT input2 / 1
Max. input current / Max. power per MPP tracker20 A / 7500 W20 A / 9000 W20 A / 10000 W20 A / 10000 W20 A / 10000 W
Max. short-circuit current per MPP tracker30 A
Battery input
Battery voltage range120 V to 600 V [5]
Max. charging / discharging power5000 W6000 W8000 W10000 W12000 W
Max. charging current / Max. discharging current30A [5]
Battery typeLiFePO4
AC input
Rated grid voltage3/N/PE, 220 V / 380 V; 230 V / 400 V; 240 V / 415 V
Rated grid frequency50 Hz / 60 Hz
Max. input power from grid10000 W12000 W16000 W20000 W24000 W
Max. input current from grid14.5 A17.4 A23.2 A29.0 A34.8 A
AC output
AC voltage range / Nominal AC voltage270 V to 480 V / 3/N/PE, 220 V / 380 V; 230 V / 400 V; 240 V / 415 V
Rated AC grid frequency50 Hz / 60 Hz
AC grid frequency range45 ~ 55 Hz / 55 ~ 65 Hz
Rated apparent power5000 VA6000 VA8000 VA10000 VA12000 VA
Max. apparent power5000 VA6000 VA8000 VA10000 VA12000 VA
Rated grid output current (@400 V)7.3 A8.7 A11.6 A14.5 A17.4 A
Max. grid output current (@400 V)8.0 A9.6 A12.8 A16.0 A19.2 A
Power factor at rated power / adjustable range1 / 0.8 [leading] to 0.8 [lagging]
Harmonics THDi (@Nominal power)< 3 % (of nominal power)
EPS output
Nominal output voltage3/N/PE, 220 V / 380 V; 230 V / 400 V; 240 V / 415 V
Nominal output frequency50 Hz / 60 Hz
Rated apparent power5000 VA6000 VA8000 VA10000 VA12000 VA
Rated current (@400 V)7.3 A8.7 A11.6 A14.5 A17.4 A
Max. current (@400 V, continuous on-grid / off-grid)14.5 A / 7.3 A17.4 A / 8.7 A23.2 A / 11.6 A29.0 A / 14.5 A34.8 A / 17.4 A
Max. power on each phase (@400 V, continuous on-grid / off-grid)3333 W / 1667 W4000 W / 2000 W5333 W / 2667 W6667 W / 3333 W8000 W / 4000 W
Peak output apparent power (@400 V, continuous on-grid / off-grid up to 10s)10000 VA / 10000 VA12000 VA / 12000 VA16000 VA / 16000 VA20000 VA / 20000 VA24000 VA / 24000 VA
Max. switch time< 10 ms
Output THDv (@Linear load)2 %
Efficiency
MPPT efficiency99.9 %
Euro efficiency / Max. efficiency97.2 % / 98.0 %97.5 % / 98.2 %97.9 % / 98.4 %
Safety protection
DC surge protection (Type II, according to EN/IEC 61643-11)
Insulation resistance detection
PV string input reverse polarity protection
Battery input reverse polarity protection
Ground fault monitoring
Residual current monitoring unit
AC short circuit protection
Anti-islanding protection
Arc fault circuit interrupter (AFCI)○ [2]
General data
Dimensions (W / H / D)545 / 465 / 205 mm
Weight24.5 kg
Operating temperature range-25 °C … +60 °C
Cooling conceptNatural convection
Noise emission< 35 dB
Degree of protection (as per IEC 60529)IP66
Max. relative humidity100 %
Max. operating altitude4000 m
Features
User interfaceLED & App
BMS interfaceCAN
Smart meter interfaceRS485
Communication interfacesDongle: WiFi (2.4 GHz) / LAN (100 Mbps)
Inverter: RS485 (ModBus RTU), LAN (100 Mbps, Modbus TCP only) [4]
Digital output (dry contact) / No. of outputs● / 2
Digital input (dry contact) / No. of inputs● / 4
Integrated power control / export power control● / ●

● standard features / ○ optional features / - not available

[1] Asymmetrical power output functionality released in August 2024, please confirm version with Solplanet's sales staff before purchase.
[2] AFCI functionality released in April 2025, please confirm version with Solplanet's sales staff before purchase.
[3] The latest optimised platform design supports MPP voltage range at 150V-950V, pending subsequent certificate updates.
[4] Modbus TCP functionality released in April 2025, please confirm version with Solplanet's sales staff before purchase.
[5] When connecting to Solplanet‘s high voltage batteries (with only 5 kWh, i.e. two modules), limitations as below apply:
    1. The maximum voltage of PV shall not exceed 750V
    2. The battery voltage range is reduced to 102.4 V for the particular operation
    3. The maximum charging and discharging current depends on the operating point and is within the range greater than 25A, less than 30A

Contact Information

SOLPLANET INTERNATIONAL

Scan QR code and contact your local team

www.solplanet.net

PDF preview unavailable. Download the PDF instead.

HT2-EU-1 Adobe PDF Library 17.0 Adobe InDesign 20.4 (Macintosh)

Related Documents

Preview Solplanet Three Phase Hybrid Inverter Quick Installation Guide
A concise guide for the quick installation of Solplanet's three-phase hybrid inverters, covering safety, wiring, mounting, and connection procedures for models ASW05kH to ASW12kH (T2, T2-O, T3, T3-O).
Preview Solplanet Inverter Battery Compatibility List
Comprehensive compatibility list for Solplanet ASW inverter series, detailing compatible battery models, models in the app, and related firmware versions. Updated September 2025.
Preview Solplanet Three-Phase Hybrid Inverter User Manual
User manual for Solplanet's three-phase hybrid inverters (ASW05kH-12kH T2/T3 series). Covers installation, operation, safety, technical data, and troubleshooting for efficient solar and battery energy management.
Preview Solplanet Three Phase Hybrid Inverter Quick Installation Guide
Quick installation guide for Solplanet three-phase hybrid inverters (ASW T2/T3 series), covering safety, system wiring, mounting, connections, and communication setup.
Preview Solplanet EU Declaration of Conformity - ASW Series Inverters
Official EU Declaration of Conformity for Solplanet ASW Series hybrid inverters, confirming compliance with Radio Equipment Directive (RED) and relevant harmonized European standards for safety, electromagnetic compatibility, frequency range, and cybersecurity.
Preview Solplanet Three Phase Hybrid Inverter User Manual
This user manual provides comprehensive instructions for the Solplanet three-phase hybrid inverter, covering installation, operation, troubleshooting, and maintenance for models ASW05kH/06kH/08kH/10kH/12kH-T2, ASW05kH/06kH/08kH/10kH/12kH-T2-O, ASW08kH/10kH/12kH-T3, and ASW08kH/10kH/12kH-T3-O.
Preview Manuale Utente Inverter Ibrido Trifase Solplanet ASW Series
Guida completa all'installazione, configurazione, funzionamento e manutenzione degli inverter ibridi trifase Solplanet ASW Series (modelli T2, T2-0, T3, T3-0).
Preview Solplanet ASW H-T3 Series Hybrid Inverters: 8-12 kW Technical Specifications
Detailed technical specifications for the Solplanet ASW H-T3 Series of three-phase hybrid inverters, covering models ASW08kH-T3, ASW10kH-T3, and ASW12kH-T3. Features include easy installation, safety, reliability, user-friendliness, and advanced technical data for PV input, battery input, AC output, and efficiency.