GREE Air Source Heat Pump Water Heater

Model: GRS-2.3Pd/TD200ANpH-K, GRS-2.3Pd/TD270ANpH-K

Product Code: GC202405-I

Technical Sales Guide - 50Hz

Capacity Range: 2.3kW

Ambient Operation Range: -7~45°C

1. Product List

Model Heating Capacity (W) Power Supply Appearance
GRS-2.3Pd/TD200ANpH-K 2300W + 2000W (electrical heater) 220V-240V ~ 50Hz

Two cylindrical units are depicted, representing the GRS-2.3Pd/TD200ANpH-K and GRS-2.3Pd/TD270ANpH-K models.

GRS-2.3Pd/TD270ANpH-K 2300W + 2000W (electrical heater) 220V-240V ~ 50Hz

2. Nomenclature

The nomenclature for the GRS series heat pump water heater is broken down as follows:

No. Description Options
1 Product code GRS - Heat pump water heater
2 Heating capacity code Heating capacity (Unit: kW)
3 Compressor system Single system - Omit; Dual system - S
4 Functions characteristics 1 Fixed frequency - Omit; Inverter - P; DC Inverter - Pd; Fixed frequency modular - M; AC Inverter modular - PM; DC Inverter modular - PdM
5 Functions characteristics 2 Normal type - Omit; Low temperature heat pump - Re
6 Water tank material Stainless Steel - Omit; T - Enameled steel
7 Function code No electric heating function - Omit; With electric heating function - D
8 Water tank capacity Capacity of water tank; Unit: L
9 Design code A-LCJW: floor standing type, outer coil pipe static heating type; B-BCJW: wall-mounted type, outer coil pipe static heating type; C-LCJ: floor standing type, built-in coil pipe static heating type; D-BCJ: wall-mounted type, built-in coil pipe static heating type
10 Water tank shape Round - Omit; Square - F
11 Inner tank number Single - Omit; Double - 2
12 Refrigerant R22 - Omit; R407c - N; R410A - Na; R134a - Nb; R32 - Nh; R290 - Np
13 Design Serial number A, B, C...or A1, A2..., B1, B2...
14 Backwater function No - Omit; Yes - H
15 E-commerce code Non-e-commerce models - Omit; E-commerce models - D
16 Power code M-380-415V 3PH~50Hz; K-220V-240V 1PH~50Hz; D-220V-240V 1PH~60Hz

3. Introductions to Components

No. Name Function
1 Compressor Increases pressure for the refrigerant and provides driving force for circular flow of the refrigerant as a main driving component.
2 Four-way valve Reverses flow direction of the refrigerant when the system switches between the normal heat up mode and defrosting mode.
3 Water tank Provides heat exchange channel for refrigerant and water and stores hot water for daily use.
4 Electronic expansion valve Speeds up high-pressure and high-temperature refrigerant and reduces pressure and adjusts the circulation amount of coolant.
5 Finned tube exchanger Provides heat exchange channel for refrigerant and air.
6 Fan motor Enhances heat exchange on the air side of the finned tube exchange and provides a low-temperature heat source continuously.
7 Filter Filters impurities in refrigerant to protect components with small diameter.

Figure 3-1 Diagram of Parts: The diagram illustrates the following components:

  • 1. Fan
  • 2. Motor
  • 3. Electrical box
  • 4. Display board
  • 5. Cold water inlet
  • 6. Mg-stick (Anode)
  • 7. Electric heater
  • 8. Electrical cover
  • 9. Thermostat
  • 10. Bottom water tank temperature sensor
  • 11. Top water tank temperature sensor
  • 12. Hot water outlet
  • 13. PTR valve
  • 14. Compressor
  • 15. Four-way valve

4. Product Parameters

Model GRS-2.3Pd/TD200ANpH-K GRS-2.3Pd/TD270ANpH-K
Rated water storage capacity 206L 270L
Heat pump heating capacity 2300W 2300W
Rated input power 426W 426W
Electric heater power 2000W 2000W
Maximum input power 830W+2000W (Electric heater) 830W+2000W (Electric heater)
Power supply 220-240V ~ 50Hz 220-240V ~ 50Hz
Water outlet temperature 35°C~70°C 35°C~70°C
Heat pump operating range -7°C~45°C -7°C~45°C
Inlet/Outlet connector diameter DN15 DN15
Water-proof grade IPX4 IPX4
Refrigerant R290 (330g) R290 (330g)
Sound pressure level 44dB(A) 44dB(A)
Dimension (W×D×H) 663mm×670mm×1643mm 663mm×670mm×1924mm
Net weight 97kg 109kg

Notes:

  • Product conforms to AS 3498:2020 and AS/NZS 2712:2007.
  • Test conditions: Outdoor ambient temperature 20/15°C (DB/WB); Water temperature from 10°C up to 55°C.
  • Under BOOST Mode, the electric heater assists in heating water.
  • Refer to the nameplate for exact data, as this table is subject to change.

5. Produce Performance Curves

Figure 5-1: Shows the heating time for the GRS-2.3Pd/TD270ANpH-K model at different ambient and target water temperatures (heat pump only).

Figure 5-2: Shows the heating time for the GRS-2.3Pd/TD200ANpH-K model at different ambient and target water temperatures (heat pump only).

Notes:

  • Curve data is based on Gree Laboratory tests with initial water temperature of 10°C and 230V ~ 50Hz power supply. A 5% tolerance is expected.
  • When the electric heater and heat pump operate simultaneously, heating time decreases, but COP decreases and power consumption increases.

6. Dimension Parameters

Unit: mm

Parameter Model: GRS-2.3Pd/TD200ANpH-K Model: GRS-2.3Pd/TD270ANpH-K
A 1643 1924
B 663 663
C 156 156
D 964 1235
E 1177 1458

The diagram shows the physical dimensions of the unit with labels A, B, C, D, and E corresponding to the values in the table.

7. Installation

7.1 Unit Installation Diagram

The diagram illustrates the installation connections for the unit, including:

  • Cold water input
  • Hot water output
  • Condensate outlet
  • Floor drain
  • PTR valve
  • Thermostatic mixer tap
  • Three-way valve
  • Cut-off valves

Warning: Insulation plastic pipes such as PPR pipes are recommended. Pipe length (L) should be determined by the formula L≥70×R², where R is the inner diameter of the pipe in cm. Pipes must be insulated. Metal pipes are not allowed.

7.2 Installation Dimension

Diagram showing required clearances for air inlet and outlet. Minimum clearances are specified:

  • Air outlet: ≥2000mm
  • Air inlet: ≥650mm (side clearance), ≥500mm (front clearance)

7.3 Installation Requirements

  • Ensure sound and airflow do not affect people, animals, or plants.
  • Ensure good ventilation. If a canopy is used, it should not impede heat dissipation or absorption.
  • Install on a solid, flat foundation, ensuring the unit is upright. Reinforce for strong winds, typhoons, or earthquakes.
  • Ensure reliable connection of the drain pipe to a proper drainage point.
  • Install in a location sheltered from rain, with sun shading devices.
  • Install piping and valves in ambient temperatures above 0°C, preferably near the main hot water point.
  • Avoid installing in areas without good drainage to prevent water leakage damage.
  • The unit must be located upright on a flat, spacious, and solid foundation capable of supporting four times the unit's weight when filled with water. Do not hang the unit or mount it on an external wall. Use fixing belts for stability, especially in high-wind areas, and consider additional reinforcement. Fixing belts are for auxiliary support only.
  • Water quality must comply with local sanitation standards for domestic drinking water.

Table 7.3-1 Water Quality Requirements:

Parameter Requirement Parameter Requirement
pH (25°C) 6.8~8.0 Turbidity (scattering turbidity unit)/NTU <1
Chloride/(mg/L) <50 Iron/(mg/L) <0.3
Sulfate/(mg/L) <50 Silica (SiO2)/(mg/L) <30
Total hardness (calculated in CaCO3)/(mg/L) <70 Nitrate (calculated in N)/(mg/L) <10
Conductivity (25°C)/(μs/cm) <300 Ammonia nitrogen (calculated in N)/(mg/L) <1.0
Total alkalinity (calculated in CaCO3)/(mg/L) <50 Sulfide/(mg/L) Shall not to be detected

7.4 Wiring

Warning: Installation must be performed by qualified personnel according to national wiring regulations. Ensure power supply, wires, and sockets comply with nameplate specifications and have sufficient capacity.

  • The fixed circuit must include a residual current device (RCD) and a circuit breaker.
  • The unit must be reliably grounded.
  • The unit circuit must be at least 1.5m away from any inflammable surface.
  • Use a separate fixed device for power supply, matching the water heater's requirements and local standards.
  • Do not use socket converters, extension cords, or wiring boards. Connect wires separately and do not share circuits with other appliances.
  • If the power cord is damaged, it must be replaced by the manufacturer or a qualified service agent.

7.4.1 Selection of Power Cord Diameter and Circuit Breaker

Table 7.4-1 Unit Power Cord Configuration Table:

Model Power Supply Minimum sectional area (mm²) of power cord Circuit breaker (A) Fuse capacity (A)
L N PE
GRS-2.3Pd/TD200ANpH-K 220-240V ~ 50Hz 1.5 1.5 1.5 16 16
GRS-2.3Pd/TD270ANpH-K 1.5 1.5 1.5 16 16

7.4.2 Wiring Diagram

Figure 7.4-1 External wiring: Shows the external wiring diagram. Internal wiring diagrams are attached to the machine.

Two installation methods for the display board (wired controller) are provided:

  • Method I: For installation in an area other than the unit's panel.
  • Method II: For installation on the unit's panel.

Figure 7.4-2 External wiring and fixing figure: Illustrates external wiring and fixing details.

Note: Power cord for GRS-2.3Pd/TD200ANpH-K and GRS-2.3Pd/TD270ANpH-K is 3×1.5mm². Display board cord is 2×0.75mm².

7.4.3 Electrical Wiring and Connection Requirement

  • Ensure power cord and communication wires are tightly secured with a wire clamp on the outer sheath.
  • Separate communication cords from power cords for the external unit. Maintain a minimum distance of 20cm between parallel wires to prevent communication anomalies. Cover strong and weak wires separately with wire sleeves.

7.4.4 Wired Controller Installation

The wired controller is installed on the unit's front panel by default. If relocating, the communication cable length should not exceed 8m.

7.5 Commissioning Operation

Warning: All personnel must adhere to safety regulations during commissioning and maintenance. Power must be cut off before performing operations. Comply with all safety requirements and regulations.

7.5.1 Check before Commissioning

After installation, perform the following checks:

Table 7.5-1 Unit Installation Checklist:

Items to be checked What may happen if the installation is improper
Whether the unit is installed reliably The unit produces noise or vibration, potentially causing danger (e.g., falling).
Whether there are obstacles at the air outlet and air inlet of the unit The unit operates abnormally.
Whether the cold water inlet pipe and hot water outlet pipe use PPR pipes Safety hazard may happen.
Whether the safety valve of water tank is installed High water tank pressure, posing a safety hazard.
Whether a stabilizing valve is installed when the inlet pressure of water tank is too high High water tank pressure; safety valve may discharge water, causing abnormal noise.
Whether all parts of the water pipeline have been properly insulated Unit performance may be affected; pipeline may be damaged by freezing.
Whether the power supply voltage is consistent with the product nameplate, and whether the wire type meets the regulations Unit malfunction or component burnout.

7.5.2 Trial Operation

Note: The water tank must be filled with water before powering on the unit. Debugging can commence after installation inspection.

Debugging Steps:

  1. Water recharge: Fill the water tank as per the installation tips label. Ensure no water leakage in pipelines or joints.
  2. Energization: Power on the unit and check the wired controller display for normal operation (no fault indicated).
  3. System time calibration: Set the time on the wired controller according to its manual.
  4. Operation: Turn on the unit via the wired controller. When the heating icon is displayed, check for normal operation: fan running smoothly, unit stable with no excessive vibration or noise. The unit can be delivered after running for at least 20 minutes without abnormality.

8. Model Selection

Residential water heater systems typically have tank capacities of 150L-300L. Tank capacity can be estimated as (50-80) L × n (number of persons) for floor-standing types.

Table 8-1 Model Selection Suggestion:

Applicable Range Model
A family of three or four persons GRS-2.3Pd/TD200ANpH-K
A family of four or five persons GRS-2.3Pd/TD270ANpH-K

Note: These suggestions are for reference; select the model based on user needs.

Contact Information

GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI

Address: West Jinji Rd, Qianshan Zhuhai, Guangdong, China 519070

Tel: (+86-756)8522218

Fax: (+86-756)8669426

E-mail: gree@cn.gree.com

Website: www.gree.com

Document Reference: JF00305669

Models: GRS-2.3Pd-TD200ANpH-K, GRS-2.3Pd-TD270ANpH-K, GRS-2.3Pd Series Air Source Heat Pump Water Heater, GRS-2.3Pd Series, Air Source Heat Pump Water Heater, Heat Pump Water Heater, Pump Water Heater, Water Heater

File Info : application/pdf, 12 Pages, 4.73MB

PDF preview unavailable. Download the PDF instead.

TSG R290 Inverter HWHP (Residential) WPS 文字

Related Documents

Preview AHRI Certified Product Ratings Certificate for GREE Mini-Split Heat Pump
Official certificate detailing the performance ratings for a GREE Mini-Split Heat Pump (Model: HRCU-A-CB-O, Outdoor: 3VIR24HP230V1BO, Indoor: CAS24HP230V1BC) as certified by AHRI, including cooling and heating capacities, SEER2, EER2, and HSPF2 ratings.
Preview GREE GWHD(36)ND3MO Multi-Zone Heat Pump System: Specifications and Capabilities
Detailed specifications, features, and allowable indoor/outdoor unit combinations for the GREE GWHD(36)ND3MO 36000 BTU/H Multi-Zone Heat Pump System, including performance data, dimensions, and clearances.
Preview GREE FLEXX ULTRA R32 Heat Pump Submittal Data & Specifications
Detailed submittal data, specifications, dimensions, and clearance requirements for the GREE FLEXX ULTRA R32 36000 BTU/H A-Coil Unitary Heat Pump Split System (FXA36C32AH / FXU36HP230V1R32AO).
Preview GREE G Series Fan Coil Unit Technical Sales Guide
This document provides technical specifications, performance data, installation instructions, and optional parts for the GREE G Series Fan Coil Unit. It covers nomenclature, product introduction, detailed technical information including performance correction tables, dimensions, wiring diagrams, selection requirements, and thermostat options.
Preview GREE FLEXX ULTRA R32 A-Coil Unitary Heat Pump Submittal Data and Specifications
Detailed submittal data, specifications, dimensions, and installation clearances for the GREE FLEXX ULTRA R32 A-Coil Unitary Heat Pump Split System (FXA48C32AH / FXU60HP230V1R32A0), featuring 48000 BTU/H capacity.
Preview GREE MUL30HP230V1R32AO Multi-Zone Heat Pump System Submittal Data
Technical specifications and compatibility information for the GREE MUL30HP230V1R32AO 30000 BTU/H Multi-Zone Heat Pump System, including performance data, dimensions, and features. Details system compatibility and operational parameters.
Preview GREE DC Inverter Heat Pump Condensing Unit Technical Sales Guide
Comprehensive technical sales guide for GREE DC Inverter Heat Pump Condensing Units, covering model specifications, performance data, dimensions, and wiring diagrams for residential applications.
Preview GREE 4LIV Series Service Manual
Comprehensive service manual for GREE 4LIV series air conditioning units, detailing installation, maintenance, troubleshooting, and technical specifications for models including 4LIV09, 4LIV12, 4LIV18, and 4LIV24.