1 Description
The ECS-50WBU provides backup capability when operating the ECS-DUAL50W in the 100 watt-with-backup mode for both single and dual channel setups.
1.1 Compatibility
The ECS-50WBU is compatible with the following Honeywell Farenhyt Series Fire Alarm Control Panels (FACPs). For more information, refer to the FACP Installation Manual or the ECS Series Manual (PN 151455).
- IFP-2100ECS
- IFP-300ECS
- IFP-2000ECS
- IFP-1000ECS
- IFP-100ECS
2 Installation and Wiring
The ECS-50WBU mounts on top of the ECS-DUAL50W board on the standoffs provided.
- Remove AC power from the ECS-DUAL50W.
- Disconnect backup batteries from the ECS-DUAL50W.
- Connect one end of the supplied wiring harness (P/N 50116775-001) from the connector labeled, "Backup Amplifier" on the ECS-DUAL50W to the connector on the ECS-50WBU as shown in Figure 1.
- Mount the ECS-50WBU to the standoffs using the 4 supplied screws as shown in Figure 1.
- Restore AC Power.
- Reconnect backup batteries.
Figure 1: Installation and Wiring Diagram Description
This diagram illustrates the physical mounting and wiring connection of the ECS-50WBU to the ECS-DUAL50W. It shows the ECS-50WBU unit positioned above the ECS-DUAL50W board. Arrows labeled "secure with screws" point from the ECS-50WBU to mounting points, indicating it is attached with screws to standoffs. A wiring harness is shown connecting the ECS-50WBU to a connector on the ECS-DUAL50W, which is labeled "Backup Amplifier". The diagram also indicates points on the ECS-DUAL50W where standoffs should be installed, labeled "install standoffs".