SK-NIC Network Interface Card
Product Installation Document
PN LS10172-001SK-E:C | 12/15/2021 | ECN: 151062
Description
The SK-NIC Network Interface Card is used when networking a group of Fire Alarm Control Panels (FACPs). It is used to link the panels together.
[NOTE] The SK-NIC provides a common communications link for the 6700, 6808, and 6820/6820EVS. These panels cannot be linked together for peer-to-peer networking.
Compatibility
The SK-NIC is compatible with the following Honeywell Silent Knight and Farenhyt Series FACPs. For information on programming and addressing, refer to the Networking / Common Communication link Section of the FACP Installation Manuals.
- IFP-2100/ECS
- IFP-300/ECS
- IFP-75
- 6820/6820EVS
- 6808
- 6700
Specifications
- Standby Current: 21mA
- Alarm Current: 21mA
- Operating Voltage: 24VDC
- Operating Temperature: 32°F to 120°F (0°C to 49°C)
Installation
Layout and Mounting
The SK-NIC can be mounted within the FACP cabinet (except for the IFP-75 or 6700), in a 5815RMK accessory cabinet, or in a SK-NIC-KIT cabinet. Up to two SK-NIC cards can fit inside the 5815RMK. Refer to the 5815RMK Installation Document, P/N 151391.
The SK-NIC-KIT is an accessory cabinet kit containing an SK-NIC card, a small cabinet with door, a 6-pin cable and mounting hardware. Up to two SK-NIC cards can fit inside the SK-NIC-KIT. For more information, refer to the SK-NIC-KIT Installation Document P/N LS10171-001SK-E.
Figure 1: SK-NIC Board
The SK-NIC board features two ports labeled 'Port 1' and 'Port 2', a connector labeled 'P3', and other component placements. It is shown with a connection to the FACP.
Installation (Wiring)
NOTE: Installation and wiring of this device must be done in accordance with NFPA 72 and local ordinances.
Refer to the following steps to properly connect the SK-NIC to the FACP port using the supplied 6-pin cable.
- Place the SK-NIC on one of the SLC expander standoff sets.
- Using the 6-pin cable, connect one end to the FACP pin connector labeled "Data Network" and the other end to the SK-NIC board's P3 connector.
Figure 2: Panel to SK-NIC Connection
This diagram illustrates the connection between a Fire Alarm Control Panel (FACP) and the SK-NIC. A 6-pin cable connects the FACP's 'Data Network' connector to the SK-NIC's P3 connector. The FACP layout may vary. An optional conduit is shown for remote mounting.
SK-NIC Remote Mounting
Follow Steps 1 and 2 above except the 6-pin cable that runs from the SK-NIC to the FACP must be run in conduit. Refer to the SK-NIC-KIT or 5815RMK Installation Document.
Fiber Loop Modules
The SK-NIC connects to other networked units using unshielded, twisted-pair wiring or fiber-optic cable.
The SK-FML and SK-FSL are plug-in fiber loop modules. The two types of fiber optic modules are used as one channel to transmit or receive communications with the SK-NIC, ARCNET communication circuit.
The following two types of fiber-optic modules are available:
- The SK-FML is a fiber module that allows the multi-mode fiber to network between nodes.
- The SK-FSL is a fiber module that allows the single-mode fiber to network between nodes.
For more information on the fiber modules, refer to the SK-FML and SK-FSL Installation Document P/N:LS10178-001SK-E.
Figure 3: SK-NIC Fiber Loop Modules Mounted on SK-NIC
The SK-NIC board is shown with plug-in fiber loop modules, SK-FML and SK-FSL. It includes terminals for connecting to other units using copper wire instead of fiber modules. LED indicators (LED1, LED2) are also visible.