GE APPLIANCES
Installation Instructions for your new RAK315SP, RAK320SP, RAK330SP
Power Supply Kit for Sub-base
Before you begin - Read these instructions completely and carefully. IMPORTANT – OBSERVE ALL GOVERNING CODES AND ORDINANCES.
Note to Installer – Be sure to leave these instructions with the Consumer.
Note to Consumer – Keep these instructions with your Owner's Manual for future reference.
Tools Needed
- Phillips Head Screw Driver
This kit is for use with 230/208 volt replacement GE Zoneline units only with previously installed sub-bases. NOTE: Use only with sub-base kits RAK204D15*, RAK204D20*, or RAK204D30*.
230/208 VOLT ELECTRICAL SUPPLY
A power supply kit must be used to supply power to the Zoneline unit. The appropriate kit is determined by the voltage, the means of electrical connection, and the amperage of the branch circuit. See the POWER CONNECTION CHART to confirm the appropriate kit.
Power supply kit - Appearance may vary
All wiring, including installation of the receptacle, must be in accordance with the NEC, local codes, ordinances, and regulations.
IMPORTANT NOTES
- This unit must be properly connected to a grounded circuit.
- The electrical rating marked on the power supply kit must be the same as the supply branch circuit.
- Aluminum building wiring may present special problems - consult a qualified electrician.
- All wiring, including installation of the receptacle, must be in accordance with the NEC, local codes, ordinances, and regulations.
- Use ONLY the wiring size recommended for single outlet branch circuit.
- Proper current protection is the responsibility of the owner.
Recommended branch circuit wire sizes*
Nameplate maximum circuit breaker size | AWG wire size** |
---|---|
15A | 14 |
20A | 12 |
30A | 10 |
AWG - American Wire Gauge
* Single circuit breaker from main box
** Based on copper wire, single-insulated conductor at 60°C
NOTE: Use copper conductors only.
230/208 volt receptacle configuration
- Tandem 15 Amp
- Perpendicular 20 Amp
- Large Tandem 30 Amp
POWER CONNECTION CHART
GE 230/208 Volt Power Supply Kit | Receptacle Configuration | Circuit Protective Device |
---|---|---|
RAK315SP | Tandem | 15-Amp Time-Delay Fuse or Breaker |
RAK320SP | Perpendicular | 20-Amp Time-Delay Fuse or Breaker |
RAK330SP | Large Tandem | 30-Amp Time-Delay Fuse or Breaker |
Installation Instructions
FOR 230/208 VOLT ZONELINE POWER CORD CONNECTIONS ONLY
For GE Zoneline AZ45 & AZ65 Series Units (Installation Instruction Specific to Units Ending in W5 or Higher)
This kit must be used in conjunction with a GE junction box kit and sub base with chaseway.
1. REMOVE ROOM FRONT
Remove the room cabinet by pulling it out at the bottom to release it; then lift it up to clear the rail along the unit top.
2. REMOVE JUNCTION BOX COVER
Remove the junction box cover by removing the screw holding it to the assembly.
3. CONCEAL POWER SUPPLY KIT SUB-BASE AND CHASEWAY
- Remove the rectangular knockout at the bottom of the junction box. Remove the rectangular knockout at the right end of the sub-base.
- Power Supply kit is placed between the two halves of the chaseway. Observe the orientation of the chaseway.
- Align the screw holes and secure the halves together using two type A screws.
- Slide the upper end of chaseway with wiring protruding into rectangular knockout opening in the junction box. Be sure chaseway "ears" are on the inside of the box.
- Drive one type A screw through the junction box bottom into the chaseway "ear" hole.
- Insert lower end of chaseway into rectangular hole in sub-base and slide to right into the rectangular knockout making sure chaseway "ears" are inside the sub-base.
- Route wire toward the center of the sub-base.
- Drive one type A screw through the sub-base slotted hole into chaseway "ear" hole.
4. INSTALL JUNCTION BOX (230/208V UNITS)
Install the junction box by engaging the tabs of the junction box with the slots on the control housing, align the screw hole at the top and drive the supplied screw until secure.
5. CONNECT THE CORDSET
Plug in the connectors on the power supply kit into the corresponding mating connectors on the Zoneline. Be sure to locking tabs at the sides are engaged. Insert the plug into the receptacle inside the sub-base.
NOTE: Power Supply Kit – Appearance may vary. RAK315SP will only have one power connector.
6. INSTALL JUNCTION BOX COVER
- Replace and secure all front covers on the sub base. Do not pinch any wires.
- Place the junction box cover in place. Replace the two screws removed earlier and tighten securely.
- Replace the Zoneline front cabinet.
GE is a trademark of the General Electric Company. Manufactured under trademark license.
31-5000693 Rev. 0 03-22 GEA