Danfoss EKC 361 Media Temperature Controller

Installation Guide

This guide provides detailed instructions for installing and operating the Danfoss EKC 361 media temperature controller. It covers electrical connections, operation, menu settings, troubleshooting, and performance characteristics. The original document contains information in Danish, English, German, and French.

Wiring and Connections

Necessary Connections

The following connections are required for the EKC 361 controller:

Application Dependent Connections

Additional connections depend on the application:

Data Communication Wiring

For data communication, observe the following cable length recommendations:

Wiring Diagram Description

A typical wiring diagram shows the EKC 361 controller connected to components such as ICS, ICM, CVQ, EVRA, and temperature sensors (Pt 1000 AKS 21). It illustrates the flow of power and signals for system operation.

Operation and Display

Display and Indicators

The controller displays values with three digits. The temperature unit can be set to °C or °F. Front panel LEDs indicate relay activation. The three lowest LEDs flash if an error occurs in the regulation. Error codes can be displayed, and alarms cancelled by briefly pressing the uppermost button.

Controller Messages

The controller may display the following messages:

Using the Buttons

Two buttons are used to adjust settings, increasing or decreasing values. To change a setting:

  1. Access the menu by pressing the upper button for a few seconds.
  2. Navigate through parameter codes using one of the buttons.
  3. Press both buttons simultaneously to select a parameter.
  4. Press one button to change the value.
  5. Press both buttons simultaneously to save the new value.

Example: Setting a Set-point

  1. Press both buttons simultaneously.
  2. Use one button to select the new value.
  3. Press both buttons again to confirm the setting.

Example: Setting Other Menus

  1. Press the upper button until a parameter is shown.
  2. Use one button to find the desired parameter.
  3. Press both buttons simultaneously until the parameter value is shown.
  4. Use one button to select the new value.
  5. Press both buttons again to confirm the setting.

Menu Overview

Function Parameter Min. Max. Factory Setting
Normal displayShows temperature at selected sensor. At ICM valve, OD can also be selected.
Reference-70°C160°C10°C
Temperature unitr05°C°F°C
Input signal's temperature influencer06-50°C50°C0.0
Correction of the signal from Sairr09-10.0°C10.0°C0.0
Correction of the signal from Sauxr10-10.0°C10.0°C0.0
Start/stop of refrigerationr12OFF/0On/1On/1
Alarm: Upper deviationA01050 K5.0
Alarm: Lower deviationA02050 K5.0
Alarm's time delayA030180 min30
Regulating parameters: Actuator max. temperaturen0141°C140°C140
Regulating parameters: Actuator min. temperaturen0240°C139°C40
Regulating parameters: Actuator typen03162
Regulating parameters: P: Amplification factor Kpn040.5503
Regulating parameters: I: Integration time Tnn0560 s600 s240
Regulating parameters: D: Differentiation time Tdn060 s60 s10
Transient phenomenonn07022
OD - Opening degree - max. limit (ICM only)n320%100%100
OD - Opening degree - min. limit (ICM only)n330%100%0
Miscellaneous: Controller's address003*09900
Miscellaneous: ON/OFF switch004*
Miscellaneous: Define output signal of analog output009020
Miscellaneous: Define input signal of analog input010020
Miscellaneous: Language011*060
Miscellaneous: Set supply voltage frequency01250 Hz/060 Hz/10
Miscellaneous: Select of running display value017Au/0Air/1Air/1
Set temperature for min. output signal (0 or 4 mA)027-70°C160°C-35
Set temperature for max. output signal (20 mA)028-70°C160°C15
Service: Read temperature at Sair sensoru01°C
Service: Read regulation referenceu02°C
Service: Read temperature at Saux sensoru03°C
Service: Read valve's actuator temperatureu04°C
Service: Read reference of valve's actuator temperatureu05°C
Service: Read value of external current signalu06mA
Service: Read value of transmitted current signalu08mA
Service: Read status of input DIu10on/off
Service: ICM opening degree (ICM only)u24%

* This setting is only possible if a data communication module is installed.

Performance Graphs (n01 and n02)

These graphs illustrate the relationship between evaporating temperature and actuator temperature. Parameter n01 is set for the highest regulated room temperature, requiring a +10 K offset from the curve due to actuator tolerances. Parameter n02 is set for the lowest suction pressure, requiring a -10 K offset from the curve.

CVMQ Valve

Graph showing Pressure (bar eff.) vs. Temperature (°C) for CVMQ valves, indicating 'Open' and 'Closed' actuator states for different refrigerants (R22, R134a, R404A) and pressure ranges (-1-5 bar eff., 0-6 bar eff., 1.7-8 bar eff.).

CVQ Valve

Graph showing Pressure (bar eff.) vs. Temperature (°C) for CVQ valves, indicating 'Open' and 'Closed' actuator states for different refrigerants (R22, R134a, R404A) and pressure ranges (-1-5 bar eff., 0-6 bar eff., 1.7-8 bar eff.).

KVQ Valve

Graph showing Pressure (bar eff.) vs. Temperature (°C) for KVQ valves, indicating 'Open' and 'Closed' actuator states for different refrigerants (R22, R134a, R404A) and pressure ranges (-1-5 bar eff., 0-6 bar eff., 1.7-8 bar eff.).

Startup and Troubleshooting

Startup Procedure

After electrical connections are made, follow these steps to start regulation:

  1. Switch off the external ON/OFF switch that starts and stops regulation.
  2. Follow the menu overview and set parameters to desired values.
  3. Switch on the external ON/OFF switch to start regulation.
  4. If a thermostatic expansion valve is fitted, set it to minimum stable superheating. Adjust n01/n02 if a specific T0 is required during expansion valve adjustment, and remember to reset them afterwards.
  5. Monitor the room temperature on the display. A current signal representing room temperature can be transmitted on terminals 2 and 5. Consider connecting a data collection unit to follow temperature performance.

Temperature Fluctuations (Oscillation)

If the system oscillates after achieving stable operation, adjust parameters based on oscillation periods and integration time (Tn).

If oscillation period is longer than integration time (Tp > Tn):

  1. Increase Tn to 1.2 times the current Tn.
  2. Wait for the system to stabilize.
  3. If oscillation persists, reduce Kp by approximately 20%.
  4. Wait for the system to stabilize.
  5. Repeat steps 3 and 4 if oscillation continues.

If oscillation period is shorter than integration time (Tp < Tn):

  1. Reduce Kp by approximately 20% of the scale reading.
  2. Wait for the system to stabilize.
  3. Repeat steps 1 and 2 if oscillation continues.

Literature and Factory Reset

Literature References

Relevant documentation includes:

Factory Reset Procedure

To revert to factory-set values:

  1. Disconnect the controller's supply voltage.
  2. Keep both buttons depressed while reconnecting the supply voltage.
Models: EKC 361 Media Temperature Controller, EKC 361, EKC 361 Temperature Controller, Media Temperature Controller, Temperature Controller, Controller

File Info : application/pdf, 12 Pages, 1.11MB

PDF preview unavailable. Download the PDF instead.

AN00008642619602-000701 Danfoss A/S Adobe PDF Library 8.0

Related Documents

Preview Danfoss EKC 367: Instructions and Operation Guide
Comprehensive instructions and operational guide for the Danfoss EKC 367 electronic refrigeration controller, covering installation, connections, parameters, and troubleshooting.
Preview Danfoss EKC 202 Series User Guide: Temperature Control for Refrigeration
This user guide details the Danfoss EKC 202 series controllers, designed for precise temperature management in refrigeration appliances and cold rooms. It covers features like defrost control, fan operation, alarms, and connectivity within ADAP-KOOL® systems.
Preview Danfoss EKC 315A Controller: Instructions and Operation Manual
Comprehensive instructions and operational guide for the Danfoss EKC 315A refrigeration and air conditioning controller, covering connections, menu navigation, parameter settings, and troubleshooting.
Preview Danfoss ICAD 600/900 Actuator: Installation, Operation, and Technical Data
Comprehensive guide to the Danfoss ICAD 600 and ICAD 900 actuators, covering installation, electrical data, general operation, parameter settings, alarms, and technical specifications. Includes wiring diagrams and compatibility information.
Preview Danfoss AK-CC 550A Instruction Manual - Refrigeration Controller Guide
Comprehensive instructions for the Danfoss AK-CC 550A refrigeration controller, covering identification, dimensions, principle, connections, operation, parameters, and error messages. Learn how to set up and manage your refrigeration system efficiently.
Preview Danfoss ERC 214 Digital Regulator Installation Guide
Comprehensive installation guide for the Danfoss ERC 214 digital regulator, detailing its features, user interface, quick-start configuration, basic functions, technical data, and parameter settings for refrigeration and defrosting applications.
Preview Danfoss EKC 223 Case Controller Installation Guide
This guide provides installation, operation, and technical data for the Danfoss EKC 223 case controller, designed for commercial air-conditioning and refrigeration applications.
Preview Danfoss EKC 202D and EKC 302D Temperature Controllers: Manual and Specifications
A comprehensive guide to the Danfoss EKC 202D and EKC 302D temperature controllers, detailing their applications in refrigeration, operational principles, functions, digital inputs, defrost methods, alarm settings, technical specifications, and ordering information.