Danfoss EKC 315A Controller

Instructions

This document provides instructions and operational details for the Danfoss EKC 315A controller, designed for refrigeration and air conditioning applications.

Identification and Dimensions

The EKC 315A unit is identified by model numbers such as 084B7086. Dimensions are provided for reference, showing the physical size of the unit.

A system schematic illustrates the EKC 315A controller connected to sensors (S2 for evaporator outlet, S3 for air temperature) and an actuator (AKV/TQ), along with a solenoid valve.

Connections

The controller features various terminals for necessary and application-dependent connections.

Necessary Connections

  • Terminals 25-26: Supply voltage 24 V a.c.
  • Terminals 17-18: Signal from TQ actuator (only).
  • Terminals 20-21: Pt 1000 sensor at evaporator outlet (S2).
  • Terminals 14-15: Pressure transmitter (e.g., AKS 33).
  • Terminals 9-10: Relay switch for solenoid valve start/stop.
  • Terminals 1-2: Switch function for regulation start/stop. If no switch is connected, terminals 1 and 2 must be short-circuited.

Application Dependent Connections

  • Terminals 21-22: Pt 1000 sensor for air temperature measurement (S3).
  • Terminals 12-13: Alarm relay. A connection exists between 12 and 13 during alarm situations or when the controller is powered off.
  • Terminals 18-19: Current signal from other regulation (Ext.Ref.).
  • Terminals 23-24: Supply voltage to actuator AKV/TQ.
  • Terminals 2-5: Current output for displaying superheat or air temperature, or for signaling a slave module, or for controlling an ICM valve.
  • Terminals 3-4: Data communication. This connection is only used if a data communication module is installed. Proper installation of the data communication cable is crucial. Refer to separate literature RC8AC for details.

Wiring diagrams are provided for ICAD units and AKV actuators, illustrating typical connections. A graph shows the recommended cable cross-section (mm²) versus cable length (m) for a 24V supply, indicating that longer cable runs require thicker wires (e.g., 0.75 mm² for <25m, 1.5 mm² for 25-75m, 2.5 mm² for >75m).

Operation and Controls

The display shows values with three digits and can be set to display temperature in °C or °F.

Front panel LEDs indicate the status of the controller:

  • The upper LED shows the valve's opening degree (short pulse for low liquid flow, long pulse for high liquid flow).
  • The next LED indicates when the controller is calling for refrigeration.
  • The three lower LEDs flash if there is an error. Error codes can be viewed on the display, and alarms can be canceled by briefly pressing the upper button.

The two buttons on the unit are used for navigation and adjusting settings. Pressing the upper button for a few seconds accesses the menu. Once in the menu, parameters can be selected and values changed by pressing the buttons. Pressing both buttons simultaneously saves the changes.

Examples of Operation:

  • Setting Set-point: Press both buttons, use one button to select the value, then press both buttons again to confirm.
  • Setting Other Menus: Press the upper button to cycle through parameters, use one button to find the desired parameter, press both buttons to view its value, use one button to change the value, and press both buttons to save.

Factory settings can be restored by disconnecting power, holding both buttons, and reconnecting power.

Menu Overview and Parameters

The controller offers a comprehensive menu for configuration and monitoring. Key parameters include:

FunctionParameterMin.Max.Factory Setting
Normal displayDefine view in o17---
ReferenceSet the required set point-60°C50°C10
Differentialr010.1 K20.0 K2.0
Units (0=°C+bar / 1=°F+psig)r05010
External contribution to the referencer06-50 K50 K0
Correction of signal from S2r09-50.0 K50.0 K0.0
Correction of signal from S3r10-50.0 K50.0 K0.0
Start/stop of refrigerationr12OFFOn1
Define thermostat function (0=no, 1=On/off)r14010
Alarm: Upper deviationA013.0 K20 K5.0
Alarm: Lower deviationA021 K10 K3.0
Alarm's time delayA030 min.90 min.30
Regulating parameters: P: Amplification factor Kpn040.5203.0
I: Integration time Tnn0530 s600 s120
D: Differentiation time Td (0=off)n060 s90 s0
Max. value of superheat referencen092 K50 K6
Min. value of superheat referencen101 K12 K4
MOP (max.=off)n110.0 bar60 bar60
Period time (AKV/A valve only)n133 s10 s6
Stability factor for superheat controln180105
Damping of amplification around referencen190.21.00.3
Amplification factor for superheatn200.010.00.4
Definition of superheat control (1=MSS, 2=LOADAP)n21121
Value of min. superheat reference for loads <10%n221152
Standby temp. (valve closed, TQ only)n260 K20 K0
Standby temp. (valve open, TQ only)n27-15 K70 K20
Max. opening degreen320100100
Min. opening degreen3301000
Miscellaneous: Controller's addresso03*0119-
ON/OFF switch (service-pin message)o04*---
Define valve and output signal (0:Off, 1:TQ AO 0-20mA, 2:TQ AO 4-20mA, 3:AKV AO 0-20mA, 4:AKV AO 4-20mA, 5:AKV AO EKC 347-SLAVE, 6:ICM AO 0-20mA/ICM OD%, 7:ICM AO 4-20mA/ICM OD%)o09070
Define input signal on analog input AIA (0:no signal, 1:Temp setpoint 0-20mA, 2:Temp setpoint 4-20mA, 3:Superheat ref. displacement 0-20mA, 4:Superheat ref. displacement 4-20mA)o10040
Set supply voltage frequencyo1250 Hz60 Hz0
Select display for "normal picture" (o17)o17131
Manual control of outputs (OFF: no manual control, 1: Relay ON, 2: AKV/A output ON, 3: Alarm relay activated)o18off3Off
Working range for pressure transmitter - min. valueo20-1 bar60 bar-1.0
Working range for pressure transmitter - max. valueo21-1 bar60 bar12
Set temp. value or opening degree for min. output signal (0 or 4 mA) (for 009 function, AKV/TQ only)o27-70°C160°C-35
Set temp. value or opening degree for max. output signal (20 mA) (for 009 function, AKV/TQ only)o28-70°C160°C15
Refrigerant setting (1=R12, 2=R22, ..., 35=R438A)o300350

Start-up and Troubleshooting

Start-up Procedure:

  1. Ensure the external ON/OFF switch is off.
  2. Follow the menu overview to set parameters.
  3. Turn on the external switch to start regulation.
  4. Monitor room temperature or superheat on the display. A current signal representing the display can be output on terminals 2 and 5 for data logging.

If Superheat Fluctuates:

If the system is stable, factory settings usually provide good regulation. Fluctuations may indicate superheat parameters are too low. Adjust n09, n10, n18 (adaptive superheat) or n09, n10, n22 (load-defined superheat). Alternatively, regulation parameters might not be optimal.

  • If oscillation time (Tp) > integration time (Tn): Increase Tn by 20%, wait for stability, or reduce Kp by 20% if oscillation persists.
  • If oscillation time (Tp) < integration time (Tn): Reduce Kp by 20%, wait for stability, or repeat if oscillation persists.

Excessive Underswing at Start-up:

  • For AKV valves: Adjust n22 slightly up and/or n04 slightly down.
  • For TQ valves: Adjust n26 slightly down.

Controller Messages:

  • E1: Fault in controller.
  • E11: Valve actuator temperature out of range.
  • E15: S2 sensor cut-out.
  • E16: S2 sensor short-circuited.
  • E17: Error message.
  • E18: S3 sensor cut-out.
  • E19: S3 sensor short-circuited.
  • E20: Input signal on terminals 18-19 out of range.
  • A1: High-temperature alarm.
  • A2: Low-temperature alarm.
  • A11: No refrigerant selected.
  • Input signal on terminals 14-15 (PO signal) out of range.
Models: 315A, 084B7086, EKC 315A Industrial Refrigeration Superheat Controller, EKC 315A, Industrial Refrigeration Superheat Controller, Refrigeration Superheat Controller, Superheat Controller

File Info : application/pdf, 12 Pages, 383.40KB

PDF preview unavailable. Download the PDF instead.

AN12368642832001-000701 Danfoss A/S GPL Ghostscript 10.03.1

Related Documents

Preview Danfoss EKC 102C1 Temperature Controller: Official Instructions and Guide
Explore the official instructions for the Danfoss EKC 102C1 temperature controller. This guide covers setup, parameter configuration, operation, and troubleshooting for refrigeration and air conditioning systems.
Preview Danfoss EKC 202 Series User Guide: Temperature Control for Refrigeration
This user guide details the Danfoss EKC 202 series controllers, designed for precise temperature management in refrigeration appliances and cold rooms. It covers features like defrost control, fan operation, alarms, and connectivity within ADAP-KOOL® systems.
Preview Danfoss EKC 367: Instructions and Operation Guide
Comprehensive instructions and operational guide for the Danfoss EKC 367 electronic refrigeration controller, covering installation, connections, parameters, and troubleshooting.
Preview Danfoss AK-CC 550B Instructions: Refrigeration Controller Guide
Comprehensive instructions and technical guide for the Danfoss AK-CC 550B refrigeration controller, covering identification, dimensions, principle, applications, connections, operation, parameters, and fault messages.
Preview Danfoss EKC 201C Controller for Temperature Control - Manual
Technical manual detailing the features, operation, and specifications of the Danfoss EKC 201C temperature controller, designed for refrigeration appliances and supermarkets. Covers installation, functions, parameters, and troubleshooting.
Preview Danfoss EKC 223 Case Controller Installation Guide
This guide provides installation, operation, and technical data for the Danfoss EKC 223 case controller, designed for commercial air-conditioning and refrigeration applications.
Preview Danfoss EKC 361 Media Temperature Controller Installation Guide
Comprehensive installation guide for the Danfoss EKC 361 media temperature controller, covering electrical connections, operation, menu parameters, troubleshooting, and performance graphs.
Preview Danfoss EKE Series Superheat Controllers: EKE 1A, EKE 1B, EKE 1C Data Sheet
Explore the Danfoss EKE series superheat controllers (EKE 1A, EKE 1B, EKE 1C). This data sheet details features, specifications, applications, and technical information for advanced refrigeration and air conditioning control.