INSTALLATION MANUAL R-KEY-LT R-KEY-LT-P

PRELIMINARY WARNINGS

The word WARNING preceded by the symbol ⚠️ indicates conditions or actions that put the user's safety at risk. The word ATTENTION preceded by the symbol ? indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.

WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available via QR-CODE shown on page 1.

The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.

Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.

Documentation for R-KEY-LT and R-KEY-LT-P is available.

CONTACT INFORMATION

SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY; Tel. +39.049.8705359 - Fax +39.049.8706287

Technical supportsupport@seneca.it
Product informationsales@seneca.it

This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised. The content of this document corresponds to the described products and technologies. Stated data may be modified or supplemented for technical and/or sales purposes.

Document ID: MI00472-3-EN

MODULE LAYOUT

Dimensions: Height 110mm, Width 53mm, Depth 32mm.

Weight: 80g. Enclosure: UL94-V0 self-extinguishing PC/ABS material, black.

SIGNALS VIA LED ON FRONT PANEL

LEDSTATUSLED meaning
PWROnThe device is powered with assigned IP
PWRFlashingIP not assigned
TXFlashingData transmission on port RS232/RS485
RXFlashingData receipt on port RS232/RS485
ETH ACT (Yellow)FlashingPacket transit on Ethernet port
ETH LNK (Green)FlashingEthernet port connected
COM (R-KEY-LT-P version only)FlashingProfinet communication active
COM (R-KEY-LT-P version only)OffNo Profinet communication
COM+PWR (R-KEY-LT-P version only)FlashingWebserver active / Profinet not active

DEVICE CONFIGURATION

The device can be fully set up via an integrated web server. Product programming and configuration tools, as well as all manuals, can be downloaded from a web address accessible via QR code. For further information, refer to the USER MANUAL.

FACTORY IP ADDRESS

The default module IP address is static: 192.168.90.101

WEB SERVER AND PROFINET MODE (R-KEY-LT-P)

The device operates in Profinet mode by default, where configuration is done via Easy Setup 2 software. To access the internal web server, the device must be switched to Webserver mode using Easy Setup2 or Seneca Device Discovery software. The operating mode can be changed by pressing the side button.

To force webserver mode:

To force Profinet mode:

WEB SERVER

To access the maintenance Web Server using the factory IP address, use the following credentials:

Username: admin; Password: admin

Note: For the R-KEY-LT-P version, webserver mode must be activated first.

⚠️ CAUTION: DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.

TECHNICAL SPECIFICATIONS

CategoryDetails
CERTIFICATIONS[CE] certification. URL for declaration: https://www.seneca.it/products/r-key-lt/doc/CE_declaration. [UL Listed] 3LUT.
INSULATION1500 Vac
POWER SUPPLYVoltage: 11 ÷ 40Vdc; 19 ÷ 28Vac; 50 ÷ 60 Hz, max absorption: 1W
ENVIRONMENTAL CONDITIONSTemperature: -25°C ÷ +65°C. Humidity: 30% ÷ 90% non condensing. Storage temperature: -30°C ÷ + 85°C. Protection rating: IP20 (not rated by UL).
ASSEMBLYDIN rail 35mm IEC EN60715, wall or panel with screws.
CPUARM 32 bit
OPERATING SYSTEMReal time multitasking
CONFIGURATIONConfiguration and FW update via webserver; Via DIP - SWITCH; Via EASY SETUP 2 configuration software.
CONNECTIONSRemovable 7-way screw terminals, 5 mm pitch, cable section up to 2.5 mm². Removable 2-way screw terminals, 5 mm pitch, cable section up to 2.5 mm².
COMMUNICATIONRJ45 connector for Ethernet cable.
ETHERNET PORTSRS232/RS485 on 1-7 terminal; maximum Baud rate 115k. 1 x 100Mbit Ethernet port with auto switch.

DIP - SWITCH SETTINGS

⚠️ WARNING: The DIP-switch settings are read only at boot time. At each change, perform a restart.

SW1 DIP-SWITCH:

Through DIP-SWITCH-SW1, the polarization of the bus relative to the RS485 port can be set:

DESCRIPTIONDIP 1DIP 2
To polarize the bus on RS485, both SW1 DIP switch selectors must be set to ON[ON][ON]
NOT to polarize the bus on RS485, both SW1 DIP switch selectors must be set to OFF[OFF][OFF]

SW2 DIP-SWITCH:

Through DIP-SWITCH-SW2, the IP configuration of the device can be set:

DESCRIPTIONDIP 1DIP 2
To obtain the configuration from the Flash memory, both SW1 DIP switch selectors must be set to OFF[OFF][OFF]
To reset the device to factory settings, both SW1 DIP switches must be set to ON[ON][ON]
To force the device's IP address to the standard value of SENECA Ethernet products: 192.168.90.101[ON][OFF]
Reserved[OFF][ON]

ELECTRICAL CONNECTIONS

⚠️ CAUTION: Switch the module off before connecting inputs and outputs. To meet electromagnetic immunity requirements:

  • Use shielded signal cables.
  • Connect the shield to a preferential instrumentation earth system.
  • Separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc.).

⚠️ CAUTION: Use only copper or copper-coated aluminium or AL-CU or CU-AL conductors.

POWER SUPPLYRS485 SERIAL PORTRS232 SERIAL PORT
Vac / Vdc 8A(+) 1GND 3
Vac / Vdc 9B(-) 2RTS 4
GND 3Tx 5
CTS 6
Rx 7

The power supply source must be protected from any module malfunctions using appropriately-sized safety fuses.

⚠️ CAUTION: The device can only be powered by a power supply with a limited energy circuit 40Vdc / 28Vac max in output according to CAN/CSA-C22.2 No.61010-1-12 / UL Std.No.61010-1 (3rd Edition) chapter 6.3.1/6.3.2 and 9.4 or class 2 according to CSA 223/UL1310.

⚠️ CAUTION: These are open type devices intended for installation in a final casing/panel that offers mechanical protection and protection against the spread of fire.

Models: R-KEY-LT, R-KEY-LT-P, Compact Industrial ModBUS Gateway

PDF preview unavailable. Download the PDF instead.

Installation-Manual-R-KEY-LT-R-KEY-LT-P Adobe PDF Library 15.0 Adobe InDesign 16.3 (Windows)

Related Documents

Preview SENECA R-KEY-LT / R-KEY-LT-P Installation Manual - Industrial Gateway
Comprehensive installation manual for SENECA R-KEY-LT and R-KEY-LT-P industrial gateways. Covers setup, configuration, technical specifications, and electrical connections.
Preview SENECA Industrial Gateways: Protocol Converters for R-KEY & Z-KEY Models
Explore SENECA's range of Industrial Gateways, including R-KEY and Z-KEY models. These protocol converters facilitate seamless data transfer between various industrial networks and fieldbuses, supporting protocols like Modbus, Profinet, Ethernet/IP, OPC UA, and IEC 61850.
Preview Seneca KEY Series Gateways User Manual: OPC-UA / Modbus RTU&TCP
Comprehensive user manual for Seneca's KEY series multiprotocol gateways, detailing configuration, operation, and features for OPC-UA and Modbus communication protocols. Covers hardware, firmware, operating modes, web server access, and Modbus register information.
Preview SENECA KEY Series Multiprotocol Gateways User Manual - IEC 61850 & Modbus
Explore the SENECA KEY series multiprotocol gateways with this user manual. Learn about IEC 61850 and Modbus protocol conversion, device configuration, FLEX technology, firmware updates, and more for industrial automation.
Preview SENECA Gateway Industriali: Convertitori di Protocollo R-KEY e Z-KEY
Scopri la gamma di Gateway Industriali SENECA, convertitori di protocollo R-KEY e Z-KEY. Soluzioni flessibili per la comunicazione tra reti industriali, supportando Modbus, Profinet, Ethernet/IP, OPC UA e IEC 61850.
Preview Manuale Utente Z-KEY MBUS R-KEY MBUS - SENECA
Manuale utente per i gateway SENECA Z-KEY MBUS e R-KEY MBUS, che convertono protocolli MODBUS (TCP-IP / RTU) in M-BUS (Meter Bus). Include guide alla configurazione, connessione, gestione dei dispositivi e protocolli supportati.