Sterling W-A Convector
Submittal Specification
Flat Top Cabinet Wall Mounted
Specifications
Front and Liner
- STYLE: Front Outlet
- OUTLET: Stamped Louvers, Pencil Proof
Lengths
- 20" thru 64" in 4" Increments
Material (Cabinet Front and Liner)
- 18 Ga./20 Ga. CRS (Std)
- 18 Ga./18 Ga. CRS (Opt'l)
- 16 Ga./20 Ga. CRS (Opt'l)
- 16 Ga./18 Ga. CRS (Opt'l)
- 16 Ga./16 Ga. CRS (Opt'l)
- 14 Ga./20 Ga. CRS (Opt'l)
- 14 Ga./18 Ga. CRS (Opt'l)
- 14 Ga./16 Ga. CRS (Opt'l)
- 14 Ga./14 Ga. CRS (Opt'l)
- 18 Ga./20 Ga. SS (Opt'l)
- 18 Ga./18 Ga. SS (Opt'l)
- 16 Ga./20 Ga. SS (Opt'l)
- 16 Ga./18 Ga. SS (Opt'l)
- 16 Ga./16 Ga. SS (Opt'l)
Finish
- Baked Powder Prime
- Baked Powder Color (Opt'l)
Coil and Connections
Element/Coil
Bronze Header 3/4" NPT w/Copper Tube/Alum Fins (Mechanically Expanded).
Header Connections
- Single Header Both Ends (Std)
- Single Inlet 1 End / Dual Inlet 1 End (Opt'l)
- Dual Inlet Both Ends (Opt'l)
Piping Knockout
- (Opt'l)
4" End Pockets
- LH (Opt'l)
- RH (Opt'l)
- Both Ends (Opt'l)
Perforated Front
- Consult Factory
- 16 Ga. (Opt'l)
- 14 Ga. (Opt'l)
Optional Accessories
Damper
- Damper Blades Factory Installed
- Knob Damper (Opt'l)
- Tamper Resistant (Opt'l)
Access Doors
- (Opt'l)
Insulation
- Back Only (Opt'l)
- Back, Sides, Top (Opt'l)
Model Dimensions - Type W-A
Dimensions (D, L, H, B, J) for Type W-A models. Note: When adding end pockets, liner and front length increase.
Model Series | D (in) | L (in) | H (in) | B (in) | J (in) |
---|---|---|---|---|---|
4xx-14 | 14 | 20-64 (4" increments) | 14 | 2-1/8 | 2 |
4xx-18 | 18 | 20-64 (4" increments) | 18 | 2-1/8 | 2 |
4xx-20 | 20 | 20-64 (4" increments) | 20 | 2-1/8 | 2 |
4xx-26 | 26 | 20-64 (4" increments) | 26 | 2-1/8 | 2 |
4xx-32 | 32 | 20-64 (4" increments) | 32 | 2-1/8 | 2 |
6xx-14 | 14 | 20-64 (4" increments) | 14 | 3-1/8 | 4 |
6xx-18 | 18 | 20-64 (4" increments) | 18 | 3-1/8 | 4 |
6xx-20 | 20 | 20-64 (4" increments) | 20 | 3-1/8 | 4 |
6xx-26 | 26 | 20-64 (4" increments) | 26 | 3-1/8 | 4 |
6xx-32 | 32 | 20-64 (4" increments) | 32 | 3-1/8 | 4 |
8xx-14 | 14 | 20-64 (4" increments) | 14 | 4-1/8 | 6 |
8xx-18 | 18 | 20-64 (4" increments) | 18 | 4-1/8 | 6 |
8xx-20 | 20 | 20-64 (4" increments) | 20 | 4-1/8 | 6 |
8xx-26 | 26 | 20-64 (4" increments) | 26 | 4-1/8 | 6 |
8xx-32 | 32 | 20-64 (4" increments) | 32 | 4-1/8 | 6 |
Diagram Description: The diagram illustrates the physical layout and key dimensions of the W-A convector, including overall length, riser centers, header placement, and depth indicators. Notes indicate that end pockets increase overall length but not coil length.
Steam Ratings (BTU/H)
Ratings are provided for 215°F water temperature at 65°F Entering Air Temperature (EAT). Correction factors for other temperatures and pressures are available in separate tables.
Depth (in) | Front Outlet, Wall Mounted, Nominal Height - TYPE W-A | ||||
---|---|---|---|---|---|
14" | 18" | 20" | 26" | 32" | |
4 | 2495 | 2830 | 2930 | 3120 | 3265 |
3145 | 3625 | 3720 | 3985 | 4150 | |
3815 | 4345 | 4465 | 4775 | 5040 | |
4490 | 5110 | 5255 | 5665 | 5950 | |
5160 | 5880 | 6025 | 6505 | 6865 | |
5810 | 6600 | 6790 | 7320 | 7730 | |
44 | 6480 | 7390 | 7560 | 8160 | 8640 |
48 | 7105 | 8110 | 8350 | 8975 | 9530 |
52 | 7800 | 8855 | 9070 | 9745 | 10345 |
56 | 8450 | 9625 | 9865 | 10630 | 11305 |
60 | 9120 | 10345 | 10610 | 11400 | 12120 |
64 | 9790 | 11135 | 11400 | 12290 | 13080 |
20 | 3625 | 4250 | 4390 | 4850 | 5040 |
24 | 4560 | 5375 | 5570 | 6170 | 6410 |
28 | 5520 | 6480 | 6670 | 7370 | 7655 |
32 | 6480 | 7610 | 7870 | 8690 | 9025 |
36 | 7390 | 8690 | 9025 | 9935 | 10345 |
40 | 8375 | 9815 | 10200 | 11230 | 11665 |
44 | 9290 | 10920 | 11350 | 12480 | 12985 |
48 | 10250 | 12025 | 12455 | 13705 | 14305 |
52 | 11185 | 13105 | 13535 | 14905 | 15505 |
56 | 12145 | 14230 | 14735 | 16225 | 16920 |
60 | 13055 | 15310 | 15840 | 17425 | 18145 |
64 | 14040 | 16440 | 17065 | 18770 | 19585 |
20 | 4535 | 5040 | 5135 | 5570 | 5810 |
24 | 5760 | 6360 | 6575 | 7105 | 7465 |
28 | 6960 | 7680 | 7895 | 8520 | 8930 |
32 | 8185 | 9025 | 9310 | 10055 | 10560 |
36 | 9385 | 10390 | 10705 | 11545 | 12120 |
40 | 10630 | 11760 | 12070 | 13055 | 13655 |
44 | 11830 | 13055 | 13440 | 14545 | 15190 |
48 | 12935 | 14400 | 14810 | 16080 | 16800 |
52 | 14230 | 15670 | 16105 | 17425 | 18145 |
56 | 15505 | 17090 | 17570 | 19010 | 19850 |
60 | 16655 | 18335 | 18840 | 20375 | 21215 |
64 | 17880 | 19750 | 20330 | 21960 | 22895 |
Correction Factors
Table 3: Convector BTU Correction Factors (Temperature)
Correction factors based on Average Water Temperature and Entering Air Temperature (Standard conditions: 215°F water, 65°F EAT).
AVERAGE WATER TEMPERATURE (°F) | ENTERING AIR TEMPERATURE (°F) (STD) | ||||
---|---|---|---|---|---|
55° | 60° | 65° | 70° | 75° | |
100° | 0.17 | 0.14 | 0.12 | 0.09 | 0.07 |
110° | 0.23 | 0.20 | 0.17 | 0.14 | 0.12 |
120° | 0.29 | 0.26 | 0.23 | 0.20 | 0.17 |
130° | 0.35 | 0.32 | 0.29 | 0.26 | 0.23 |
140° | 0.43 | 0.39 | 0.35 | 0.32 | 0.29 |
150° | 0.50 | 0.46 | 0.43 | 0.39 | 0.35 |
160° | 0.58 | 0.54 | 0.51 | 0.47 | 0.43 |
170° | 0.67 | 0.63 | 0.58 | 0.54 | 0.51 |
180° | 0.76 | 0.71 | 0.67 | 0.63 | 0.58 |
190° | 0.85 | 0.81 | 0.76 | 0.71 | 0.67 |
200° | 0.95 | 0.90 | 0.85 | 0.81 | 0.76 |
210° | 1.05 | 1.00 | 0.95 | 0.90 | 0.85 |
215° (STD) | 1.10 | 1.05 | 1.00 | 0.95 | 0.90 |
220° | 1.15 | 1.10 | 1.05 | 1.00 | 0.95 |
230° | 1.26 | 1.20 | 1.15 | 1.10 | 1.05 |
240° | 1.37 | 1.32 | 1.26 | 1.21 | 1.15 |
250° | 1.47 | 1.43 | 1.37 | 1.32 | 1.27 |
Table 4: Correction Factors for Steam Pressures Other Than 1 PSI Gauge
Apply factors shown above to the ratings shown on the 215°F ratings page. Maximum recommended operating pressure is 150 PSIG, (365.9°F). For conversion from steam to hot water, use correction factors shown in Table 3.
PRESSURE PSI GAUGE | 5 | 10 | 15 | 20 | 25 | 50 |
---|---|---|---|---|---|---|
FACTOR | 1.12 | 1.25 | 1.36 | 1.46 | 1.56 | 1.93 |
BTU PER SQ. FT. | 269 | 301 | 327 | 351 | 374 | 463 |
Table 5: Correction Factors for Access Doors
Factors for Free Standing, Non-Recessed Non-Standard Access Door Locations and Semi-Recessed or Fully Recessed Non-Standard Access Door Locations. Derating factors do not apply to units with end pockets.
Length | Free Standing, Non-Recessed Non-Standard Access Door Locations | Semi-Recessed or Fully Recessed Non-Standard Access Door Locations | ||||||
---|---|---|---|---|---|---|---|---|
3 or 4 | 3 & 4 | 5 or 6 | 5 & 6 | 3 or 4 | 3 & 4 | 5 or 6 | 5 & 6 | |
20" | 0.940 | 0.880 | 0.820 | 0.650 | 0.975 | 0.950 | 0.925 | 0.850 |
24" | 0.950 | 0.910 | 0.860 | 0.720 | 0.980 | 0.960 | 0.940 | 0.880 |
28" | 0.960 | 0.920 | 0.890 | 0.770 | 0.982 | 0.968 | 0.948 | 0.902 |
32" | 0.970 | 0.940 | 0.890 | 0.800 | 0.985 | 0.972 | 0.955 | 0.918 |
36" | 0.970 | 0.940 | 0.920 | 0.830 | 0.988 | 0.975 | 0.962 | 0.925 |
40" | 0.970 | 0.950 | 0.920 | 0.850 | 0.990 | 0.978 | 0.970 | 0.932 |
44" | 0.980 | 0.950 | 0.930 | 0.860 | 0.990 | 0.980 | 0.970 | 0.940 |
48" | 0.980 | 0.960 | 0.940 | 0.880 | 0.990 | 0.982 | 0.970 | 0.948 |
52" | 0.980 | 0.960 | 0.950 | 0.890 | 0.992 | 0.985 | 0.978 | 0.955 |
56" | 0.980 | 0.960 | 0.950 | 0.890 | 0.992 | 0.985 | 0.978 | 0.955 |
60" | 0.980 | 0.970 | 0.950 | 0.900 | 0.992 | 0.985 | 0.978 | 0.955 |
64" | 0.980 | 0.970 | 0.950 | 0.910 | 0.992 | 0.988 | 0.978 | 0.962 |
Pressure Loss (Hot Water)
Pressure loss in feet of water for different flow rates (GPM) in 4", 6", and 8" models. Used for determining pressure head requirements. Based on 64" length units, but applicable to shorter units as most loss is due to headers.
WATER FLOW IN GPM | PRESSURE LOSS IN FEET OF WATER | ||
---|---|---|---|
4 INCH MODELS | 6 INCH MODELS | 8 INCH MODELS | |
.25 | 0.044 | -- | -- |
.50 | 0.160 | 0.070 | 0.046 |
1 | 0.597 | 0.270 | 0.167 |
2 | 2.220 | 1.047 | 0.616 |
3 | -- | 2.260 | 1.367 |
4 | -- | 3.793 | 2.380 |
5 | -- | -- | 3.673 |
Flow Rate Corrections
Table 7: Gallons Per Minute of Hot Water Required
This graph illustrates the relationship between Gallons Per Minute (GPM) and MBH (Thousands of BTU per Hour) for various temperature drops (10°F, 20°F, 30°F, 40°F).
Table 8: Output-Flow Rate Corrections
Shows MBH which result at specific water temperature drops and minimum water flow rates which are required to maintain turbulent flow within element tubes. Minimum flow rate is 0.25 Ft./Sec.
Convector Depth | Tubes per Element | GPM | MBH Based on T.D. & Min. Flow Rate | |||
---|---|---|---|---|---|---|
10TD | 20TD | 30TD | 40TD | |||
4" | 2 | 0.15 | 0.750 | 1.500 | 2.250 | 3.000 |
6" | 3 | 0.225 | 1.125 | 2.250 | 3.375 | 4.500 |
8" | 4 | 0.30 | 1.500 | 3.000 | 4.500 | 6.000 |
Convector Coil Details
Coil construction features 2, 3, or 4 tube elements with copper tubes and aluminum fins, mechanically bonded at 6 fins per inch. Fin height is 2-1/2 inches.
Coil dimensions: 4" depth has 2 tubes (3-3/4" width), 6" depth has 3 tubes (5-3/4" width), 8" depth has 4 tubes (7-3/4" width).
Diagram Description: Illustrates the convector coil with details on tube elements, header connections (3/4" NPT typical), vent plug, and hanger attachment points.
Note: When ordering convectors with end pockets, the overall physical length increases by 4" for each end pocket, while the coil length remains standard.
Manufacturer Information
Sterling Commercial Hydronic Products
260 North Elm St., Westfield, MA 01085
(413) 564-5535
Website: www.sterlingheat.com