CMeX10S-13S User Manual
DIN-mounted M-Bus master for 32-256 M-Bus unit loads
1 Document Notes
All information in this manual, including product data, diagrams, charts, etc. represents information on products at the time of publication, and is subject to change without prior notice due to product improvements or other reasons. It is therefore recommended that customers contact Elvaco AB for the latest product information before purchasing a CMeX10 Series product.
The documentation and product are provided on an “as is” basis only and may contain deficiencies or inadequacies. Elvaco AB takes no responsibility for damages, liabilities or other losses by using this product.
1.1 Copyright and Trademark
© 2014, Elvaco AB. All rights reserved. No part of the contents of this manual may be transmitted or reproduced in any form by any means without the written permission of Elvaco AB. Printed in Sweden.
CMeX10 Series is a trademark of Elvaco AB, Sweden.
1.2 Contacts
Elvaco AB Headquarter
Teknikgatan 18
434 37 Kungsbacka
SWEDEN
Phone: +46 300 30250
Fax: +46 300 18440
E-Mail: info@elvaco.com
Elvaco AB Technical Support
Phone: +46 300 434300
E-Mail: support@elvaco.se
Online: http://www.elvaco.com
2 Using this manual
2.1 Purpose and Audience
This manual provides information needed to mount, configure and use the CMeX10 Series product. It is intended for field engineers and developers.
2.2 Models
CMeX10, CMeX11, CMeX10S, CMeX11S, CMeX12S, CMeX13S
2.3 Additional and updated information
Latest documentation version is available on Elvaco web site at http://www.elvaco.com.
3 Introduction
3.1 Product configuration
Use the table below to find out the capabilities of your product.
Product name | Comments |
---|---|
CMeX10 | M-Bus master for up to 32 M-Bus slaves with IR-interface |
CMeX11 | M-Bus master for up to 64 M-Bus slaves with IR-interface |
CMeX10S | M-Bus master for up to 32 M-Bus slaves with IR-interface and RS232 interface |
CMeX11S | M-Bus master for up to 64 M-Bus slaves with IR-interface and RS232 interface |
CMeX12S | M-Bus master for up to 128 M-Bus slaves with IR-interface and RS232 interface |
CMeX13S | M-Bus master for up to 256 M-Bus slaves with IR-interface and RS232 interface |
Table 1 Product configuration
3.2 Capabilities
The CMeX10 Series makes it possible to expand your CMe Series with up to 256 extra M-Bus slaves. The CMeX10 Series features standard M-Bus over IR communication and is equipped with the unique IR Pass Through function, making the product series stackable. The modular and expandable design allows the customer to select a suitable level based on price and functionality.
The CMeX10S, CMeX11S, CMeX12S and CMeX13S also add the RS232 interface to use with any standard RS232 communicating device.
3.3 Applications
The CMeX10 Series fits into almost any kind of meter collection system. For example:
- With CMe Series to expand your M-Bus master to handle up to 256 M-Bus slaves
- Standalone M-Bus master from RS232 to M-Bus 2-wire
- Split M-Bus 2-wire bus between two M-Bus masters with galvanic isolation using the IR- Pass Through
3.4 Overview CMeX10, CMeX11
This section describes the physical overview of the CMeX10 and CMeX11 models.
Top View Features:
- 4. DIN-rail lock: Mechanism for mounting and demounting from a DIN-rail.
- 6. M-Bus out: Terminal block for M-Bus output connections.
- 5. IR interface: Infrared communication interface.
Front View Features:
- 8. Power supply L: Terminal for mains supply Line.
- 9. Power supply N: Terminal for mains supply Neutral.
- 10. Power LED (Green): Indicates mains power status.
- 11. Error LED (Red): Indicates error status on the M-Bus bus.
- 12. Serial number: Label displaying the product's serial number.
- 13. RX LED (Yellow): Indicates incoming data from M-Bus slaves.
- 14. TX LED (Yellow): Indicates outgoing data to M-Bus slaves.
Figure 1 CMeX10, CMeX11 Overview
3.5 Overview CMeX10S, CMeX11S, CMeX12S, CMeX13S
This section describes the physical overview of the CMeX10S, CMeX11S, CMeX12S, and CMeX13S models.
Top View Features:
- 1. M-Bus out: Terminal block for M-Bus output connections.
- 2. M-Bus out: Additional terminal block for M-Bus output.
- 3. RS232 in: Connector for RS232 communication input.
- 4. DIN-rail lock: Mechanism for mounting and demounting from a DIN-rail.
- 5. IR interface: Infrared communication interface.
- 6. M-Bus out: Terminal block for M-Bus output connections.
- 7. Ground: Terminal for ground connection.
Front View Features:
- 8. Power supply N: Terminal for mains supply Neutral.
- 9. Power supply L: Terminal for mains supply Line.
- 10. Power LED (Green): Indicates mains power status.
- 11. Error LED (Red): Indicates error status on the M-Bus bus.
- 12. Serial number: Label displaying the product's serial number.
- 13. RX LED (Yellow): Indicates incoming data from M-Bus slaves.
- 14. TX LED (Yellow): Indicates outgoing data to M-Bus slaves.
Figure 2 CMeX10S, CMeX11S, CMeX12S, CMeX13S Overview
4 Physical Installation
This chapter covers the physical installation of the CMeX10 Series.
4.1 Mounting
The product should be mounted on a DIN-rail. The DIN-lock (4) on the bottom is used to mount and demount the unit from the DIN-rail. To fully comply with safety regulations, a DIN-rail enclosure must cover the terminals.
4.1.1 M-Bus 2-wire bus
M-Bus is a multi-drop 2-wire bus, with no polarity. Use a cable of area 0.25-1.5 mm², e.g. a standard telephone cable (EKKX 2x2x0.25). Connect the wiring to the screw connector (1, 2) or the push wire connector (6). Do not exceed the maximum cable length of 1000 meters (CMeX10, CMeX11) or 5000 meters (CMeX10S, CMeX11S, CMeX12S, CMeX13S).
⚠️ IMPORTANT
Please take the following in consideration:
- CMeX10 Series handles from 32 up to 256 slaves, be sure to use the correct model in your application. Overloading the bus will turn the ERR LED on and turn off the M-Bus bus.
- All connected M-Bus slave devices must have unique primary or secondary M-Bus addresses depending on addressing mode used.
4.1.2 IR Interface with ABB electricity meters or CMeX series modules
If the IR interface is to be used beside an ABB electricity meter or other CMeX module, the IR shield (5) should be removed. The CMeX10 Series should be mounted on the left side of the ABB electricity meter. There shall be no space between the CMeX10 Series product and the ABB electricity meters or other CMeX module. (Do not remove the shield if not used beside an ABB electricity meter or CMeX module.)
4.1.3 RS232 interface
Use the RS232 interface to use the CMeX10S, CMeX11S, CMeX12S and CMeX13S as an M-Bus master from RS232 to M-Bus 2-wire interface. Connect the RS232 interface to the RJ45 connector (3).
4.1.4 Power supply
The installation should be performed by a qualified electrician or an installer with the required knowledge. The power supply should be connected via a switch so the unit can be switched off during service work. The main supply should be connected to screw terminal (8) and screw terminal (9). Main supply voltage should be in the range of 100-240 VAC, 50/60 Hz. If ground signal is available, connect to screw terminal (7).
5 Application Description
This chapter covers general application description of the product.
5.1.1 Power on
When powered on, the CMeX10 Series product has an internal boot time before the product can be used. The boot time depends on the numbers of M-Bus slaves connected to the bus. The maximum boot time is approximately 10 seconds. During boot the ERR LED (red) is permanently on.
5.1.2 Normal operation/Idle
In normal operation, ERR LED (red) is off and PWR LED (green) is on. During normal communication, TX LED will flash when communication takes place from the DTE to the M-Bus 2-wire bus, and vice versa on the RX LED when M-Bus slave devices transmitting data back to the DTE.
5.1.3 Light collision detect (25 mA to 500 mA)
When the product detects a light slave collision, i.e. during secondary addressing, the product will send a break signal of 45 ms on the M-Bus 2-wire bus and to the right IR interface. The product will also send a break signal (45 ms), garbage characters (200 ms) and a break signal (45 ms) again to the DTE (left IR interface and RS232 interface). This procedure makes it possible to detect slave collisions in the DTE even if the used bearer does not support break signalling, i.e. TCP/IP communication.
5.1.4 Heavy collision detect and short circuit (>500 mA)
When the product detects a heavy collision, i.e. during secondary addressing or short circuit of the bus, the product will turn off the bus for 0.5 seconds. The product will also send a break signal of 45 ms to the right IR interface and a break signal (45 ms), garbage characters (200 ms) and a break signal (45 ms) again to the DTE (left IR interface and RS232 interface).
5.1.5 High idle current
When the M-Bus 2-wire bus is in idle state and the idle current is too high (depending on CMeX10 Series model), the product will turn off the M-Bus 2-wire interface and restart. The ERR LED (red) will be permanently on during this state. This procedure will continue until the idle current is within acceptable level for the CMeX10 Series model.
5.1.6 LED indications
5.1.6.1 PWR LED (green)
PWR LED (green) indicates mains supply.
Mode | Description | Visual |
---|---|---|
Permanently on | Mains power connected | [Solid Green Light] |
Permanently off | No mains power connected | [No Light] |
Table 2 PWR LED
5.1.6.2 ERR LED (red)
ERR LED (red) indicates M-Bus 2-wire bus status.
Mode | Description | Visual |
---|---|---|
Permanently on | Short circuit of the M-Bus 2-wire bus | [Solid Red Light] |
Permanently off | Normal mode, Idle | [No Light] |
Short flash every second | No M-Bus slaves connected | [Slow Red Flashing] |
Flashing for 1 second | M-Bus slave collision | [Fast Red Flashing] |
Table 3 ERR LED
5.1.6.3 RX LED (yellow)
RX LED (yellow) indicates communication from M-Bus slave to DTE.
Mode | Description | Visual |
---|---|---|
On/Flashing | M-Bus slave is transmitting data | [Flashing Yellow Light] |
Off | M-Bus slave is not transmitting data. | [No Light] |
Table 4 RX LED
5.1.6.4 TX LED (yellow)
TX LED (yellow) indicates communication from DTE to M-Bus slaves.
Mode | Description | Visual |
---|---|---|
On/Flashing | DTE is transmitting data | [Flashing Yellow Light] |
Off | DTE is not transmitting data | [No Light] |
Table 5 TX LED
6 Troubleshooting
6.1 All LEDs are permanently off
There is a problem with the supply voltage. Please verify 100-240 VAC. If the problem persists, the product may be malfunctioning.
6.2 Red LED is permanently on
This indicates an error on the M-Bus 2-wire bus. Please verify no short-circuit of the M-Bus bus. The voltage of the bus should be between 21 VDC and 42 VDC.
6.3 Cannot read connected M-Bus slaves
Please verify M-Bus status:
- Voltage over M-Bus slave device should be between 21 VDC and 42 VDC
- All M-Bus slave devices must have unique secondary or primary M-Bus addresses depending on addressing mode
- M-Bus slave device baud rates
6.4 TX LED is permanently on
When CMeX10 Series is stacked with other CMeX10 Series products and there is a short circuit on a product which is mounted on the left side of the issued product, the TX LED may be permanently on. Verify left side mounted products for no short circuit.
If you still have problems getting your CMeX10 Series running, please contact Elvaco support, see contact information section 1.2.
7 Technical specifications
7.1 Characteristics
Mechanics
Type | Value | Unit | Comments |
---|---|---|---|
Casing material | Polyamide | - | |
Protection class | IP20 | - | |
Dimensions (w x h x d) | CMeX10, CMeX11: 36 x 90 x 65 CMeX10S, CMeX11S, CMeX12S, CMeX13S: 108 x 90 x 65 | mm | CMeX10,CMeX11: 3 modules wide CMeX10S, CMeX11S, CMeX12S, CMeX13S: 7 modules wide |
Weight | CMeX10, CMeX11: 100 CMeX10S, CMeX11S, CMeX12S, CMeX13S: 220 | g | |
Connection M-Bus | CMeX10, CMeX11: Pin terminal CMeX10S, CMeX11S, CMeX12S, CMeX13S: Pin terminal and screw terminal | - | Pin terminal: Solid wire 0.6-0.8Ø mm Screw terminal: Cable 0-2.5 mm², 0.5 Nm tightening torque |
Mounting | DIN-mounted | - | |
Power supply | Screw terminal | - | Cable 0.75-2.5 mm², 0.5 Nm tightening torque |
Electrical
Type | Value | Unit | Comments |
---|---|---|---|
Nominal voltage | 100-240 | VAC | |
Voltage range | -10 to +10 | % | Of nominal voltage |
Frequency | 50/60 | Hz | |
Power consumption (max) | CMeX10, CMeX11: 6 CMeX10S, CMeX11S, CMeX12S, CMeX13S: 25 | W | |
Power consumption (nom) | CMeX10: 3,5 CMeX11: 6 CMeX10S, CMeX11S, CMeX12S, CMeX13S: 0,07 W x number of M-Bus slaves + 1,5 W | W | |
Power consumption M-Bus (max) | CMeX10: 50 CMeX11: 100 | mA | |
Installation category | CAT 3 | - |
Environmental
Type | Value | Unit | Comments |
---|---|---|---|
Operating temperature range | -30 to +55 | °C | |
Storage temperature range | -40 to +85 | °C | |
Operating humidity max | 80 | %RH | Temperatures up to 31 °C, decreasing linearly to 50%RH at 40 °C |
Pollution | Degree 2 | - | |
Operating altitude | 0-2000 | m | |
Usage | Indoor use only | - | Can be extended with IP67 enclosure for outdoor use |
User interface
Type | Value | Unit | Comments |
---|---|---|---|
Green LED | Power | - | |
Red LED | Error | - | |
Yellow LED | RX | - | |
Yellow LED | TX | - | |
Push button | Not used | - |
M-Bus
Type | Value | Unit | Comments |
---|---|---|---|
M-Bus standard | EN 13757 | - | |
M-Bus baud rate | 300, 2400 | Bit/s | |
Maximum connected M-Bus slaves | 32-256 | - | CMeX10: 32 M-Bus slaves CMeX11: 64 M-Bus slaves CMeX10S: 32 M-Bus slaves CMeX11S: 64 M-Bus slaves CMeX12S: 128 M-Bus slaves CMeX13S: 256 M-Bus slaves |
Maximum cable length | CMeX10, CMeX11: 1000 CMeX10S, CMeX11S, CMeX12S, CMeX13S: 5000 | m | |
Maximum load capacitance | 1.5 | uF | |
Light collision detect | >28 to 500 | mA | |
Heavy collision detect and short circuit | >500 | mA | |
RS232 to M-Bus | CMeX10, CMeX11: No CMeX10S, CMeX11S, CMeX12S, CMeX13S: Yes | - | |
Break signal length M-Bus 2-wire and right IR interface | 45 | ms | |
Break signal RS232 interface and left IR interface | - | ms | 45 ms break + garbage 200ms 45 ms break. This method is used for garbage generation when using other bearer than RS232, i.e. TCP/IP. |
Nominal voltage | CMeX10, CMeX11: 28 CMeX10S, CMeX11S, CMeX12S, CMeX13S: 42 | VDC | |
Maximum idle current | CMeX10: 55 CMeX11: 100 CMeX10S: 55 CMeX11S: 100 CMeX12S: 200 CMeX13S: 400 | mA | |
IR interface | Yes | - | |
Pass Through | Yes | - | Maximum of 4 CMeX10 Series products side by side |
Compatibility | All standard M-Bus meters, all ABB meters with IR interface, CMeX Series products | - |
Table 6 Technical specifications
8 Type approvals
CMeX10 Series is designed to comply with the directives and standards listed below.
Approval | Description |
---|---|
EMC | EN 61000-6-2, EN 61000-6-3 |
Safety | EN 61010-1, CAT 3 |
Table 7 Type approvals
9 Safety and environment
9.1 Safety precautions
The following safety precautions must be observed during all phases of the operation, usage, service or repair of any CMeX10 Series product. Users of the product are advised to convey the following safety information to users and operating personnel and to incorporate these guidelines into all manuals supplied with the product. Failure to comply with these precautions violates safety standards of design, manufacture and intended use of the product. Elvaco AB assumes no liability for customer's failure to comply with these precautions.
All instructions must be carefully read before CMeX10 Series is installed and used. They contain important information about how the product is used properly.
The installation of CMeX10 Series should not be started before the technical specifications are fully understood. The work must be performed in the order listed in this manual, and only by qualified personnel. The work must also be done in accordance with national electrical specifications and applicable local regulations.
In order to avoid the product being damaged by static electricity, an ESD wristband should be worn when handling the product.
To prevent hazardous power levels, the M-Bus 2-wire cable should be disconnected from the M-Bus master or other installations.
The product is intended for permanent connection to the M-Bus master through the M-Bus 2-wire cable. The M-Bus master's 2-wire cable must be properly dimensioned, and if necessary, it must be possible to disconnect the product from the 2-wire cable.
The labelling of the product may not be changed, removed or made unrecognizable.
The symbol indicates that the product belongs to insulation class II and no protective earth is necessary. The product is equipped with double insulation.
10 Document History
Version | Date | Description | Author |
---|---|---|---|
1.0 | 2010-01-25 | First release | David Vonasek |
2.0 | 2010-11-23 | Updated text and technical specifications | Ericha Bloom |
3.0 | 2011-09-23 | Updated with CMeX10S, CMeX11S, CMeX12S and CMeX13S. | Ericha Bloom |
4.0 | 2013-09-19 | Updated technical specifications | Ericha Bloom |
2014-06-13 | Updated section 4.1.4 and technical specifications | Ericha Bloom |
10.1 Document software and hardware appliance
10.1.1 CMeX10
Type | Version | Date | Comments |
---|---|---|---|
Hardware | R2A | 2010-01 | |
Software | 1.0.0 | 2010-01 |
10.1.2 CMeX11
Type | Version | Date | Comments |
---|---|---|---|
Hardware | R2A | 2010-01 | |
Software | 1.0.0 | 2010-01 |
10.1.3 CMeX10S
Type | Version | Date | Comments |
---|---|---|---|
Hardware | R4B | 2010-01 | |
Software | 1.0.5 | 2010-01 |
10.1.4 CMeX11S
Type | Version | Date | Comments |
---|---|---|---|
Hardware | R4B | 2010-01 | |
Software | 1.0.5 | 2010-01 |
10.1.5 CMeX12S
Type | Version | Date | Comments |
---|---|---|---|
Hardware | R4B | 2010-01 | |
Software | 1.0.5 | 2010-01 |
10.1.6 CMeX13S
Type | Version | Date | Comments |
---|---|---|---|
Hardware | R4B | 2010-01 | |
Software | 1.0.5 | 2010-01 |
11 References
11.1 References
[1] EN-13757-1, EN-13757-2, EN-13757-3 Communication System for meters and remote reading of meters – Part1, Part2 and Part3
11.2 Terms and Abbreviations
Abbreviation | Description |
---|---|
AMR | Automatic Meter Reading |
Product | In this document, CMeX10 Series product. |
11.3 Number representation
Decimal numbers are represented as normal number, i.e. 10 (ten). Hexadecimal numbers are represented with prefix 0x, i.e. 0x0A (ten) Binary numbers are represented with prefix 0b, i.e. 0b00001010 (ten)