ASCO SERIES 300 Dual Purpose Manual Transfer Switch

with Integrated Quick Connects (MTDQ) & (MGDQ)

J design, 150 - 600 Amperes

Operator's Manual

Document Number: 381333-494

Date: 06/2021

Safety Information

[DANGER]

DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious injury.

[WARNING]

WARNING is used in this manual to warn of a hazardous situation which, if not avoided, could result in death or serious injury.

[CAUTION]

CAUTION is used in this manual to warn of a hazardous situation which, if not avoided, could result in minor or moderate injury.

Rating Label

Refer to the outline and wiring drawings provided with the ASCO SERIES 300 MTDQ and MGDQ for all installation details.

The transfer switch contains a rating label to define operational limits. Refer to the label for specific values.

[WARNING]

Do not exceed the values on the rating label. Exceeding the rating can cause person injury or serious equipment damage.

Catalog Number Identification

A typical Catalog Number is shown below with its elements explained. The example is for a J-design, solid neutral, 3 poles, 400 amps, in Type 3R enclosure:

FrameProductNeutral CodePhase PolesAmperesVoltageGroup CodeEnclosure
J3MDTQ
3MGDQ
A
(A-solid
B-switched)
2
3
150
200
230
260
400
600
A 115
B 120
C 208
D 220
E 230
F 240
H 380
J 400
K 415
L 440
M 460
N 480
P 550
Q 575
R 600
00-No Accessory
0X-Accessory
0Z-Custom Accessory
M- Type 3R secure
S- Type 3RX secure (316)
SS

Installation

ASCO SERIES 300 Dual Purpose Manual Transfer Switches (MTDQ and MGDQ) are factory assembled and tested. Installation requires mounting, connecting power conductors and auxiliary control circuits (if required).

Supporting Foundation

The supporting foundation for the enclosure must be level and straight. Refer to the applicable enclosure outline drawing included with the transfer switch for all mounting details including door opening space.

If bottom cable entry is used, the foundation must be prepared so that the conduit stubs are located correctly. Refer to the enclosure outline drawing for specified area and location. Provide clearance between field installed conductors and parts of the transfer switch. When a concrete floor is poured, use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment.

Mounting

Refer to the outline drawing furnished with this switch and mount the SERIES 300 MTDQ and MGDQ according to details and instructions shown.

NOTICE

Protect the transfer switch from construction grit and metal chips to prevent malfunction or shortened life of the transfer switch.

Mount the SERIES 300 MTDQ or MGDQ to a rigid supporting structure. Level all mounting points by using flat washers behind the mounting hole locations to avoid distortion of the switch.

Line Connections

Refer to the wiring diagram provided with the transfer switch. All wiring must be made in accordance with the National Electrical Code and local codes.

[DANGER]

De-energize the conductors before making any line or auxiliary circuitry connections. Be sure that Source 1 and Source 2 line connections are in proper phase rotation. Place engine generator starting control(s) in the OFF position. Make sure all engine generator(s) are not in operation.

Testing Power Conductors

Do not connect the power conductors to the transfer switch until they are tested. Installing power cables in conduit, cable troughs and ceiling-suspended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor's strands. For this reason, after the cables are pulled into position, and before they are connected, they should be tested to verify that they are not defective or have been damaged during installation.

Connecting Power Conductors

After the power conductors have been tested, connect them to the appropriate terminals on the transfer switch as shown on the wiring diagram provided. Make sure the conductors being installed are suitable for use with the terminals provided on the transfer switch. Standard terminals are solderless, screw type and will accept the wire sizes and types listed on the drawings provided with the transfer switch. Be careful when stripping insulation from the cables; avoid nicking or ringing the conductor. Remove surface oxides from conductors by cleaning with a wire brush. When aluminum conductors are used, apply joint compound to them. Tighten terminals to the torque specified on the rating label.

Connecting Portable Generator

The Dual Purpose Manual Transfer Switch with Integrated Quick Connects contains 16 Series quick connects, providing a means for connecting a portable generator.

Figure 1 Description

Figure 1 shows the female receptacles for the quick connect system.

Quick connects for Portable Generator connection are located on the Source 2 (emergency) side of this MTDQ or MGDQ.

Making Quick Connect Connections

NOTICE

MGDQ variants provide a protection breaker between the portable generator 16 Series connectors and switch.

  1. Open MTDQ or MGDQ chamber door.
  2. Feed ground (green) cable through trap door located on the bottom of the unit.
  3. Complete the Connection Proper connection (See Figure 2):
    1. Grasp connector jacket and firmly insert cam connector into cam plug.
    2. Push on cam connector jacket until connector fully seats in cam plug.
    3. Rotate cam connector jacket counterclockwise until it stops.
  4. Complete the Neutral (white) connection Proper connection (See Figure 2):
    1. Grasp connector jacket and firmly insert cam connector into cam plug.
    2. Push on cam connector jacket until connector fully seats in cam plug.
    3. Rotate cam connector jacket counterclockwise until it stops.
  5. Complete the Phase (hot) connections:

    If generator and utility power phase rotation match:

    Generator HotASCO SERIES 300 MTDQ or MGDQ
    AA
    BB
    CC

    If generator and utility power phase rotation do NOT match:

    Generator HotASCO SERIES 300 MTDQ or MGDQ
    AB
    BA
    CC
  6. Proper connection (See Figure 1):
    1. Grasp connector jacket and firmly insert cam connector into cam plug.
    2. Push on cam connector jacket until connector fully seats in cam plug.
    3. Rotate cam connector jacket counterclockwise until it stops.
  7. Make sure all connections are right and secure.
  8. Close MTDQ or MGDQ chamber door, and secure allowing cables to exit cable trap door at the bottom of the unit.

Figure 2 Description

Figure 2 illustrates the process of inserting and securing the cam connectors for proper connection.

Disconnection of Quick Connects

  1. Verify that the MTDQ or MGDQ is in the OFF or Source 1 position.
  2. Disconnect the Phase (hot) connections, beginning with the furthest to the left.
  3. Disconnect the Neutral (white) connection.
  4. Disconnect the Ground (green) connections.

Connecting Load Bank

The Dual Purpose Manual Transfer Switch with Integrated Quick Connects contains a disconnect breaker and 16 Series quick connects, providing a means for connecting a Load Bank.

Figure 3 Description

Figure 3 shows a diagram of the female receptacles and the disconnect breaker (labeled ON/OFF 52LB) for load bank connections.

Quick connects for Load Bank are located on the Source 1 side of this MTDQ or MGDQ.

[DANGER]

Ensure circuit breaker is OFF and the connectors are locked out from Source power prior to connection.

  1. Open MTDQ OR MGDQ chamber door.
  2. Feed ground(green) cable through trap door located on the bottom of the unit.
  3. Complete the Connection Proper connection (See Figure 2):
    1. Grasp connector jacket and firmly insert cam connector into cam plug.
    2. Push on cam connector jacket until connector fully seats in cam plug.
    3. Rotate cam connector jacket counterclockwise until it stops.
  4. Figure 4 Description

    Figure 4 illustrates the process of inserting and securing the cam connectors for hot connections.

  5. Complete the hot connections connection Proper connection(See Figure 4):
    1. Grasp connector jacket and firmly Insert cam connector into cam plug.
    2. Push on cam connector jacket until connector fully seats in cam plug.
    3. Rotate cam connector jacket counterclockwise until it stops.
  6. Make sure all connections are right and secure.
  7. Close MTDQ OR MGDQ chamber door, and secure allowing cables to exit cable trap door at the bottom of the unit.

Disconnection of Quick Connects

  1. Ensure circuit breaker is OFF and the connectors are locked out from Source power prior to connection.
  2. Disconnect the Phase (hot) connections.
  3. Disconnect the Ground (green) connections.

Manual Operation Procedure

The SERIES 300 MTDQ and MGDQ have an external manual operating handle on the front left of the enclosure. Observe the switch position indicators - SOURCE 1, SOURCE 2 and DISCONNECTED. See Figures 5, 6, 7 and 8.

[WARNING]

Close the transfer switch enclosure door and tighten the screws before you use the manual operating handle.

  1. Operate the manual operating handle to DISCONNECT the load or transfer to SOURCE 1 or SOURCE 2. The selected switch position is indicated with a yellow indicator window. See Figures 5, 6, 7 and 8.
  2. Provision for a padlock (not provided) allows the manual operating handle to be locked in the SOURCE 1, SOURCE 2 or DISCONNECTED position.

Operation of the Transfer Switch

[DANGER]

Operate the transfer switch only with the enclosure door closed!

To Transfer from SOURCE 1 to DISCONNECTED:

Pull handle out. Turn handle counterclockwise until DISCONNECTED position is indicated.

Figure 5 Description

Figure 5 shows the DISCONNECTED (from SOURCE 1) position indicator.

To Transfer from DISCONNECTED to SOURCE 2:

Push handle in. Turn handle counterclockwise until SOURCE 2 position is indicated.

Figure 6 Description

Figure 6 shows the SOURCE 2 position indicator.

To Transfer from SOURCE 2 to DISCONNECTED:

Push handle in. Turn handle clockwise until DISCONNECTED position is indicated.

Figure 7 Description

Figure 7 shows the DISCONNECTED (from SOURCE 2) position indicator.

To Transfer from DISCONNECTED to SOURCE 1:

Pull handle out. Turn handle clockwise until SOURCE 1 position is indicated.

Figure 8 Description

Figure 8 shows the SOURCE 1 position indicator.

Testing & Service

Transfer Test

Operate the transfer switch monthly to ensure proper operation.

Preventive Maintenance

Reasonable care in preventive maintenance will insure high reliability and long life for the SERIES 300 MTDQ and MGDQ.

An annual preventive maintenance program is recommended.

ASCO Power Services, Inc. is ASCO Power Technologies service organization for the United States and Canada. Call 1-800-800-2726 (ASCO) to request a service call and information on preventive maintenance agreements.

Annual Inspection Checklist

[DANGER]

Hazardous voltage capable of causing shock, burns, or death is used in this switch!

PDF preview unavailable. Download the PDF instead.

MTS-QCDualPurpose-OM-100-600A Acrobat Distiller 21.0 (Windows)

Related Documents

Preview ASCO Series 300 Dual Purpose Manual Transfer Switch Operator's Manual
Operator's manual for the ASCO Series 300 Dual Purpose Manual Transfer Switch with Integrated Quick Connects (MTDQ) & (MGDQ), H design, 800 through 1200 Amperes. Covers installation, operation, testing, and maintenance.
Preview ASCO Series 300 Manual Transfer Switch (MTS) Operator's Manual - J-design, 150-600 Amperes
Operator's manual for ASCO Series 300 Manual Transfer Switches (MTS), J-design models rated 150 through 600 Amperes. Covers installation, manual operation, testing, and maintenance procedures for safe and effective use.
Preview ASCO Series 300 Manual Transfer Switch (MTS) Operator's Manual
Operator's manual for the ASCO Series 300 Manual Transfer Switch (MTS), H-design, covering installation, operation, testing, and maintenance. Includes catalog number identification and safety guidelines.
Preview ASCO 300 Series G3MGDQ Transfer Switch Wiring Diagrams and Specifications
Detailed wiring diagrams, connection schematics, and accessory specifications for ASCO 300 Series manually operated transfer switches (Type G3MGDQ), rated for 1000-3000 Amperes. Includes information on field connections, power poles, optional accessories, and wire run listings.
Preview ASCO Series 300 Automatic Transfer Switch Wiring Diagrams and Technical Data
Comprehensive technical document detailing wiring diagrams, control schematics, physical layout, and operator controls for ASCO Series 300 Automatic Transfer Switches (ATS) with Group 1 Controls, available in 600, 800, 1000, and 1200 Ampere ratings. Includes wire run lists and accessory information.
Preview ASCO Series 300 Manual Transfer Switch Operator's Manual
Operator's manual for the ASCO Series 300 Manual Transfer Switch (MTS), G-design, covering installation, operation, testing, and maintenance for models 1600 through 3000 Amperes.
Preview ASCO 300 Series Transfer Switches (E3ATS/E3NTS) 260 & 400 Amperes Outline
Outline drawing and dimensional data for ASCO 300 Series E3ATS/E3NTS automatic transfer switches, rated for 260 and 400 amperes, open type. Includes general notes, cabling notes, and mounting dimensions.
Preview ASCO 300 Series Transfer Switches Outline Drawing - 30-200 Amperes, Type 1 Enclosure
Detailed outline drawing for ASCO 300 Series Transfer Switches (D3ATS/D3NTS) rated 30-200 Amperes, Type 1 enclosure, including physical dimensions, general notes, and technical specifications.