ASCO 300 Series Transfer Switches (E3ATS/E3NTS) 260 & 400 Amperes Outline
Diagram Description
This document provides outline drawings and dimensional data for ASCO 300 Series E3ATS/E3NTS automatic transfer switches, rated for 260 and 400 amperes, in an open type configuration.
Page 1 presents a schematic of the transfer switch, illustrating 3-pole or 2-pole configurations with options for an overlapping neutral pole. It details terminal connections for Phase A, Phase B, Phase C, and Neutral (LN, NN), along with various dimensions and mounting hole locations. The drawing also indicates standard and maximum overhangs for components.
Page 2 focuses on control panel and power meter mounting data. It includes front and side views of the control panel mounting arrangement, specifying required clearances, such as a minimum of 6.00 inches [152.4mm] for door control. Detailed cutout and mounting hole dimensions are provided for different enclosure types (Type 1, Type 3R, 4, & 12) through specific details (A-1, B-1, A-2, B-2).
General Notes
- The standard switch configuration features top-mounted Load and Emergency sources and bottom-mounted Normal source.
- Neutral configurations include optional full-rated neutrals: solid (copper bus), switched neutral pole (available only on 2-pole units), or overlapping neutral pole.
- Standard terminal lugs are mechanical (screw type) AL/CU.
- Conductors should be connected to similarly marked phases of the Normal, Emergency, and Load connections.
- All internal connections are factory-made.
- Maintain an electrical clearance of 1.00 inch [25.4mm] between live metal parts and grounded metal.
- For enclosure mounting, a minimum depth of 6.00 inches [152.4mm] is required for controls on the inside rear surface of the door.
- Control panels connect to the transfer switch via a harness with quick disconnect plug(s), exiting on the right side. Extension harnesses are available from the factory.
- Specific cutout data for Type 1 enclosures is found in Detail A-1 and Detail B-1. For Type 3R, 4, & 12 enclosures, refer to Detail A-2 & Detail B-2. Gaskets and bezels are supplied for Type 3R, 4, & 12 enclosures.
Cable Accommodations & Cabling Notes
Cable Accommodations (per phase & neutral)
- Screw Type (Standard): Accommodates (2) 1/0 - 250 MCM AL/CU cables or (1) #4 - 600 MCM AL/CU cable.
Cabling Notes
- Standard lugs are mechanical (screw type).
- Lug material: Aluminum Alloy 6061-T6 with electro tin plated finish.
- Screw material: Aluminum Alloy 6262-19 with electro tin plated finish.
- Products are UL Listed and CSA Certified.
- Screw tightening torque for lugs is 19 FT-LBS per UL 486B.
Switch Notes (260-400 AMP Switches)
- Supplied with standard mechanical (screw type) lugs on the Normal, Emergency, and Load bus stabs. Each stab is suitable for connecting two (2) 1/0 - 250 MCM CU/AL cables or one (1) #4 - 600 MCM CU/AL cable.
Enclosure and Mounting Dimensions
Minimum Required Enclosure Size
Switch Rating (AMPS) | Height (INCH / MM) | Width (INCH / MM) | Depth (INCH / MM) |
---|---|---|---|
260-400 AMPS | 48.00 (1219.2) | 18.00 (457.2) | 13.00 (330.2) |
Suggested Bolt Size for Mounting ATS
1/4-20 x 3.00" LONG MINIMUM QUANTITY (4)
Overall Dimensions (2 and 3 Pole with and without Overlapping Neutral)
Dimension | Value (INCH) | Value (MM) |
---|---|---|
A | 11.00 | 279.4 |
B | 12.00 | 304.8 |
C | 6.87 | 174.5 |
D | 10.00 | 254.0 |
E | 0.50 | 12.7 |
F | 11.00 | 279.4 |
G | 0.50 | 12.7 |
H | 3.87 | 98.3 |
J | 2.12 | 53.8 |
K | 2.12 | 53.8 |
L | 0.31 | 7.9 |
T | 4.93 | 125.2 |
U | 3.00 | 76.2 |
W | 2.12 | 53.8 |
Control Panel & Power Meter Data
Control Panel & Controls Mounting
The document illustrates the mounting of control panels and associated controls. A minimum door control clearance of 6.00 inches [152.4mm] is required. The arrangement includes space for the control panel, an optional power meter, and a user interface cutout. Mounting rails are provided for operator controls or DIN rail mounted accessories.
Cutout and Mounting Details
Specific details are provided for different enclosure types:
- Detail A-1 (For Type 1): Provides dimensions for control panel and user interface mounting cutouts.
- Detail B-1 (For Type 1): Provides dimensions for mounting operator controls or DIN rail mounted accessories.
- Detail A-2 (For Type 3R, 12 & 4): Provides dimensions for control panel and user interface mounting cutouts for these enclosure types.
- Detail B-2 (For Type 3R, 12 & 4): Provides dimensions for mounting operator controls or DIN rail mounted accessories for these enclosure types.
Add-on panels can be mounted using specified PEM studs (e.g., Ø0.25" DIA. & 1/4-20 x 1.50" LONG PEM STUD).
Manufacturer Information
ASCO Power Technologies, L.P.
Florham Park, New Jersey 07932 U.S.A.
Drawing Number: 978732-002
Revision: B, ECN 265705