Samsung Wind-Free™2.0 Split System Submittal Data

Samsung "Wind-Free™2.0" AR24TSFABWKNCV/AR24TSFABWKXCV Wall Mounted Split System

Submittal Data Sheet

Product Overview

This document provides detailed submittal data for the Samsung "Wind-Free™2.0" wall-mounted evaporator split system, model series AR24TSFABWKNCV (Indoor Unit) and AR24TSFABWKXCV (Outdoor Unit). It outlines key specifications, features, construction details, and optional accessories.

The "Wind-Free™" mode disperses air through thousands of micro-holes to prevent cold air drafts, providing enhanced comfort. The system includes standard Wi-Fi capability for control via the Samsung SmartThings app.

Specifications

General Information

US CodeModelIndoor Unit: RNS24ABT
Outdoor Unit: RXS24ABT
Model NumberIndoor Unit: AR24TSFABWKNCV
Outdoor Unit: AR24TSFABWKXCV
Location
Job NameEngineer
PurchaserReference
Submitted toSchedule #
ApprovalConstruction

Performance

Nominal Capacity (Cooling / Heating)21,000 / 27,400 Btu/hSEER / EER20 / 12.5
Capacity Range (Cooling / Heating)8,800-31,700 Btu/h / 7,500-41,000 Btu/hCOP (Nominal Heating)3.36
HSPF10AHRI Reference Number205132634

Power & Electrical

Voltage1Ø / 208-230V / 60HzWorking Voltage Range (VAC)176 - 254
Operating Current (Cooling)2.7 / 7.6 / 13.7 A (Min./Std./Max.)Max. Breaker30 A
Operating Current (Heating)2.6 / 10.7 / 18.9 A (Min./Std./Max.)Min. Circuit Ampacity (A)20 A

Dimensions & Weight

Indoor Unit (WxHxD)41 17/32" x 11 3/4" x 8 7/16"Indoor Unit Weight27.6 lbs
Outdoor Unit (WxHxD)37" x 39 1/4" x 13"Outdoor Unit Weight150.4 lbs

Operating Conditions & Connections

Condensate Connection11/16" ODSound Pressure Level (Indoor Low/High)28 / 47 dB
Sound Pressure Level (Outdoor High)56 dBOperating Temperatures (Outdoor Cooling)14°F ~ 115°F (-10°C ~ 46.1°C)
Operating Temperatures (Outdoor Heating)-5°F ~ 75°F (-20.5°C ~ 23.9°C)Operating Temperatures (Indoor Cooling)61°F ~ 90°F (16°C ~ 32°C)
Operating Temperatures (Indoor Heating)81°F (27°C) or lessPipe Connections (High side / Low side)1/4" / 5/8"
Max / Min Line Set Length98 ft / 9.8 ftMax Vertical Separation66 ft

Refrigerant System

Refrigerant TypeR410AFactory Charge88.2 oz.
Charged for25 feetAdditional Refrigerant0.16 oz./ft. over 25 ft.

Compressor

ManufacturerSamsungTypeBLDC Rotary
RLA15.2 A

Evaporator Fan

TypeBLDC motor with cross-flow fanAir Volume (Cooling L/M/H/Turbo)399 / 512 / 622 / 713 CFM
Air Volume (Heating L/M/H/Turbo)399 / 512 / 622 / 713 CFMConsumption27 Watts
FLA0.12 AMotor Output125 Watts

Condenser Fan

FLA0.48 AAir Volume (max.)2,825 CFM

Certifications & Safety Devices

CertificationsETL (UL 1995)Safety DevicesPCB fuses, indoor unit terminal block thermal fuse, current transformer, over-voltage protection, crankcase heating, temperature limit protection logic, compressor overload sensing.

Construction & Features

Construction

  • Indoor unit chassis: UL94 V0 rated, with a galvanized steel mounting bracket.
  • Easy-access panel on the bottom of the indoor unit for wire, pipe, and drain connections, facilitating installation and service.
  • Outdoor unit: Constructed from galvanized steel with a durable baked-on powder coat finish.

Heat Exchanger

Features mechanically bonded fin to copper tube construction.

Refrigerant System

Utilizes a hermetically sealed, inverter-controlled BLDC Rotary compressor. Refrigerant flow is managed by an electronic expansion valve located at the outdoor unit.

Indoor Fan

A single, antibacterial cross-flow fan provides air circulation. Offers three fan speed settings plus an auto setting. Features automatic motorized vertical swing (up/down) and horizontal swing (left/right) louvers.

Controls & Connectivity

  • Built-in Wi-Fi adapter for control and monitoring via the Samsung SmartThings app (Android, iOS).
  • Supports dual set temperature when connected to the Advanced Wired Controller (MWR-WG00UN).
  • Includes a connection point for overflow detection devices or other normally closed contacts for simple unit shutdown.
  • Ships with a wireless controller, holder, and batteries. Wired controller options are available.
  • Compatible with Samsung central control systems (requires MIM-R10UN accessory).

Convenience Features

  • System energy consumption can be monitored through the SmartThings mobile app or the indoor unit display.
  • AI (Artificial Intelligence) Auto Mode: Learns user patterns to optimize comfort and efficiency (Wi-Fi connection required).
  • Eco Mode: Reduces energy consumption during low demand periods.
  • Smart Install Mode: Performs system diagnostics during initial operation.
  • Auto Restart functionality.
  • Auto Clean Function.
  • A 7-segment digital display on the front of the unit shows temperature and unit status.
  • "Fast" mode for rapid temperature achievement.
  • Auto changeover between cooling and heating.
  • Good Sleep mode, Quiet mode, Dry mode.
  • Simple ON/OFF time function programmable via the wireless controller.
  • Features an electro-static, washable main filter accessible from the top of the unit.
  • Includes a filter cleaning reminder.

Optional Accessories

  • Condensate pump: Aspen Mini Orange (ASP-MO-UNIV 110-250), Blue Diamond (BD-BLUE-230)
  • Wired controller: Advanced (MWR-WG00UN), Simple Touch (MWR-SH11UN)
  • Wired controller sub-PCB: MIM-A00UN (Required for optional wired controllers)
  • 24 VAC thermostat adapter: MIM-A60UN
  • External temperature sensor: MRW-TA
  • Central control interface module: MIM-R10UN
  • External contact control interface module: MIM-B14 (Requires MIM-A00UN sub-PCB)
  • Line sets (insulated and flared, interconnect cables included): 25' - ILS2509, 50' - ILS5009
  • Wall bracket (for outdoor unit): CKN-250
  • Wind Baffle / Guard (Front): WBF-2M-B
  • Wind Baffle / Guard (Back): WBB-3M

Dimensional Drawings

Indoor Unit Dimensions

The indoor unit has the following approximate dimensions:

  • Width: 41 17/32 inches
  • Height: 11 3/4 inches
  • Depth: 8 7/16 inches

Outdoor Unit Dimensions

The outdoor unit has the following approximate dimensions:

  • Width: 37 inches
  • Height: 39 5/16 inches
  • Depth: 13 inches

Installation Clearances

Minimum clearances are recommended for proper operation:

  • Walls (Sides): 5 inches
  • Walls (Back): 12 inches
  • Ceiling: 24 inches

Wiring Diagram Description

The system utilizes basic power and communication wiring between the indoor and outdoor units. Both units feature L1, L2, F1, and F2 terminals for power and communication connections. The outdoor unit connects to the main power supply.

PDF preview unavailable. Download the PDF instead.

ar24tsfabwkncv ar24tsfabwkxcv+(rns24abt rxs24abt) submittal wind+free+2.0 07142020

Related Documents

Preview Samsung AR24TSFABWKNCV RNS24ABT Wind-Free 2.0 Wall Mounted Evaporator Submittal Data
Technical specifications and dimensional data for the Samsung AR24TSFABWKNCV RNS24ABT Wind-Free 2.0 wall-mounted multi-zone air conditioning evaporator, including performance, airflow, controls, and compatibility.
Preview Samsung Max Heat 2.0 AR24TSFABWKNCV/AR24TSFACWKXCV Submittal Data Sheet
Technical submittal data sheet for the Samsung Max Heat 2.0 wall-mounted evaporator split system, including specifications, dimensions, and optional accessories for models AR24TSFABWKNCV and AR24TSFACWKXCV.
Preview Samsung Air Conditioner 2020 Line-Up: Features and Specifications
Explore the 2020 line-up of Samsung Air Conditioners, including Wind-Free™ technology, Digital Inverter Boost, and various models like Split Type Wall Mounted, Floor Standing, and Commercial Air Conditioners. Discover features, benefits, and detailed specifications for optimal cooling and energy efficiency.
Preview Samsung AX350A9350 BESPOKE Cube Air Purifier | Features & Specifications
Discover the Samsung AX350A9350 BESPOKE Cube Air Purifier with 360° Purification, Pet Mode, enhanced filtration, and smart features. Designed to fit your lifestyle and improve air quality.
Preview Samsung AR9500T SIEL WindFree PM1.0 AI Energy Air Conditioner User Manual
Comprehensive user manual for the Samsung AR9500T SIEL WindFree PM1.0 AI Energy air conditioner. This guide provides essential information on safety precautions, product features, operation, cleaning, and disposal, ensuring optimal and safe use of your appliance.
Preview Samsung Air Conditioner Installation Terms and Conditions
Detailed terms and conditions for the installation of Samsung air conditioning units, covering requirements, inclusions, exclusions, and costs. Ensures safe and proper installation procedures.
Preview Samsung AC009BNJDCH/AA Console Split System: Technical Specifications and Overview
Detailed submittal document for the Samsung AC009BNJDCH/AA (CNH09JDB) and AC009BXADCH/AA (CXH09ADB) single-zone console split system air conditioner, including performance, dimensions, and operational specifications.
Preview Samsung WindFree 4-Way Cassette AC048BN4DCH/AA Split System Submittal
Submittal document for the Samsung WindFree 4-Way Cassette, Single Zone, Split System, model AC048BN4DCH/AA (CNH484DB) and AC048BXADCH/AA (CXH48ADB). Includes specifications, dimensions, general information, and optional accessories.