Smappee MID 100A SERIES DIN Rail Smart Meters

User Manual v1.0

1 Introduction

This document provides operating, maintenance, and installation instructions for the Smappee MID 100A SERIES DIN rail smart meters. These units measure and display characteristics of single-phase two-wire (1p2w), three-phase three-wire (3p3w), and three-phase four-wire (3p4w) electrical networks. Key measured parameters include voltage (V), frequency (Hz), current (A), power (kW/kVa/kVar), and import, export, and total energy (kWh/kVarh). The meters can also measure maximum demand current and power over preset periods up to 60 minutes.

These units are rated for a maximum of 100A direct operation and do not require external current transformers (CTs). They feature built-in pulse, RS485 Modbus RTU, and Mbus outputs. Configuration is password protected.

1.1 Unit Characteristics

The Smappee MID 100A SERIES meters include models such as the i1-EN3-1, which measures kWh/kVarh, kW/kVar, kVA, Power (P), Frequency (F), Power Factor (PF), Demand (dmd), Voltage (V), Current (A), and Total Harmonic Distortion (THD%), with pulse/Modbus output and tariff capabilities.

1.2 RS485 Serial Modbus RTU

The RS485 serial port utilizes the Modbus RTU protocol, enabling remote monitoring and control of the unit. Setup screens are available for configuring the RS485 port parameters.

1.3 Mbus

The Mbus port uses the EN13757-3 protocol for remote monitoring and control, with dedicated setup screens for configuration.

1.4 Pulse Output

Two pulse outputs are provided to signal measured active and reactive energy. Pulse output 2 for active energy has a fixed constant of 400imp/kWh and a fixed pulse width of 100ms. Configurable pulse output 1 defaults to 400imp/kWh with a 100ms pulse width, and its settings can be adjusted via the setup menu.

2 Start-up Screens

Upon power-up, the meter displays all segments for a display check. This is followed by the software version information. The unit then performs a self-test, indicating the result. After a brief delay, the screen displays the active energy interface, showing the total active energy in kWh.

3 Measurements

The meter's buttons are used for navigation and selection:

3.1 Voltage and Current

Pressing the measurement selection buttons cycles through the following parameters:

3.2 Frequency, Power Factor, and Demand

Pressing the measurement selection buttons cycles through:

3.3 Power

Pressing the measurement selection buttons cycles through:

3.4 Energy Measurements

Pressing the measurement selection buttons cycles through:

Note: Date and time can only be set via RS485 communication.

4 Set-up

To enter set-up mode, press and hold the [M] button for 3 seconds until the password screen appears. Setup is password protected; the default password is 1000. Press [M] for 3 seconds to confirm the password. An incorrect password entry will display "PASS Err". To exit set-up mode, repeatedly press the [ESC] button until the measurement screen is restored.

4.1 Set-up Entry Methods

Some menu items require a four-digit number entry (e.g., password), while others require selection from a list of options (e.g., supply system).

4.1.1 Menu Option Selection

  1. Use the [M] and [P] buttons to scroll through menu options.
  2. Press [E] to confirm a selection.
  3. If an item flashes, it can be adjusted using the [M] and [P] buttons.
  4. After selecting an option, press [E] to confirm. The [SET] indicator will appear.
  5. To return to a higher menu level after setting a parameter, press [ESC]. The [SET] indicator will be removed.
  6. After completing all settings, press [ESC] repeatedly to return to the main measurement screen.

4.1.2 Number Entry Procedure

For number entry (like passwords), digits are set individually from left to right:

  1. The current digit flashes and is set using the [M] and [P] buttons.
  2. Press [E] to confirm each digit setting. The [SET] indicator appears after the last digit is set.
  3. After setting the last digit, press [E] to exit the number setting routine. The [SET] indicator will be removed.

4.2 Change Password

Navigate to the "Change Password" option using [M] and [P], then press [E]. The new password screen will appear with the first digit flashing. Use [M] and [P] to set the digit, then press [E] to confirm. Repeat for the remaining three digits. After the last digit, [SET] will show. Press [E] to exit and return to the Set-up menu.

4.3 Supply System

The default setting is 3-Phase 4-Wire (3P4). This section allows setting the electrical system type. From the set-up menu, select "Supply System" using [M] and [P]. Press [E] to enter the selection routine where the current selection flashes. Use [M] and [P] to choose the required system: 1P2(W), 3P3(W), or 3P4(W). Press [E] to confirm; the [SET] indicator will appear. Press [ESC] to exit and return to the main set-up menu.

4.4 Backlit Set-up

The backlight duration is settable, with a default of 60 minutes. If set to 5, the backlight turns off after 5 minutes of inactivity. From the set-up menu, select "Backlit" using [M] and [P]. Press [E] to enter the selection routine; the current time interval flashes. Options are: 0 (always on), 5, 10, 30, 60, 120 minutes. Use [M] and [P] to select the interval, then press [E] to confirm.

4.5 Communication

The RS485/Mbus port supports Modbus RTU protocol. Parameters are selected via the front panel. From the set-up menu, select "Communication" using [M] and [P]. Press [E] to enter the selection routine; the current setting flashes. Use [M] and [P] to choose the Modbus address (001 to 247). Press [E] to confirm and [ESC] to return to the main set-up menu.

4.6 Demand Integration Time (DIT)

This setting defines the period in minutes over which current and power readings are integrated for maximum demand measurement. Options include 0, 5, 8, 10, 15, 20, 30, 60 minutes. From the set-up menu, select "DIT" using [M] and [P]. Press [E] to enter the selection routine; the current time interval flashes. Use [M] and [P] to select the desired time. Press [E] to confirm; the [SET] indicator will appear. Press [ESC] to exit and return to the menu.

4.7 CLR (Clear Maximum Demand)

This function resets the maximum demand value for current and power. From the set-up menu, select the "CLR" option using [M] and [P]. Press [E] to enter the selection routine; the "MD" value will flash. Press [E] to confirm the setting and [ESC] to return to the main set-up menu.

4.8 Pulse Output Configuration

This section allows configuring Pulse Output 1 to generate pulses representing defined amounts of active or reactive energy. Options include Total kWh/Total kVarh, Import kWh/Export kWh, and Import kVarh/Export kVarh. From the set-up menu, select "Pulse Output" using [M] and [P]. Press [E] to enter the selection routine; the unit symbol flashes. Use [M] and [P] to choose kWh or kVarh. Press [E] to confirm and [ESC] to return to the main set-up menu.

4.8.1 Pulse Rate

Set the energy represented by each pulse. Rates can be set to 1 pulse per dFt (default, 2.5 Wh/Varh), 0.01 = 10 Wh/Varh, 0.1 = 100 Wh/Varh, 1 = 1 kWh/kVarh, 10 = 10 kWh/kVarh, or 100 = 100 kWh/kVarh. From the set-up menu, select "Pulse Rate" using [M] and [P]. Press [E] to enter the selection routine; the current setting flashes. Use [M] and [P] to choose the pulse rate. Press [E] to confirm and [ESC] to return to the main set-up menu.

4.8.2 Pulse Duration

The pulse width can be selected as 200ms (non-MID versions only), 100ms (default), or 60ms. From the set-up menu, select "Pulse Width" using [M] and [P]. Press [E] to enter the selection routine; the current setting flashes. Use [M] and [P] to choose the pulse width. Press [E] to confirm and [ESC] to return to the main set-up menu.

5 Specifications

5.1 Measured Parameters

The unit can monitor and display parameters for single-phase two-wire (1p2w), three-phase three-wire (3p3w), or three-phase four-wire (3p4w) systems.

5.1.1 Voltage and Current

5.1.2 Power Factor, Frequency, and Maximum Demand

5.1.3 Energy Measurements

5.2 Measured Inputs

Voltage inputs are via a 4-way fixed connector with 25mm² stranded wire capacity for single-phase two-wire (1p2w), three-phase three-wire (3p3w), or three-phase four-wire (3p4w) unbalanced systems. Line frequency is measured from L1 voltage or L3 voltage.

5.3 Interfaces for External Monitoring

Three interfaces are provided:

Modbus/Mbus configuration (baud rate, etc.) and pulse relay output assignments are configured through the set-up screens.

5.3.1 Pulse Output Details

Pulse output can be set to generate pulses for kWh or kVarh. Rates include: dFt = 2.5 Wh/Varh (default), 0.01 = 10 Wh/Varh, 0.1 = 100 Wh/Varh, 1 = 1 kWh/kVarh, 10 = 10 kWh/kVarh, 100 = 100 kWh/kVarh. Pulse width options are 200ms, 100ms (default), or 60ms.

5.3.2 RS485/Mbus Output for Communication

For Modbus RTU, configurable RS485 parameters include:

For the Modbus/Mbus protocol document, please contact Smappee.

5.4 Accuracy

5.5 Reference Conditions of Influence Quantities

Influence quantities affect measurement errors. Accuracy is verified under nominal conditions:

5.6 Environment

*Maximum operating and storage temperatures are in the context of typical daily and seasonal variations.

5.7 Mechanics

5.8 Manufacturer Declaration

Smappee n.v. declares under its sole responsibility that the polyphase multifunction electrical meter "SMAPPEE MID 100A series" corresponds to the production model described in the EU-type examination certificate and meets the requirements of Directive 2014/32/EU. EU type examination certificate number: 0120/SGS0462. Identification number of the Notified Body: NB0120.

6 Dimensions

The unit has a width of 72mm, a height of 100mm, and a depth of 58.7mm, designed for DIN rail mounting.

7 Wiring Diagram

The meter provides interfaces for external monitoring. The wiring configurations for different systems are as follows:

7.1 Single Phase Two Wires (1P2)

Connections are made to terminals:

7.2 Three Phase Three Wires (3P3)

Connections are made to terminals:

7.3 Three Phase Four Wires (3P4)

Connections are made to terminals:

Note: The diagrams show terminal blocks for voltage inputs (U/I) and phase connections (L1, L2, L3, N).

Safety Warnings

[!] Risk of Danger: These instructions contain important safety information. Read them before starting installation or servicing of the equipment.

[⚡] Caution: Risk of Electric Shock.

Important safety information is also contained in the Maintenance section. Familiarize yourself with this information before attempting installation or other procedures.

Manufacturer: Smappee n.v.

Address: Evolis 104, 8530 Harelbeke, Belgium

Contact: info@smappee.com | www.smappee.com

Certifications: CE, ROHS, MID

Models: MID 100A Series, MID 100A Series DIN Rail Smart Meters, DIN Rail Smart Meters, Rail Smart Meters, Smart Meters, Meters

File Info : application/pdf, 2 Pages, 4.21MB

PDF preview unavailable. Download the PDF instead.

Smappee-MIDmeter-Manual-v2-2309

References

Adobe PDF Library 17.0 Adobe InDesign 18.5 (Macintosh)

Related Documents

Preview Smappee EV Charging, Energy Management & Battery Storage Catalogue
Comprehensive catalogue of Smappee's advanced EV charging solutions, energy management systems, and battery storage products, including EV One, EV Wall, EV Ultra, Genius, BESS, and more.
Preview Smappee Infinity Installation Manual
Comprehensive installation manual for the Smappee Infinity energy management system. Learn how to install, configure, and troubleshoot your Smappee device for smart energy monitoring and control.
Preview Smappee P1 Module: Real-Time Grid Monitoring and Smart Energy Management
The Smappee P1 module provides real-time grid import/export monitoring and smart energy management. It supports solar surplus charging and dynamic overload protection, offering easy plug-and-play installation compatible with digital meters featuring a P1 port.
Preview Smappee Infinity Installation Manual
Comprehensive guide for installing the Smappee Infinity energy monitoring system. Learn about setup, configuration, and troubleshooting for efficient home energy management.
Preview Smappee EV Base Installation Guide and Connection Diagram
A comprehensive guide for installing the Smappee EV Base electric vehicle charging station, including safety warnings, connection diagrams, and step-by-step instructions for installers. Covers preparation, mounting, electrical connections, and app configuration.
Preview Smappee EV Wall Technical Specifications and Features
Detailed technical specifications, features, and operational details for the Smappee EV Wall, a compact AC charging station for home and business use. Covers dimensions, weight, operating conditions, connectivity, charging capabilities, and safety features.
Preview Smappee Platform Services Terms and Conditions
This document outlines the terms and conditions for using Smappee's platform services, including the mobile app and dashboard. It covers essential functionalities, smart and business subscriptions, fees, usage restrictions, termination, and warranties.
Preview Smappee Pay Station Installation Manual
Comprehensive installation manual for the Smappee Pay Station, detailing installation, configuration, safety guidelines, and operational procedures for electric vehicle charging infrastructure.