Certificate of Conformity
Certificate Number: U25-0580
Applicant: NingBo Deye Inverter Technology Co., Ltd.
No. 26 South YongJiang Road, Daqi, Beilun, NingBo, China
Manufacturer: NingBo Deye Inverter Technology Co., Ltd.
No. 26 South YongJiang Road, Daqi, Beilun, NingBo, China
Place of Production: NingBo Deye Inverter Technology Co., Ltd.
No. 26 South YongJiang Road, Daqi, Beilun, NingBo, China
Product Information
Product: Photovoltaic Inverter
Models: SUN-M130G4-EU-Q0, SUN-M160G4-EU-Q0, SUN-M180G4-EU-Q0, SUN-M200G4-EU-Q0, SUN-M220G4-EU-Q0, SUN-M130G4-EU-Q0-I, SUN-M160G4-EU-Q0-I, SUN-M180G4-EU-Q0-I, SUN-M200G4-EU-Q0-I, SUN-M220G4-EU-Q0-I
Device intended for: Type A installations
Software Version: 0308-1426
Applicable Regulations and Standards
- Commission Regulation (EU) 2016/631 of April 14, 2016 establishing network codes for connection requirements.
- General Requirements from Commission Regulation EU 2016/631 establishing network codes for connection requirements - approved by Decision of the President of the Energy Regulatory Office DRE.WOSE.7128.550.2.2018.ZJ of January 2, 2019.
- Conditions and procedures for using certificates in the process of connecting energy generation modules to the electricity grid.
- EN 50549-1:2019/A1:2023, PN-EN 50549-1:2019/A1:2023
- Requirements for generating installations intended for parallel connection to public distribution networks -- Part 1: Connection to the LV distribution network -- Generating installations up to type B inclusive.
- EN 50549-10:2022, PN EN 50549-10:2023 Requirements for generating installations intended for parallel connection to public distribution networks -- Part 10: Testing for conformity assessment of generating units.
Certification Details
Certification Program: NSOP-0032-DEU-ZE-V10
Product Assessment Report Number: ASUE-ESH-P24120291
Product Certification Type (EN ISO/IEC 17067): 1a
Issue Date: 2025-07-15
Validity Period: 2025-07-15 to 2029-07-14
Certification Institute: Bureau Veritas CPS Germany GmbH
Location: Türkheim, Germany
Accreditation: DAkkS, D-ZE-12024-01-00
Technical Specifications
Parameter | SUN-M130G4-EU-Q0 | SUN-M160G4-EU-Q0 | SUN-M180G4-EU-Q0 | SUN-M200G4-EU-Q0 | SUN-M220G4-EU-Q0 | SUN-M130G4-EU-Q0-I | SUN-M160G4-EU-Q0-I | SUN-M180G4-EU-Q0-I | SUN-M200G4-EU-Q0-I | SUN-M220G4-EU-Q0-I |
---|---|---|---|---|---|---|---|---|---|---|
Input Parameters | ||||||||||
MPP Voltage Range [V] | 25-55 | 25-55 | 25-55 | 25-55 | 25-55 | 25-55 | 25-55 | 25-55 | 25-55 | 25-55 |
Max DC Input Voltage [V] | 60 | 60 | 60 | 60 | 60 | 60 | 60 | 60 | 60 | 60 |
Max DC Input Current [A] | 15*4 | 15*4 | 15*4 | 15*4 | 15*4 | 18*4 | 18*4 | 18*4 | 18*4 | 18*4 |
Output Parameters | ||||||||||
AC Output Voltage [V] | L/N/PE, 230V, 50Hz | |||||||||
Rated AC Output Current [A] | 5.7 | 7.0 | 7.9 | 8.7 | 9.6 | 5.7 | 7.0 | 7.9 | 8.7 | 9.6 |
Max AC Output Current [A] | 5.7 | 7.0 | 7.9 | 8.7 | 9.6 | 5.7 | 7.0 | 7.9 | 8.7 | 9.6 |
Active Power AC [kW] | 1.30 | 1.60 | 1.80 | 2.00 | 2.20 | 1.30 | 1.60 | 1.80 | 2.00 | 2.20 |
Max Apparent Power AC [kVA] | 1.30 | 1.60 | 1.80 | 2.00 | 2.20 | 1.30 | 1.60 | 1.80 | 2.00 | 2.20 |
General Data | ||||||||||
Operating Temperature Range [°C] | -40 to +65 °C, derating above 45 °C | |||||||||
Permissible Ambient Humidity | 0-100% | |||||||||
Permissible Altitude [m] | 2000m | |||||||||
Noise Level [dB] | ≤25 dB | |||||||||
IP Protection Rating | IP 67 | |||||||||
Inverter Topology | Isolated | |||||||||
Surge Category | OVC II (DC), OVC III (AC) |
EN 50549-1 Parameters
Standard Clause | Parameter | Typical Range of Values | Default Setting for Poland |
---|---|---|---|
4.3.2 Connection Switch | Requirement for single disturbance tolerance for connection switch | Yes / No | Yes |
4.4.2 Frequency Range | Frequency range 47.0 – 47.5 Hz | 0-20 s | 0 s |
Frequency range 47.5 – 48.5 Hz | 30-90 min | ≥30 min | |
Frequency range 48.5 - 49.0 Hz | 30-90 min | ≥30 min | |
Frequency range 49.0 – 51.0 Hz | Configurable | Unlimited | |
Frequency range 51.0 – 51.5 Hz | 30-90 min | ≥30 min | |
Frequency range 51.5 - 52 Hz | 0-15 min | 0 s | |
4.4.3 Minimum requirements for active power delivery at reduced frequency | Reduction threshold | 49 Hz - 49.5 Hz | Electronic inverter, no power limitation |
Maximum reduction rate | 2-10% P/Hz | ≤ 2% | |
4.4.4 Continuous operating voltage range | Upper limit | 100-110% | 1.15 Un |
Lower limit | 90-100% | 0.85 Un | |
4.5.2 Immunity to rapid frequency changes (ROCOF) | ROCOF tolerance (defined with a sliding measurement window of 500 ms) | 0-10 Hz/s | ≥ 2.0 Hz/s |
4.6.1 Active power response to increased frequency | Threshold frequency f1 | 50.2 Hz - 52 Hz | 50.2 Hz |
Steepness | 2%-12% | 5% | |
Reference power | P_M / P_max | P_max | |
Delay | 0-2 s | 0 s | |
Deactivation threshold fstop | 50.0 Hz - f1 | Deactivated | |
Deactivation time tstop | 0-600 s | Not applicable | |
Permission for gradual disconnection | Yes / No | No | |
4.6.2 Response to reduced frequency | Frequency threshold f1 | 49.8 Hz - 46 Hz | Not applicable |
Steepness | 2-12% | Not applicable | |
Reference power | P_M / P_max | Not applicable | |
Delay | 0-2 s | Not applicable | |
4.7.2.2 Reactive power regulation capability | Power factor in over-excitation range | 0.9-1 | 0.9 |
Power factor in under-excitation range | 0.9-1 | 0.9 | |
4.7.2.3 Control modes | Active control mode | Q_set, Q(U), cos φ (P) | Q_set, cos φ_set |
Q and excitation setting | 0-48% PD | 0 | |
cos φ and excitation setting | 1-0.9 | 1 | |
Setting capability for all parameters | Possibility to set all parameters | ||
4.7.2.3.3 Voltage-related control modes | Characteristic curve Q(U) | Q(U) (single-phase inverter): 0.0...-0.436, 0.92...-0.436, 0.94...0.0, 1.06...0.0, 1.08...0.436, 1.2...0.436 | |
Characteristic curve P(U) | P(U) deactivated | P(U) deactivated | |
Time constant | 3 s - 60 s | 10 s | |
Minimum power factor | 0.0-1 | 0.9 | |
Power unlock / Power block | 0%-20% / 0%-20% | Deactivated / Deactivated | |
4.7.2.3.4 Power-related control mode | Zero current mode for generation technology connected to the converter: Enable | On / Off | Off |
Static voltage range (raised) | 1.0 Un - 1.2 Un | Not applicable | |
Static voltage range (lowered) | 0.2 Un - 1.0 Un | Not applicable | |
4.9.3 Requirements for voltage and frequency protection | Threshold for dedicated device protection [A or kW or kVA] | 16 A (Note: Rated current of the internal protection device) | |
Under-voltage protection trip threshold - stage 1 | 0.2 Un - 1 Un | 0.85 Un | |
Under-voltage protection trip time - stage 1 | 0.1 s - 100 s | 1.2 s | |
Under-voltage protection trip threshold - stage 2 | 0.2 Un - 1 Un | Not applicable | |
Under-voltage protection trip time - stage 2 | 0.1 s - 100 s | Not applicable | |
Over-voltage protection trip threshold - stage 1 | 1.0 Un - 2.0 Un | 1.15 Un | |
Over-voltage protection trip time - stage 1 | 0.1 s - 100 s | 0.1 s | |
Over-voltage protection trip threshold - stage 2 | 1.0 Un - 2.0 Un | Not applicable | |
Over-voltage protection trip time - stage 2 | 0.1 s - 100 s | Not applicable | |
Over-voltage protection trip threshold - average over 10 min | 1.0 Un - 2.0 Un | 1.1 Un | |
Over-voltage event operation time: average over 10 min (update every 3 s) | 0.04 - 10 s | 10 min (update every 3 s) | |
Under-frequency protection trip threshold - stage 1 | 44.0 Hz - 50.0 Hz | 47.5 Hz | |
Under-frequency protection trip time - stage 1 | 0.1 s - 100 s | 0.3 s | |
Under-frequency protection trip threshold - stage 2 | 44.0 Hz - 50.0 Hz | Not applicable | |
Under-frequency protection trip time - stage 2 | 0.1 s - 1000 s | Not applicable | |
Over-frequency protection trip threshold - stage 1 | 50.0 Hz - 66.0 Hz | 52.0 Hz | |
Over-frequency protection trip time - stage 1 | 0.1 s - 1000 s | 0.3 s | |
Over-frequency protection trip threshold - stage 2 | 50.0 Hz - 66.0 Hz | Not applicable | |
Over-frequency protection trip time - stage 2 | 0.1 s - 1000 s | Not applicable | |
Loss of voltage according to EN 62116 (LoM) | 0-6000s | 2 s | |
4.10.2 Automatic reclosing after tripping | Lower frequency | 47.0 Hz - 50.0 Hz | 49.00 Hz |
Upper frequency | 50.0 Hz - 52.0 Hz | 50.05 Hz | |
Lower voltage | 0.5 Un - 1.0 Un | 0.85 Un | |
Upper voltage | 1.0 Un - 1.2 Un | 1.10 Un | |
Observation time | 10 s - 600 s | 60 s | |
Active power ramp rate | 1% - 10000%/min | 9%/min | |
4.10.3 Start of electrical energy generation | Lower frequency | 47.0 Hz - 50.0 Hz | 49.00 Hz |
Upper frequency | 50.0 Hz - 52.0 Hz | 50.05 Hz | |
Lower voltage | 0.5 Un - 1.0 Un | 0.85 Un | |
Upper voltage | 1.0 Un - 1.2 Un | 1.10 Un | |
Observation time | 10 s - 600 s | 60 s | |
Active power ramp rate | 1% - 10000%/min | 9%/min | |
4.11.1 Cessation of active power | Remote control of logical connection | Yes / No | Yes (Signal via WIFI can be used to change or suspend active power output) |
4.11.2 Reduction of active power setting | Remote control | Yes / No | Yes (Signal via WIFI can be used to change or suspend active power output) |
4.11.3 Remote information exchange | Required remote information exchange | Yes / No | No |
Functionality Scope and Assessment
Based on the principles of equipment certification for energy park modules (PPM), as defined in the PTPIREE document.
Commission Regulation (EU) 2016/631 of April 14, 2016 establishing network codes for connection requirements (Official Journal of the EU L 112/1 of 27.4.2016).
General Requirements from Commission Regulation EU 2016/631 establishing network codes for connection requirements - approved by Decision of the President of the Energy Regulatory Office DRE.WOSE.7128.550.2.2018.ZJ of January 2, 2019.
Parameter | NC RfG | PSE 2018 | Type A | Type B | Type C | Type D | Assessment (**) |
---|---|---|---|---|---|---|---|
Frequency Range | 13.1 a) | 13.1 a), i | X | Positive | |||
Ability to withstand rate of change of frequency (ROCOF) df/dt | 13.1 b) | 13.1 b) | X | Positive | |||
Remote cessation of active power generation | 13.6 | 13.6 | X | Nd. | Nd. | Positive | |
Remote control of active power | 14.2 | 14.2 b) | X | Nd. | Nd. | Nd. | Nd. |
Operation mode of the generating unit, where the active power generated decreases in response to an increase in system frequency above a specified value (LFSM-O) | 13.2 (*) | 13.2 a), b), f) | X | Positive | |||
Operation mode of the generating unit, where the active power generated increases in response to a decrease in system frequency below a specified value (LFSM-U) | 15.2 c) | 15.2 c), i | Nd. | Nd. | Nd. | Nd. | |
Ability to withstand voltage dips for connections below 110 kV | 14.3 | 14.3 a), i, b) | Nd. | Nd. | Nd. | ||
Ability to withstand voltage dips for connections above 110 kV | 16.3 | 16.3 a), i, c) | Nd. | Nd. | Nd. | Nd. | Nd. |
Introduction of fast disturbance current, symmetrical and asymmetrical disturbances | 20.2 b), c) 21.3 e) | 20.2 b), c) 21.3 e) | Nd. | Nd. | Nd. | ||
Non-disturbing active power recovery | 20.3 | 20.3 a | Nd. | Nd. | Nd. |
(*) Clause 13.2. letter b) applies exclusively to Type A PPMs in accordance with NC RfG.
(**) Positive assessment applies only to energy park modules (PPM) of a type that has been unequivocally indicated on the first page of the Certificate of Conformity (Device intended for operation with a type device).
Notes
Interface protection settings are password protected and can be adjusted within the specified range. In case of using the aforementioned devices with an external protection device, the inverter protection settings must be adjusted according to the manufacturer's declaration. Any modifications affecting the tests must be indicated by the product manufacturer/supplier to ensure the product meets all requirements.