Broan B98DHV/B120DHV Installation & Operation Instructions

The B98DHV and B120DHV are ventilating dehumidifiers that integrate into the heating and cooling system to provide the ultimate in comfort, health and property protection through:

Serial Number: ____________________

Install Date: ____________________

Sold By: ____________________

ETL Listed

Engineered & Assembled in Madison, WI

Table of Contents

These Broan dehumidifiers conform to unified standard UL 60335-2-40 and CSA standard C22.2.60335-2-40.

Brand Name Individual Model Number Basic Model Number Rating Conditions Integrated Energy Factor (L/kWh) Capacity (Pint/Day)
Broan B98DHV 4044350 98.1-W 73F/60% 2.217 71.4
Broan B120DHV 4044450 120.1-W 73F/60% 2.106 88

FOR REPAIR & TECH SUPPORT: 1-800-558-1711 (follow prompts)

Broan is committed to manufacturing quality products. To maintain our standards, product specifications may change without notice.

Broan, LLC
926 West State Street, Hartford, WI 53027
www.Broan-NuTone.com
800-558-1711

Safety Instructions

! WARNING! THIS SYMBOL MEANS IMPORTANT INSTRUCTIONS. FAILURE TO HEED THEM CAN RESULT IN SERIOUS INJURY OR DEATH.

▲ CAUTION! THIS SYMBOL MEANS IMPORTANT INSTRUCTIONS. FAILURE TO HEED THEM CAN RESULT IN INJURY OR MATERIAL PROPERTY DAMAGE.

Read the installation, operation and maintenance instructions carefully before installing and operating this device. Proper adherence to these instructions is essential to obtain maximum benefit from the Broan Whole House Ventilating Dehumidifier.

▲ WARNING! 120 VOLTS MAY CAUSE SERIOUS INJURY FROM ELECTRIC SHOCK. DISCONNECT ELECTRICAL POWER BEFORE STARTING INSTALLATION OR SERVICING, AND LEAVE POWER DISCONNECTED UNTIL INSTALLATION OR SERVICE IS COMPLETED.

▲ CAUTION!

REFRIGERANT SAFETY GROUP A2L

▲ WARNING! DO NOT USE MEANS TO ACCELERATE THE DEFROSTING PROCESS OR TO CLEAN, OTHER THAN THOSE RECOMMENDED BY THE MANUFACTURER. THE APPLIANCE SHALL BE STORED IN A ROOM WITHOUT CONTINUOUSLY OPERATING IGNITION SOURCES (FOR EXAMPLE: OPEN FLAMES, AN OPERATING GAS APPLIANCE, OR AN OPERATING ELECTRIC HEATER. DO NOT PIERCE OR BURN. BE AWARE THAT REFRIGERANTS MAY NOT CONTAIN AN ODOR.

Dehumidifier Set Up

Location Considerations

Unventilated Areas

Unventilated areas where the dehumdifier is installed or stored need to be so constructed that should any refrigerant leak, it will not stagnate so as to create a fire or explosion hazard.

The dehumidifier shall not be stored or ducted into one or multiple rooms with continuously operating open flames (for example an operating gas appliance) or other POTENTIAL IGNITION SOURCES (for example an operating electric heater, hot surfaces). A flame-producing device may be installed in the same space if the device is provided with an effective flame arrest.

▲ CAUTION! REMOVE COMPRESSOR SHIPPING TIE FROM THE UNIT. FAILURE TO REMOVE SHIPPING TIE WILL CAUSE EXCESS VIBRATION TO BE TRANSMITTED TO THE FRAME.

Removal of Compressor Shipping Support

The Dehumidifier uses a compressor to power the refrigeration system. To protect the compressor and refrigeration system during shipping, a plastic tie wrap secures it to the unit's frame. Remove the tie wrap by cutting the tie wrap and pulling from the unit as shown. After removing tie wrap, insert plastic plugs provided into the holes.

ATTENTION/ATENCION

Before turning on unit:

  1. Cut and remove zip tie.
  2. Insert included plugs into holes.

Avant de mettre l'unité en marche:

  1. Couper l'attache et la et la retirer.
  2. Insérer les bouchons inclus dans les trous.

Antes de encender la unidad:

  1. Corte y retire el amarre
  2. Inserte los tapones en los agujeros.

Diagram showing clearances:

6" Minimum Clearance For Proper Airflow

Top View

Electrical Service Access (Either Side)

Filter

Drain Port

15"

9' Power Cord

For Filter (Either Side)

A 6" Fresh Air Intake (Optional)

B 10" Return Air Inlet

C 10" Supply Air Outlet

Attaching Duct Collars

Fresh Air Ventilation Duct

Fresh air ventilation is optional. A 6" diameter duct is attached to the unit. The 6" duct should be capped if fresh air is not desired. If setting up the unit to provide fresh air ventilation, see page 10.

Return Air Inlet

A 10" diameter duct collar is attached to the unit.

Supply Air Outlet

The back panel of the dehumidifier can be rotated to allow for horizontal flow through or vertical flow through of the supply air.

Horizontal Flow Through

The unit ships configured for a horizontal flow through. A 10" diameter duct collar is attached to the unit.

Vertical Flow Through

Remove the exhaust panel using a T25 torx bit. Rotate the panel so the exhaust collar is located on the top of the unit. Align screw holes and snap the panel onto the base. Secure the exhaust panel to the base by replacing the six screws.

Diagrams showing horizontal and vertical flow through:

Horizontal Flow Through (End Discharge)

A 6" Fresh Air Inlet (Optional)

B 10" Return Air Inlet

C 10" Supply Air Outlet

Front View

Rear View

Vertical Flow Through (Top Discharge)

A 6" Fresh Air Inlet (Optional)

B 10" Return Air Inlet

C 10" Supply Air Outlet

Front View

Top View

Rear View

Electrical Requirements

The Dehumidifier plugs into a common grounded 115 VAC outlet. Locate the dehumidifier in an area where the cord's length (9') easily reaches a 115 VAC electrical outlet with a minimum of 15 Amp circuit capacity. If used in an area that may become wet, a GFCI protected circuit is recommended. Consult local electrical codes for further information.

A variety of control devices can be used with this dehumidifier. The control is to be located remotely from the dehumidifier and placed in the space to be conditioned. A low voltage (24 Volt) control MUST be used with the Dehumidifier and MUST be connected with low voltage (18-22 gauge) thermostat wire.

▲ WARNING! THE REMOTE CONTROLS OF THE DEHUMIDIFIER ARE POWERED BY A LOW VOLTAGE CIRCUIT (24 VAC) AND MUST NEVER CONTACT OR BE CONNECTED TO A HIGH VOLTAGE CIRCUIT.

▲ CAUTION! DO NOT ALLOW THE 24V TERMINAL TO CONTACT THE COM/DMPR TERMINALS ON THE DEHUMIDIFIER OR DAMAGE TO THE TRANSFORMER WILL RESULT.

▲ CAUTION! SOME OF THE SCREW TERMINALS ON THE DEHUMIDIFIER MAY NOT BE USED WITH CERTAIN CONTROLS AND SHOULD BE LEFT UNCONNECTED.

Electrical Precautions

Wiring Diagram:

Diagram showing wiring connections for the dehumidifier.

Drain Installation

The Dehumidifier generates condensate.

Place a secondary drain pan with a float switch under the dehumidifier if it is suspended above a finished area or above an area where water leakage could cause damage.

A drain trap is required for the dehumidifier to drain properly. Install a 3/4" threaded male NPT adapter to the drain pan. Install a drain pipe assembly utilizing 3/4" PVC pipe to transport the condensate to a drain. Pitch of drain should be 1" per 10'.

An optional condensate pump kit is available for use with the Dehumidifier and may be installed if lift is required to dispose of condensate. Condensate is automatically pumped to a remote location when the water level in the pump's reservoir rises to close the float switch.

The pump also contains a safety float switch. The white leads from this switch extend from beneath the pump cover. This switch should be installed in series with the field wire that connects to the common lead from the Dehumidifier to the control panel. If the pump fails, this switch opens the common control circuit and stops water production before the reservoir overflows. Contact a qualified electrician to install the safety float switch to the Dehumidifier.

Note: An optional condensate pump kit can be purchased through your dealer or online.

Diagram showing drain installation:

Drain Installation

Side View

Drain Port.

Secondary Drain Pan

Drain Trap

Drain Trap

Drain Port

Secondary Drain Pan

Ducting to HVAC Systems

The recommended installation creates a separate return for the Dehumidifier in a central area of the structure. Duct the supply of the unit to the air supply of the existing HVAC system. Connect an insulated duct from outside to the 6" collar of the Dehumidifier to provide fresh make-up air.

▲ CAUTION! DO NOT CONNECT WITH A STATIC PRESSURE GREATER THAN OR EQUAL TO +0.5 WG. CONTACT TECHNICAL SUPPORT AT (800) 558-1711 FOR ADDITIONAL DETAILS.

Ducting Considerations:

Fresh Air Ventilation

Fresh air ventilation is optional.

Fresh air may be brought into the structure by connecting an insulated duct from outside the structure to the 6" inlet of the Dehumidifier. A ventilation control is needed to program the time and frequency that the unit introduces outside air. The time and frequency of ventilation should be based on the size and occupancy of the residence.

Fresh Air Ventilation With Dehumidifier Off and Fan Only Operation

Outside air mixes with the dehumidifier's return air before being supplied to the home. Outside temperature, inside temperature and relative humidity will impact the combined outlet air conditions.

Diagrams illustrating fresh air ventilation in hot and cold climates:

Hot Climate:

A 6" Fresh Air Inlet (Optional)

B 10" Return Air Inlet

C 10" Supply Air Outlet

Outdoor Air 90°F, 65%RH

Indoor Air 70°F, 50%RH

Mixed Air 75°F, 65%RH

Outlet Air 75°F, 65%RH

Cold Climate:

A 6" Fresh Air Inlet (Optional)

B 10" Return Air Inlet

C 10" Supply Air Outlet

Outdoor Air 30°F, 65%RH

Indoor Air 70°F, 50%RH

Mixed Air 59°F, 51%RH

Outlet Air 59°F, 51%RH

Note: Temperature and relative humidity may vary depending on duct distribution scheme.

Determine Ventilation Requirements

The MINIMUM ventilation requirement is calculated using ASHRAE 62.2-2016. Use one or both of the options below to determine your ventilation requirement. Follow all local and national building and safety codes.

Option 1: Calculating Airflow Requirement Using ASHRAE 62.2-2016 Airflow Equation

ASHRAE Airflow in CFM = [House Area in Sq.Ft. x 0.03] + [(Number of Bedrooms +1) x 7.5]

NOTE: Use ‘Number of Bedrooms + 1' or 'Number of Occupants', whichever is larger.

Example 1: Number of Bedrooms + 1

1800 square foot house with 3 bedrooms, 4 occupants = [1800 X 0.03] + [(3+1) X 7.5] = 84 CFM

Example 2: Number of Occupants

1800 square foot house with 3 bedrooms, 5 occupants = [1800 X 0.03] + [5 X 7.5] = 91.5 CFM

Record the required CFM: ____________________

Option 2: Calculating Airflow Requirement Using Table 4.1 from ASHRAE 62.2-2016

Ventilation Air Requirements, CFM

Floor Area (ft²) Number of Bedrooms
1 2 3 4 5
< 500 30 38 45 53 60
501 - 1000 45 53 60 68 75
1001-1500 60 68 75 83 90
1501 - 2000 75 83 90 98 105
2001 - 2500 90 98 105 113 120
2501 - 3000 105 113 120 128 135
3001-3500 120 128 135 143 150
3501-4000 135 143 150 158 165
4001 - 4500 150 158 165 173 180
4501-5000 165 173 180 188 195

Table 4.1 from ASHRAE 62.2-2016

Record the required CFM: ____________________

Controls

A control must be used with the dehumidifier. Broan offers the DEH 3000R proprietary control. The DEH 3000R allows homeowners to monitor and control relative humidity and proper ventilation levels in their home.

Note: The DEH 3000R is sold separately. Other controls are compatible with the dehumidifier.

Wiring Controls

▲ CAUTION! DO NOT ALLOW THE 24V TERMINAL FROM THE DEHUMIDIFIER TO CONTACT THE COM TERMINAL ON THE DEHUMIDIFIER OR DAMAGE TO THE TRANSFORMERS WILL RESULT.

Circuit Breaker

To prevent damage to the 24 volt control transformer, the Dehumidifier comes with a resettable circuit breaker. Check wiring for any electrical short and repair before resetting breaker. Resetting the circuit breaker without correcting the electrical short may result in transformer damage. Be sure to check the electrical schematic in this manual or inside the access panel of the Dehumidifier before making any control connections. The reset button for the circuit breaker can be found on the back of the unit.

Diagram showing rear view of B98DHV and B120DHV with circuit breaker reset button indicated.

Rear View

B98DHV

B120DHV

Circuit Breaker Reset Button

Control Connections

The control and the dehumidifier are labeled to prevent confusion. Depending on the control, some of the screw terminals on the Dehumidifier may not be used. Be sure to consult the electrical schematic in this manual or inside the access panel of the dehumidifier before making control connections.

A low voltage control must be used with the dehumidifier.

Terminal Block Control Operation:

Terminal Operation
COM 24VAC Power Transformer Neutral Side
FAN Fan Control
24V Transformer High Side
DEHU Dehumidification (Fan and Compressor) Control
FLOAT External Low Voltage Float Switch or Water Sensor (Use Normally Closed Switch)
FLOAT External Low Voltage Float Switch or Water Sensor (Use Normally Closed Switch)

Between the COM lead and the 24V TERMINAL is a 40VA transformer. This low voltage power source powers the relay coils which control the fan and compressors. This 24VAC transformer can also be used to power HVAC accessories external to the dehumidifier.

Function Connection
Compressor ON / Fan ON Make contact between 24V and DEHU terminals
Compressor OFF / Fan ON Make contact between 24V and FAN terminals
Power HVAC Accessory Connect the accessory to the DMPR (OR COM) and 24V terminals

NOTE: 18 gauge wire needed between the dehumidifier and the external control.

Air Filtration

The Dehumidifier is equipped with a MERV-13 (Dimensions: 1.75” x 14.00” x 17.50”) filter. The filter should be checked and replaced every three to six months. Operating the unit with a dirty filter will reduce dehumidifier capacity and efficiency.

DO NOT operate the unit without the recommended filter. Filter non-compliance voids the product warranty.

▲ CAUTION! MAKE SURE UNIT IS OFF BEFORE CHANGING THE FILTER.

Changing the Filter

For greatest filtration and efficiency of the dehumidifier, it is recommended the air filter be replaced every three to six months with a MERV 13 rated filter.

Step 1: Remove the magnetized filter door by pulling it off of the dehumidifier. You can remove it on either side to gain access to the filter.

Diagram showing filter door removal:

Optional Outdoor Air Intake

Return

Filter Door

Side View

Step 2: Remove the filter by gently pulling straight out of the unit. Insert new filter by gently pushing it straight into the unit. Make sure the AIR FLOW arrow on the filter is pointing into the unit.

Diagrams showing filter removal and insertion:

Fresh Air Intake (Optional)

Return

Filter

To Remove, pull out straight.

To Replace, push in straight.

Filter

Filter

Return

Return

Side View

Front View

Front View

Step 3: Attach the magnetized filter door back into place, ensuring it covers the filter compartment completely.

Diagram showing filter door reattachment:

Optional Outdoor Air Intake

Return

Filter Door

Side View

MERV Rating Chart

MERV Rating Chart

Standard 52.5 Minimum Efficiency Reporting Value Dust Spot Efficiency Arrestance Typical Controlled Contaminant Typical Applications and Limitations Typical Air Filter/Cleaner Type
20 n/a n/a <0.30 pm Particle Size Virus (unattached) Radioactive Materials Cleanrooms Pharmaceutical Man. >99.999% eff. On .10-.20 pm Particles
19 n/a n/a Carbon Dust Particles
18 n/a n/a Particulates
17 n/a n/a All Combustion Smoke
16 n/a n/a .30-1.0 pm Particle Size General Surgery Hospital Inpatient Care ≥99.97% eff. On 30 pm Particles Bag Filter - Nonsupported microfine fiberglass or synthetic media, 12-36 in. deep, 6-12 pockets.
15 >95% n/a All Bacteria
14 90-95% >98% Most Tobacco Smoke Smoking Lounges Box Filter - Rigid Style Cartridge Filters 6 to 12" deep may use lofted or paper media.
13 89-90% >98% Proplet Nuceli (Sneeze) 1.0-3.0 pm Particle Size Legionella Superior Commercial Buildings Bag Filter - Nonsupported microfine fiberglass or synthetic media, 12-36 in. deep, 6-12 pockets.
12 70-75% >95% Humidifier Dust Lead Dust Superior Residential Box Filter - Rigid Style Cartridge Filters 6 to 12" deep may use lofted or paper media.
11 60-65% >95% Milled Flour Better Commercial Buildings
10 50-55% >95% Auto Emissions Welding Fumes Hospital Laboratories Pleated Filters - Disposable, extended surface area, thick with cotton-polyester blend media, cardboard frame.
9 40-45% >90% Commercial Buildings
8 30-35% >90% 3.0-10.0 pm Particle Size Mold Spores Hair Spray Better Residential Cartridge Filters - Graded density viscous coated cube or pocket filters, synthetic media.
7 25-30% >90% Half Spray
6 <20% 85-90% Fabric Protector Dusting Aids Industrial Workplace Throwaway - Disposable synthetic panel filter.
5 <20% 80-85% Cement Dust Pudding Mix Paint Booth Inlet Throwaway - Disposable fiberglass or synthetic panel filter.
4 <20% 75-80% >10.0 pm Particle Size Pollen Minimal Filtration
3 <20% 70-75% Dust Mites Sanding Dust Spray Paint Dust Residential Washable - Aluminum Mesh.
2 <20% 65-70% Textile Fibers Carpet Fibers Window A/C Units Electrostatic - Self charging woven panel filter.
1 <20% <65%

Table Data Source: United States Environmental Protection Agency

Service

! WARNING! SERVICING THE DEHUMIDIFIER WITH ITS HIGH PRESSURE REFRIGERANT SYSTEM AND HIGH VOLTAGE CIRCUITRY PRESENTS A HEALTH HAZARD WHICH COULD RESULT IN DEATH, SERIOUS BODILY INJURY, AND/OR PROPERTY DAMAGE. ONLY QUALIFIED SERVICE PEOPLE SHOULD SERVICE THIS UNIT.

Warranty

A warranty certificate has been enclosed in this manual; read it before any repair is initiated. If a warranty repair is required, call the factory first at 1-877-420-1330 for warranty claim authorization and technical assistance.

Technical Description

The dehumidifier uses a refrigeration system similar to an air conditioner's to remove heat and moisture from incoming air, and add heat to the air that is discharged.

Hot, high-pressure refrigerant gas is routed from the compressor to the condenser coil. The refrigerant is cooled and condensed by giving up its heat to the air that is about to be discharged from the unit. The refrigerant liquid then passes through a filter/drier and expansion device which causes the refrigerant pressure and temperature to drop. It next enters the evaporator coil where it absorbs heat from the incoming air and evaporates. The evaporator operates in a flooded condition, which means that all the evaporator tubes contain liquid refrigerant during normal operation. A flooded evaporator should maintain nearly constant pressure and temperature across the entire coil, from inlet to outlet.

The compressor collects the cool refrigerant gas and compresses it to a high pressure and temperature to repeat the process.

Service Personnel

Only qualified HVAC or electrical contractors are allowed to conduct maintenance, service and/or repair operations on the dehumidifier. Examples include but are not limited to breaking into the refrigerating circuit, opening of sealed components, and/or opening of ventilated enclosures.

Detection of Flammable Refrigerants

Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

The following leak detection methods are deemed acceptable for all refrigerant systems:

NOTE: Examples of leak detection fluids are:

If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Removal of refrigerant shall be according to Clause DD.9 of 60335-2-40.

Refrigerant Removal and Evacuation

When breaking into the refrigerant circuit to make repairs or for any other purpose – conventional procedures shall be used. However, for FLAMMABLE REFRIGERANTS it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to:

Charging Procedures

In addition to conventional charging procedures, the following requirements shall be followed:

Decommissioning

Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its details. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant. It is essential that electrical power is available before the task commences.

Before attempting the procedure, ensure that:

Labelling Decommission Machines

Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. For appliances containing FLAMMABLE REFRIGERANTS, ensure that there are labels on the equipment stating the equipment contains FLAMMABLE REFRIGERANT.

Refrigerant Recovery

Troubleshooting

▲ CAUTION! TROUBLESHOOTING SHOULD BE PERFORMED BY A QUALIFIED HVAC TECHNICIAN.

Symptom Possible Reason Troubleshooting Procedure
Neither fan nor compressor running. Dehumidification is being called for. 1. Dehumidifier unplugged or no power to outlet.
2. Humidity control set too high.
3. Loose connection in internal or control wiring.
4. Defective compressor relay.
5. Defective control transformer.
6. Open circuit between FLOAT terminals.
▲ WARNING! ELECTRICAL SHOCK HAZARD: ELECTRICAL POWER MUST BE PRESENT TO PERFORM SOME TESTS. THESE TESTS SHOULD BE PERFORMED BY A QUALIFIED SERVICE PERSON.

Troubleshooting Procedure for Control Related Issues

This method of diagnosis will test the 3 main components of the control circuit individually to indicate any potential problems. This is to be used when the control will not activate the main unit.

  1. Detach field control wiring connections from the terminals on the main unit.
  2. Connect the 24V and FAN terminals together; only the fan should run. Disconnect the terminals.
  3. Connect the 24V and DEHU terminals together; fan and compressor should run. Disconnect the terminals.
  4. If this test works, the main unit is working correctly from a control standpoint.
  5. Reconnect field control wiring to the terminals on the main unit.
  6. Remove the control panel cover and detach the field wiring from the control connections.
  7. Connect the 24V and FAN terminals together; only the fan should run. Disconnect the terminals.
  8. Connect the 24V and DEHU terminals together; fan and compressor should run. Disconnect the terminals.
  9. If this test works, then the field control wiring is ok.
  10. If the problem persists, then the control is most likely faulty.
Compressor is not running. Dehumidification is being called for. Fan is running. 1. Defective compressor run capacitor.
2. Loose connection in compressor circuit.
3. Defective compressor overload.
4. Defective compressor.
5. Defrost thermostat open.
Compressor cycles on and off. Dehumidification is being called for. 1. Low ambient temperature and/or humidity causing unit to cycle through defrost mode.
2. Defective compressor overload.
3. Defective compressor.
4. Defrost thermostat defective.
5. Dirty air filter(s) or air flow restricted.
6. Defective fan or relay.

Troubleshooting (Continued)

Symptom Possible Reason Troubleshooting Procedure
Fan is not running. Dehumidification or fan is being called for. 1. Loose connection in fan circuit.
2. Obstruction prevents fan impeller rotation.
3. Defective fan.
4. Defective fan relay.
▲ WARNING! ELECTRICAL SHOCK HAZARD: ELECTRICAL POWER MUST BE PRESENT TO PERFORM SOME TESTS. THESE TESTS SHOULD BE PERFORMED BY A QUALIFIED SERVICE PERSON.

Troubleshooting Procedure for Performance Related Issues

This method of diagnosis is used to function check the internal components in the dehumidifier. This is to be used when a performance issue is suspected.

  1. Set the humidity controller all the way to the most humid setting or off position – Did the unit shut off?
  2. If yes, turn the fan setting to the ON position – does the fan start?
  3. If fan starts, leave in the fan ON position and set the humidity all the way to driest setting. May have to wait 5 minutes for the compressor to start.
  4. Listen for a distinct buzzing/humming sound of a compressor starting up – do you hear this noise?
  5. If compressor is running and continues to run, after about 15 minutes you should feel a slight increase in air temperature being discharged out of the discharge air side of the unit.
  6. If so, depending on your environmental conditions (temp/Rh%), you should see some water production out of the hose within 30 minutes or so. (Note: If the room temperature is 55 degrees or below and/or in area of low relative humidity, the dehumidifier will produce little to no water.)
  7. Collecting the water removed in a 24 hour period will give a measurement of performance.
Low dehumidification capacity (evaporator is frosted continuously). Dehumidification is being called for. 1. Defrost thermostat loose or defective.
2. Low refrigerant charge.
3. Dirty air filter(s) or air flow restricted.
4. Excessively restrictive ducting connected to unit.
No ventilation. Ventilation is being called for. 1. Loose connection in ventilation control circuit.
2. Loose connection in damper power circuit.
3. Defective fresh air damper.
Dehumidifier removes some water, but not as much as expected. 1. Air temperature and/or humidity have dropped.
2. Humidity meter and or thermometer used are out of calibration.
3. Unit has entered defrost cycle.
4. Dirty air filter(s) or air flow is restricted.
5. Defective defrost thermostat.
6. Low refrigerant charge.
7. Air leak such as loose cover or ducting leaks.
8. Defective compressor.
9. Restrictive ducting.

Troubleshooting (Continued)

Symptom Possible Reason Troubleshooting Procedure
Control not powering dehumidifier. 1. No power to dehumidifier.
2. 24 volt circuit breaker tripped or faulty transformer.
3. Loose or missed wired control wires at humidity control.
4. Loose or missed wired control wires at unit.
5. Humidity control defective.
▲ WARNING! ELECTRICAL SHOCK HAZARD: ELECTRICAL POWER MUST BE PRESENT TO PERFORM SOME TESTS. THESE TESTS SHOULD BE PERFORMED BY A QUALIFIED SERVICE PERSON.
  1. Verify power to the unit at power outlet.
  2. Look for short in control wiring.
  3. Check wire connections at control and unit.
  4. Reset circuit breaker button on dehumidifier.

Refrigerant Charging

▲ WARNING! SERVICING THE DEHUMIDIFIER WITH ITS HIGH PRESSURE REFRIGERANT SYSTEM AND HIGH VOLTAGE CIRCUITRY PRESENTS A HEALTH HAZARD WHICH COULD RESULT IN DEATH, SERIOUS BODILY INJURY, AND/OR PROPERTY DAMAGE. SERVICE MUST BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN.

If the refrigerant charge is lost due to service or a leak, the leak should be repaired and a new charge must be accurately weighed in. If any of the old charge is left in the system, it must be recovered before weighing in the new charge. Refer to the unit nameplate for the correct charge weight and refrigerant type.

Warranty

Effective January 1, 2024

Limited Warranty. Broan, LLC ("Broan") warrants as follows: (i) the Broan Dehumidifier ("Product") will be free of material defects in workmanship or materials for a period of 5 years (“Five-Year Warranty") following the date of initial purchase of such Product by an original customer purchasing from Broan or an authorized reseller ("Customer"); and (ii) the Product's components will be free of material defects in workmanship or materials for a period of six (6) years following the date of initial purchase of such Product by a Customer.

Limitation of Remedies. CUSTOMER'S SOLE AND EXCLUSIVE REMEDY UNDER THE ABOVE LIMITED WARRANTY AND BROAN'S ENTIRE LIABILITY THEREUNDER, SHALL BE, AT THE SOLE OPTION OF BROAN, REPLACEMENT OR REPAIR OF SUCH PRODUCT OR ITS COMPONENTS (“COMPONENTS") BY BROAN OR BROAN'S AGENTS ONLY. REFRIGERANT, PIPING, SUPPLIES, TRANSPORTATION COSTS, LABOR COSTS INCURRED IN REPAIR OR REPLACEMENT OF SUCH COMPONENTS ARE NOT INCLUDED. THIS DISCLAIMER AND EXCLUSION SHALL APPLY EVEN IF THE EXPRESS WARRANTY AND LIMITED REMEDY SET FORTH HEREIN FAILS OF ITS ESSENTIAL PURPOSE. CUSTOMER ACKNOWLEDGES THAT NO REPRESENTATIVE OF BROAN OR OF ITS AFFILIATES OR RESELLERS IS AUTHORIZED TO MAKE ANY REPRESENTATION OR WARRANTY ON BEHALF OF BROAN OR ANY OF ITS AFFILIATES OR RESELLERS THAT IS NOT IN THIS AGREEMENT.

Disclaimer of Warranties. EXCEPT FOR ABOVE LIMITED WARRANTY, WHICH IS THE SOLE AND EXCLUSIVE WARRANTY PROVIDED WITH RESPECT TO THE PRODUCT AND ITS COMPONENTS, BROAN HEREBY DISCLAIMS ALL EXPRESS AND IMPLIED WARRANTIES, INCLUDING, WITHOUT LIMITATION, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.

Warranty Limitations. The foregoing limited warranty extends only to a Customer and shall be null and void upon attempted assignment or transfer. A "defect" under the terms of the limited warranty shall not include problems resulting from Customer's or Customer's employees', agents', invitees' or a third party's misuse, improper installation, improper design of any system in which the Product is included, abuse, lack of normal care, failure to follow written instructions, tampering, improper repair, or freezing, corrosion, acts of nature or other causes not arising out of defects in BROAN's workmanship or material. If a Product or Component is replaced while under warranty, the applicable limited warranty period shall not be extended beyond the original warranty time period. The limited warranty does not cover any costs related to changes to a Product or Component that may be required by any codes, laws, or regulations that may become effective after initial purchase of the Product by Customer.

Customer Responsibilities. As a further condition to obtaining warranty coverage hereunder, the Customer must send a valid warranty claim to BROAN such that BROAN receives such claim prior to the end of the applicable warranty period. BROAN shall have no obligation hereunder with respect to any claim received by BROAN after the expiration of the applicable warranty period. As a further condition to obtaining warranty coverage hereunder, the Customer must present forms of invoices evidencing proof of purchase of a Product. If such invoices do not clearly indicate the date of initial purchase by a Customer, the applicable Product's date of manufacture will be used instead of the date of initial purchase for the purpose of calculating the commencement of the applicable warranty period. Warranty service must be performed by BROAN or a servicer authorized by BROAN. In order to obtain warranty service, the Customer should call BROAN at 1-800-558-1711 and ask for the BROAN Products Service Department, which will then arrange for applicable warranty service. Warranty service will be performed during customary, daytime working hours. If the Product must be shipped for service, Customer shall be solely responsible for properly packaging the Product, for all freight charges, and for all risk of loss associated with shipment.

Limitation of Liability. IN NO EVENT SHALL BROAN, IN CONNECTION WITH THE DESIGN, SALE, INSTALLATION, USE, REPAIR, REPLACEMENT OR PERFORMANCE OF ANY PRODUCT, COMPONENT, PART THEREOF OR WRITTEN MATERIAL PROVIDED THEREWITH, BE LIABLE, TO THE EXTENT ALLOWED UNDER APPLICABLE LAW, UNDER ANY LEGAL THEORY FOR ANY SPECIAL, DIRECT, INDIRECT, COLLATERAL OR CONSEQUENTIAL DAMAGES OF ANY KIND. NOTWITHSTANDING THE ABOVE LIMITATIONS AND WARRANTIES, THE SOLE AND EXCLUSIVE LIABILITY OF BROAN, REGARDLESS OF THE NATURE OR THEORY OF THE CLAIM, SHALL UNDER NO CIRCUMSTANCES EXCEED THE PURCHASE PRICE OF THE PRODUCT, COMPONENT OR PART UPON WHICH THE CLAIM IS PREMISED.

Applicable Law and Venue. ANY ARBITRATION, ENFORCEMENT OF AN ARBITRATION OR LITIGATION RELATED TO THE PRODUCT WILL BE BROUGHT EXCLUSIVELY IN DANE COUNTY, WISCONSIN, AND CUSTOMER CONSENTS TO THE JURISDICTION OF THE FEDERAL AND STATE COURTS LOCATED THEREIN, SUBMITS TO THE JURISDICTION THEREOF AND WAIVES THE RIGHT TO CHANGE VENUE. CUSTOMER FURTHER CONSENTS TO THE EXERCISE OF PERSONAL JURISDICTION BY ANY SUCH COURT WITH RESPECT TO ANY SUCH PROCEEDING.

Miscellaneous. If any term or condition of this Limited Warranty is found by a court of competent jurisdiction to be invalid, illegal or otherwise unenforceable, the same shall not affect the other terms or conditions hereof or thereof or the whole of this Limited Warranty. Any delay or failure by BROAN to exercise any right or remedy will not constitute a waiver of BROAN to thereafter enforce such rights.

Models: 4044350, 4044450, B98DHV 100 Pint Dehumidifier, 100 Pint Dehumidifier, Pint Dehumidifier, Dehumidifier

File Info : application/pdf, 24 Pages, 2.26MB

PDF preview unavailable. Download the PDF instead.

Installation Guide B98DHV B120DHV R454B

References

Adobe PDF Library 17.0 Adobe InDesign 20.4 (Macintosh)

Related Documents

Preview Broan B98DHV/B120DHV Installation and Operation Instructions
Comprehensive guide for installing and operating Broan B98DHV and B120DHV ventilating dehumidifiers, covering setup, electrical requirements, ducting, controls, air filtration, and troubleshooting.
Preview Broan B98DHV/B120DHV Ventilating Dehumidifier Installation & Operation Instructions
Comprehensive installation and operation guide for Broan B98DHV and B120DHV whole-house ventilating dehumidifiers. Covers setup, electrical, drain, ducting, fresh air ventilation, controls, air filtration, service, and warranty information.
Preview Broan B70DHV Ventilating Dehumidifier Installation and Operation Manual
Comprehensive installation and operation instructions for the Broan B70DHV whole-house ventilating dehumidifier, covering setup, ducting, electrical, controls, air filtration, troubleshooting, and warranty information.
Preview Broan Fresh In™ Premium FIN-180P and FIN-180P-HW Installation Instructions
Comprehensive installation guide for Broan Fresh In™ Premium FIN-180P and FIN-180P-HW fresh air supply units, covering safety, planning, wiring, testing, and troubleshooting.
Preview Broan FRESH IN™ FIN-6MD Installation Instructions
Detailed installation guide for the Broan FRESH IN™ FIN-6MD motorized supply damper, covering preparation, installation steps, wiring diagrams, setup, testing, and troubleshooting for residential HVAC systems.
Preview Broan B33DHW Dehumidifier: Installation and Operation Manual
Comprehensive installation and operation guide for the Broan B33DHW built-in dehumidifier, covering setup, electrical requirements, maintenance, controls, troubleshooting, and warranty information.
Preview Broan Fresh Air Systems - 130 CFM ERV
Broan's Virtuo Air Technology™ provides advanced residential fresh air systems with integrated electronic airflow measurement, auto-balancing, and energy-efficient ECM motors. This document details the ERV unit's specifications, performance, and installation requirements.
Preview Broan Any Climate Fresh Air System - 150 CFM | BLP150E75NS
Broan's Any Climate Fresh Air System (150 CFM) with VIRTUO™ technology offers superior air quality, quick installation, and auto-balancing for residential ventilation. Features include MERV 8 filtration, ERV core, and energy-efficient operation.