Broan FRESH IN™ FIN-6MD Installation Instructions

Important Safety Information

Please take note that this manual uses the following symbols to emphasize particular information:

⚠ WARNING: Identifies an instruction which, if not followed, might cause serious personal injuries including possibility of death.

CAUTION: Denotes an instruction which, if not followed, may severely damage the unit and/or its components.

Note: Indicates supplementary information that may relate to optional parts or simply aim to facilitate a task.

General Warnings

⚠ WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSON(S) OBSERVE THE FOLLOWING:

General Cautions

CAUTION:

1. Preparation

Before you start:

Choose the best location and installation type for the FIN-6MD according to the current system. Ducting widely affects the performance of this type of device. Use the shortest, straightest duct run possible to maximize the results.

CAUTION: Do not install in an area where the temperature may exceed 160°F.

The installer shall ensure that, if necessary, an in-line heater sized according to the required airflow and outside design heating temperature from Manual J or ASHRAE table is installed to ensure that the air delivered to the AHU is never below the minimum temperature allowed by the manufacturer. The in-line heater shall have an integrated airflow sensor and an over temperature sensor to prevent heating in no-flow or low-flow conditions.

When deciding if a preheater is required and whether it should be installed BEFORE or AFTER the FIN-6MD, consider the following:

2. Installation

Always respect the orientation of the FIN-6MD and the direction of the airflow, as indicated on the unit.

Direct-to-AHU Installation

This is the fastest and easiest method:

  1. Make a 6-inch diameter hole in the return duct of your AHU.
  2. Install the seal on the FIN-6MD port that will insert into the AHU ducting. Make sure that the direction of the airflow indicated on the unit is respected.
  3. Install the 3 installation brackets on the unit.
  4. Mark and drill holes for the brackets on the AHU ducting and, using appropriate screws, secure the FIN-6MD to the duct of the AHU, making sure it is level horizontally. (Self-drilling screws are recommended to avoid marking and drilling steps.)
  5. Follow steps in section 3 to connect the insulated duct to the FIN-6MD.
  6. Perform the electrical connection to the AHU following the wiring diagram in section 4.

Installation Through a Horizontal Surface

  1. Make a hole in the surface that the duct will run through. Size the hole so that the vapor barrier of the insulated ducting is not damaged, and the insulation is not compressed.
  2. Install the 3 installation brackets on the unit.
  3. Run a piece of insulated duct through the hole and connect to the FIN-6MD following the steps in section 3. Make sure the direction of the airflow as indicated on the unit is respected.
  4. Push the excess ducting on the other side of the surface and, using appropriate screws, secure the FIN-6MD to the surface.
  5. Run the insulated duct to the AHU and connect to the AHU ducting, making sure that the vapor barrier sealing is leak-free.
  6. Follow steps in section 3 to connect the second insulated duct to the FIN-6MD.
  7. Perform the connections to the AHU following the wiring diagram in section 4.

Mounting Under, Above, or Beside a Structure

The unit can be mounted in various orientations: under, above, beside, or suspended.

  1. Install 2 installation brackets on the unit, according to the surface the unit will mount to.
  2. Using appropriate screws, secure the FIN-6MD to the structure, making sure it is level horizontally. Make sure the direction of the airflow as indicated on the unit is respected.
  3. Follow steps in section 3 to connect both insulated ducts to the FIN-6MD.
  4. Run the insulated duct to the AHU and connect to the AHU ducting, making sure that the vapor barrier sealing is leak-free.
  5. Perform the connections to the AHU following the wiring diagram in section 4.

3. Connecting the Insulated Ducts to the Unit

CAUTION: Always use insulated ducting of a minimum R-4 insulation factor.

  1. Slide the inner flexible duct over the port and secure it using a tie wrap.
  2. Pull the insulation over the flexible duct and port without compressing it.
  3. Use duct tape to seal the outer membrane of the insulated duct to the outer ring of the port.

⚠ WARNING: Make sure the outdoor intake hood is at least 18 inches above the ground and 6 feet away from any of the following: Dryer exhaust, high-efficiency furnace vent, central vacuum vent, gas meter exhaust, gas barbecue-grill, any exhaust from a combustion source, garbage bin and any other source of contamination.

Note: Make sure that the outdoor intake hood is easily accessible for annual maintenance. If located above the first floor, place it close to a window or balcony to allow easy access.

4. Wiring Diagram

⚠ WARNING: Risk of electric shock. Electrical wiring must be done by qualified personnel in accordance with all applicable codes and standards. Before connecting wires, switch off the power to the AHU at the service panel and lock service disconnecting means to prevent power from being switched on accidentally.

CAUTION: Faulty connections can cause damage to the AHU, to the thermostat and/or to this unit. Always double check connections before turning power back on.

Wiring Color Code

Wiring Diagram Description

The diagram illustrates the connections for the FIN-6MD unit. It includes:

The terminal block can be removed for easier connection. Use the included tie wrap and the loop above the terminal block to secure the wires and reduce the risk of broken connections.

AHU Wiring Options

This section details how to connect the FIN-6MD to an Air Handling Unit (AHU) and thermostat.

The diagram references 'Ref.: 1103507 rev. C'.

5. Setting Up the Unit

When powered ON, the FIN-6MD performs a 30-second booting sequence followed by a 30-minute period where it stays OFF, but will activate if a heating or cooling call is sent to the AHU.

Refer to local building codes to determine the required airflow.

  1. Double-check the wiring, and turn power back ON to the AHU.
  2. Set the thermostat to send a heating or cooling call, or jump R and Y on the terminal block. This will force the ventilation ON for at least 5 minutes.
  3. Measure the airflow. If it needs adjustment, proceed to step 4. If not, go to step 5.
  4. The damper is factory set to the fully open position. To adjust it, set the left pot to 'DAMPER ADJUSTMENT' to start the AHU blower and wait 5 seconds. The LED will blink continuously to indicate the unit is in DAMPER ADJUSTMENT mode. While measuring the airflow, adjust the damper using the 'RUN TIME %' pot until the desired value is reached.
  5. Select the desired mode according to the table and map in section 7.3. This also saves the damper adjustment.
  6. Set the 'RUN TIME %' pot. The formula is: Run time % = Required Airflow / Measured Airflow. (Example: Run Time % = 60 CFM / 120 CFM = 50%)
  7. Install the supplied cover to protect the adjustment pots and prevent accidental changes.

6. Testing

The FIN-6MD performs a 30-second booting sequence upon power-on, followed by a 30-minute OFF period, activating only if a heating or cooling call is received by the AHU.

6.1 Blower Door Test (Force the Damper Closed)

If access to the integrated or remote switch is easy, set it to OFF. If access is difficult (e.g., in an attic):

  1. Turn OFF the power to the AHU at the service panel.
  2. Turn the power back ON at the service panel.
  3. Wait 30 seconds for the booting sequence.
  4. Ensure the thermostat does not send a heating or cooling call.
  5. The unit will remain OFF with its damper closed for 30 minutes, but will activate if a call is received.

6.2 Ventilation Test (Forcing the Unit On)

  1. Turn OFF the power to the AHU at the service panel, and ensure the integrated or remote switch is set to ON.
  2. Turn the power back ON at the service panel.
  3. Wait 30 seconds for the booting sequence.
  4. Set the thermostat to send a heating or cooling call, or jump R and Y on the terminal block. This will force the ventilation ON for at least 5 minutes.

7. User Information

7.1 Integrated and Remote Switches

The unit is equipped with an integrated ON/OFF switch. For convenience, a remote switch can also be connected. To use a remote switch, disconnect the integrated switch and connect the remote switch in the same manner.

7.2 User Servicing Instructions

7.3 Comfort Mode Selection

If the indoor air becomes too humid, or to prevent such conditions, the operation mode can be changed from Code-Compliant (modes 1 and 2) to Comfort Mode (modes A to E). Refer to the map for the correct choice.

When changing modes, only change the 'Mode' setting and leave the 'Run Time %' as set by the installer. Consult your HVAC contractor if in doubt.

Climate Zone Map and Mode Selection

A map of the United States is provided, color-coded to represent different climate zones (1 through 5, with sub-zones like 2A, 2B, 3A, etc.) used for selecting the appropriate comfort mode. The table below lists the modes and their recommended climate zones:

Selected Mode Climate Zones**
1 - Ashrae 2010/IRC/IMC (factory set)Zones 1-5
2 - Ashrae 2016/2019Zones 1-5
A - Comfort mode Hot / Humid #1Zones 2A and 1
B - Comfort mode Hot / Humid #2Zones 1 and 2A
C - Comfort mode Hot / DryZone 2B
D - Comfort mode Mixed / HumidZones 3A, 4A, 5A, 3C and 4C
E - Comfort mode Mixed / DryZones 3B, 4B and 5B

*Refer to the label on the unit for the full limits table. **As defined by the Department of Energy.

The unit has adjustment pots for 'DAMPER ADJUSTMENT' and 'RUN TIME %'. The 'DAMPER ADJUSTMENT' pot can set the damper from fully open to half open. The 'RUN TIME %' pot sets the operational percentage.

7.4 Troubleshooting

An LED indicator on the unit communicates different states:

8. Available Accessories

  1. Service Parts: The S1103502 replacement hardware kit is available, containing the same components as the original kit.
  2. Dry Contact Synchronization: The FIN-6MD can be synchronized with other HVAC units via a 24 VAC dry contact using the FIN-DCS option kit. This can be used for 'Output mode' (to activate other units) or 'Input mode' (to activate the FIN-6MD). Note: This functionality will not work if the unit is turned off.

For complete warranty statement and product registration, visit www.broan-nutone.com.

Contact Broan-NuTone LLC, Hartford, Wisconsin, at 800-558-1711.

Models: FIN6MD, 1103500D, FIN6MD FRESH IN Motorized Supply Damper, FIN6MD, FRESH IN Motorized Supply Damper, Motorized Supply Damper, Supply Damper, Damper

File Info : application/pdf, 4 Pages, 1.94MB

PDF preview unavailable. Download the PDF instead.

mebqupbheoxw

References

PScript5.dll Version 5.2.2 (C) 2018 Retailer Web Services LLC, all rights reserved.

Related Documents

Preview Broan Fresh In™ Premium FIN-180P and FIN-180P-HW Installation Instructions
Comprehensive installation guide for Broan Fresh In™ Premium FIN-180P and FIN-180P-HW fresh air supply units, covering safety, planning, wiring, testing, and troubleshooting.
Preview Broan Range Hoods & Ventilation Solutions: Improve Your Home's Air Quality
Explore Broan's comprehensive range of kitchen ventilation solutions, including high-performance range hoods, blowers, and accessories designed to enhance indoor air quality and create healthier home environments. Discover various styles and features for every need.
Preview Broan ERV100S and ERV100SP Energy Recovery Ventilator Installation Guide
Comprehensive installation guide for Broan ERV100S and ERV100SP Energy Recovery Ventilators, covering typical installations, unit preparation, ductwork, electrical connections, controls, balancing, service parts, and troubleshooting for residential use.
Preview Broan ERV100S Energy Recovery Ventilator Installation Guide
Comprehensive installation guide for the Broan ERV100S Energy Recovery Ventilator, covering typical residential installations, unit preparation, ductwork planning, electrical connections, controls, speed selection, balancing procedures, service parts, and troubleshooting. Includes safety warnings and detailed instructions for optimal performance and compliance with building codes.
Preview Broan F40000 Series Range Hood Installation and User Guide
Comprehensive guide for installing, using, and maintaining your Broan F40000 Series range hood. Includes safety tips, cleaning instructions, and troubleshooting advice.
Preview Broan FIN-180P & FIN-180P-HW Inline Supply Fan CSI Specification
This document provides the CSI specification for the Broan FIN-180P and FIN-180P-HW inline supply fans, detailing product requirements, submittals, quality assurance, delivery, storage, handling, field conditions, warranty, and execution for residential ventilation and indoor air quality.
Preview Broan HRV150FL HRV190FL Heat Recovery Ventilator Installer Manual
This installer manual provides comprehensive instructions for the installation, operation, and troubleshooting of Broan HRV150FL and HRV190FL Heat Recovery Ventilators. It includes detailed technical data, specifications, typical installation methods, ductwork planning, electrical connections, wiring diagrams, balancing procedures, and a service parts list, ensuring optimal performance and compliance for residential applications.
Preview Broan Any Climate Fresh Air System - 150 CFM | BLP150E75NS
Broan's Any Climate Fresh Air System (150 CFM) with VIRTUO™ technology offers superior air quality, quick installation, and auto-balancing for residential ventilation. Features include MERV 8 filtration, ERV core, and energy-efficient operation.