Danfoss ERC 21X Series Electronic Refrigeration Controller

Smart multipurpose refrigeration controller

Introduction

Application

The ERC 21X is a smart multipurpose refrigeration controller designed to fulfill today's requirement of commercial refrigeration applications. This controller is suitable for high, medium and low temperature applications with natural, electrical and hot gas defrost compatibilities.

Typical applications include Glass door merchandisers, commercial fridges and freezers, cold rooms and various other commercial refrigeration applications.

General description

The ERC 21X controller comes with four push buttons, a big display, easy and intuitive menu structure and pre-defined applications ensure ease of use. The controller is loaded with energy efficiency features like smart evaporator fan management, night mode, and defrosts on demand features.

A high capacity 16 A relay enables direct connection of heavy loads without the use of an intermediate relay: up to 2 hp compressors depending on its power factor and motor efficiency (power factor greater than 0.65 for 230 V and greater than 0.85 for 115 V).

Safe operation of the unit is ensured through voltage protection, zero cross switching, and high condenser temperature protection features.

ERC 21X series

Three versions of the ERC 21X are available in both 230 V AC, 50/60HZ and 115 V AC, 60Hz:

  • ERC 211: Single relay output for refrigeration and heating applications.
  • ERC 213: Three relays outputs for ventilated refrigeration and heating applications.
  • ERC 214: Four relays outputs for ventilated refrigeration and heating applications.

ERC 211

The ERC 211 has one relay output and two inputs (1 analogue, 1 analogue/digital). This controller can be used for either cooling or heating applications.

Functions

Voltage protection

The voltage protection ensures that the compressor motor is operating within safe voltage ranges. If the power supply voltage gets outside the specified high/low voltage cut-out ranges, the compressor is cut-out or restricted from starting. Normal compressor operation is resumed when the power supply voltage is back in the area between the high voltage cut-out limit and the low voltage cut-in limit.

Figure 4: Voltage protection illustrates this concept with a graph showing voltage limits over time.

Compressor protection

The compressor protection feature protects the compressor from short ON and OFF cycles by securing minimum run and stop time. This would allow the refrigeration system to stabilize before starting the compressor again and also avoid the chances of too many compressor cycles.

Figure 5: Compressor protection visually represents this with graphs of temperature and power to the compressor.

Compressor protection against high condensing temperature

If the condenser is blocking up with dirt and thereby reaches a too high condensing temperature, the controller will give the user early warning through condenser alarm. If the temperature rises further, it will switch the compressor OFF. If the temperature measured by the condenser sensor (Sc) is reaching the set “pre-alarm limit”, an alarm is raised, but no further action is taken. This is used to indicate to the user that something is wrong with the condenser. Often the reason is that the air flow to the condenser is restricted (dirt) or because the condenser fan is broken.

The alarm will reset if the condenser temperature drops back by 5 °C. If the measured condenser temperature continues to increase and reaches the set “Block limit”, the compressor is stopped, and it is restricted from starting again until the alarm is reset manually. The alarm can be reset manually by setting the parameter r12 Main switch to OFF position and back to ON position or by powering the controller down.

Figure 6: Compressor protection against high condensing temperature shows a graph of Sc temperature and compressor status.

Reference displacement

This feature enables the user to toggle between two different set-points quickly by activating a switch on digital input. This provides the facility to switch between two storage temperatures without getting into the menu. For example, meat requires different set points than vegetables. The reference displacement signal changes the normal thermostat set-point and the alarm limits by a predefined reference displacement offset value (r40).

Figure 7: Reference displacement displays a graph illustrating how cabinet temperature changes with reference displacement.

Night mode

Night mode helps to reduce cooling load and thereby power consumption during non-business hours, i.e., night time. The thermostat set point will be offset by a fixed value during night mode, keeping alarm limits the same.

Figure 8: Night mode illustrates the temperature profile during night mode.

Fan cycling during compressor OFF cycle

During compressor OFF cycle, the controller will run the fan with a defined duty cycle to maintain uniform temperature and delay the need for compressor switching ON.

Figure 9: Fan cycle shows the fan and compressor status over time.

Defrost on Demand

This feature records the evaporator temperature when it is clean and constantly monitors it at every compressor cut-out. If the evaporator temperature goes below the recorded temperature by the value set in parameter d30 before the configured defrost interval, it will trigger defrost immediately.

  • This function can only be used in 1:1 systems.
  • This function is disabled when the parameter “d30” is set to 20.
  • Defrost on demand is triggered only if the time since the last defrost session has ended is greater than ¼ of the defrost interval or 2 hours, whichever is lesser.
  • Defrost doesn't start by this method during the following scenarios:
    • Pull down mode
    • Night mode
    • Main switch in DI or main switch in Menu is in OFF position
    • Manual control mode
    • Evaporator temperature greater than 0 °C.

Applications

Pre-defined applications

The purpose of the pre-defined applications is to give the user an easy and fast way to configure the controller to a specific application based on storage temperature (LT, MT, HT), defrost type (none, natural, electrical), and defrost method (terminated on time or temperature).

When a user selects a specific application based on their requirements, the controller will load a specific set of parameter values and hide parameters that are not relevant for the selected application. Adjustment of the set of parameters value will still be possible at any time.

In addition to pre-defined applications, all controller versions have two standard applications: one with a full list of parameters and another with a simplified list of parameters, that allows the user to make their own customized parameter settings (AP0 and AP5 in case of ERC 211, and AP0 and AP6 in case of ERC 213 / ERC 214).

ERC 211 controller

Table 1: Pre-defined application table of ERC 211 controller
APP Description Temp. range Defrost end DO1 AI1 DI1(1)
AP0 Fully Configurable Standard Application (Cooling / Heating) NA
AP1 MT, No defrost 4 – 20 °C NA Sair DI1
AP2 MT, Natural defrost 2 – 6 °C Time Sair DI1
AP3 MT, Natural defrost, defrost stop by Sair 2 – 6 °C Sair temp Sair DI1
AP4 Heating Thermostat 30 – 70 °C NA DI1
AP5 Fully configurable simplified application (Cooling / Heating)

(1) The digital inputs DI1 can be configured for multiple functions (refer parameter "o02").

ERC 213 controller

Table 2: Pre-defined application table of ERC 213 controller
APP Description Temp. range Defrost end DO1 DO2 DO3 AI1 AI2 DI1(1) DI2(1)
AP0 Fully Configurable Standard Application (Cooling / Heating)
AP1 MT, Natural defrost, Alarm, fan 2 – 6 °C By time Sair NC DI1/Sc DI2
AP2 MT, Electrical defrost, Fan 0 – 4 °C By time Sair NC DI1/Sc DI2
AP3 LT, Electrical defrost, fan -24 – -18 °C By time Sair NC DI1/Sc DI2
AP4 MT, Electrical defrost, Fan 0 – 4 °C By temp(S5) Sair S5 DI1/Sc DI2
AP5 LT, Electrical defrost, Fan -26 – -20 °C By temp(S5) Sair S5 DI1/Sc DI2
AP6 Fully configurable simplified application (Cooling / Heating)
AP7 Heating Thermostat 30 – 70 °C NA Sair NC DI1 DI2

(1) The digital inputs DI1 and DI2 can be configured for multiple functions (refer Parameters "o02" and "o37"). NC = Not configured

ERC 214 controller

Table 3: Pre-defined application table of ERC 214 controller
APP Description Temp. range Defrost end DO1 DO2 DO3 DO4 AI1 AI2 DI1(1) DI2(1)
AP0 Fully Configurable Standard Application (Cooling / Heating)
AP1 MT, Natural defrost, Alarm, fan 2 – 6 °C By time Sair NC DI1/Sc DI2
AP2 MT, Electrical defrost, Fan 0 – 4 °C By time Sair NC DI1/Sc DI2
AP3 LT, Electrical defrost, fan -24 – -18 °C By time Sair NC DI1/Sc DI2
AP4 MT, Electrical defrost, Fan 0 – 4 °C By temp(S5) Sair S5 DI1/Sc DI2
AP5 LT, Electrical defrost, Fan -26 – -20 °C By temp(S5) Sair S5 DI1/Sc DI2
AP6 Fully configurable simplified application (Cooling / Heating)
AP7 Heating Thermostat 30 – 70 °C NA Sair NC DI1 DI2

(1) The digital inputs DI1 and DI2 can be configured for multiple functions (refer Parameters "o02" and "o37"). NC = Not configured

Electrical connection diagram

Table 4: Electrical connection diagram provides connection details for ERC 211, ERC 213, and ERC 214 controllers.

ERC 211: Terminals 1-4 are for power supply (115/230V) and digital outputs (DO1). Terminals 5-14 are for GND, TX, RX, +5V. Inputs include DO1, Sair, DI/Sc.

ERC 213: Terminals 1-4 are for power supply (115/230V) and digital outputs (DO1, DO2, DO3). Terminals 5-14 are for GND, TX, RX, +5V. Inputs include DO1, Sair, S5, Sc/DI1, DI2.

ERC 214: Terminals 1-4 are for power supply (115/230V) and digital outputs (DO1, DO2, DO3, DO4). Terminals 5-14 are for GND, TX, RX, +5V. Inputs include DO1, Sair, S5, Sc/DI1, DI2.

Note: Cables for sensors, DI inputs, and data communication must be kept separate from other high voltage cables to avoid electric noises. Use separate cable trays and maintain a distance of at least 10 cm between cables. Long cables at the DI input should be avoided.

Connector tightening torque and wire sizes:

  • Power connectors: wire size = 0.5 – 1.5 mm², max. tightening torque = 0.4 Nm
  • Low voltage signal connectors: wire size = 0.15 – 1.5 mm², max. tightening torque = 0.2 Nm
  • 2L and 3L must be connected to the same phase.

Configuration

Menu navigation and overview

Table 5: Key functions describes button operations:

  • Scroll up/down: Short press (< 1 second)
  • Main switch ON/OFF: Press and hold (~ 3 seconds)
  • Factory reset: Press and hold at Power up
  • Back function: Short press (< 1 second)
  • Pull down start/stop: Press and hold (~3 seconds)
  • Defrost Start/Stop: Press and hold (~3 seconds)
  • Set point change or OK: Short press (< 1 second)
  • Enter Menu: Press and hold (~ 3 seconds)

Table 6: Display icons shows common icons:

  • Night mode (Energy saving)
  • Fan running
  • Compressor running (Flashes in pull-down mode)
  • Active alarm
  • Defrost
  • Unit (°C or °F)

Quick configuration at power up

  1. STEP 1: Power on
  2. STEP 2: Select the quick configuration menu: Within 30 seconds of power on, press [BACK] for 3 seconds. The main switch "r12" is automatically set to OFF.
  3. STEP 3: Select pre-installed application o61: The display automatically shows the application selection parameter "o61". Press [SET] to select the pre-installed application. The display shows the default value (e.g., “AP0” flashing). Choose the application type by pressing [UP]/[DOWN] and press [SET] to confirm. The controller presets parameter values according to the selected application and does not hide relevant parameters. (Tip: You can easily move from AP0 to AP6 by pressing the [UP] key for a circular list.)
  4. STEP 4: Select sensor type "o06": The display automatically shows sensor selection parameter "o06". Press [SET] to select the sensor type. The display shows the default value (e.g., "n10" flashing). Choose sensor type by pressing [UP]/[DOWN] (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) and press [SET] to confirm. Note: All sensors must be the same type.
  5. STEP 5: Configure DO4 output "o36": The display automatically shows the o36 parameter to configure “DO4” output (available only in 4-relay models). Select "Lig" (Light) or "ALA" (Alarm) as per the application and press [SET] to confirm. The display returns to normal display mode, and the control starts.

Note: Refer to Pre-defined applications for a complete description of the available applications.

Quick configuration via cFg menu

  1. Press [SET] button for 3 seconds to access the parameter menu (display will show "cFg").
  2. Enter "CFg" menu by pressing [SET] button (display will show first parameter "r12" main switch).
  3. Select "r12" by pressing [SET] button again and set the main switch to "OFF" (r12=0).
  4. Press [BACK] button (<) to come back to "CFg" menu.
  5. Press [DOWN] button to scroll through the "cFg" menu parameter list.
  6. Open the "o61 application mode" and select the needed application mode (Press [SET]).
  7. Open the "o06 Sensor type" and select the temperature sensor type used (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) (Press [SET]).
  8. Open the "o02 DI1 Configuration" and select the function associated to digital input 1 (Press [SET]).
  9. Open the "o37 DI2 Configuration" and select the function associated to digital input 2 (Press [SET]).
  10. Navigate back to parameter "r12 Main switch" and set it in "ON" position to start control.
  11. Go through other parameters' default settings and change wherever needed.

Figure 10: Configuration illustrates the parameter navigation flow.

Figure 11: Adjust Setpoint shows how to change the setpoint using the [SET], [UP]/[DOWN] buttons.

Figure 12: Initiate a manual defrost explains how to start/stop defrost using the [DEFROST] button.

Figure 13: Initiate a pull down explains how to start/stop pull down using the [PULL DOWN] button.

Figure 14: View active alarm describes how alarms are displayed.

Figure 15: Unlock keyboard shows how to unlock the keypad.

Factory resetting

The controller can be set back to factory settings by using the following procedure:

  1. Power OFF controller.
  2. Keep [UP] and [DOWN] arrow buttons pressed while reconnecting the supply voltage.
  3. When the code "Fac" is shown in the display, select "yes".

Note: The OEM factory setting will either be the Danfoss factory settings or a user-defined factory setting if one has been made. The user can save their setting as OEM factory setting via parameter o67.

Display codes

Table 7: Display codes
Code Description
-d- Defrost cycle is in progress
Pud A temperature pulldown cycle has been initiated
Err The temperature cannot be displayed due to a sensor error
--- (top) Shown in top of display: The parameter value has reached max. Limit
--- (bottom) Shown in bottom of display: The parameter value has reached min. Limit
Loc The display keyboard is locked
UnL The display keyboard has been unlocked
PS The access code is required to enter the parameter menu
Axx/Exx Alarm or error code flashing with normal temp. readout
OFF Control is stopped as r12 Main switch is set OFF
On Control is started as r12 Main switch is set ON (code shown in 3 seconds)
Fac The controller is reset to factory setting

Parameters

Parameter description

Configuration

Table 8: Configuration
Code Parameter description Min. Max. Unit
cFg Configuration
r12 Main Switch
With this setting refrigeration can be started, stopped or a manual override of the outputs can be allowed. Service (manual control of outputs allowed) (-1 in Controller Display)
OFF (0 in Controller Display)
ON (1 in Controller Display)
-1 1
o61 Predefined applications
Predefined applications is to give the user an easy and fast way to configure the controller. Users can set appropriate application that meets their requirements under this menu (please refer predefined applications table under section 2.4 for more details). Predefined application is protected by main switch.
AP0 AP7
o07 Select main application type for which controller is used
rE= Cooling
Ht= Heating
rE Ht
o06 Sensor type
This parameter defines the type of temperature sensors connected to the controller. Below sensor types can be used in ERC21x
n5=NTC 5K (5000 Ohm at 25 °C, Beta value=3980 @25/100 °C)
n10= NTC 10 (10000 Ohm at 25 °C, Beta value = 3435 @ 25/100 °C)
pt1= PT1000
ptc= PTC
All the mounted sensors (Sair, S5 and Sc)must be of same type.
n5 ptc
o71 This parameter defines the desired configuration for Relay 2 (DO2)
dEF=Defrost
ALA=alarm
Lig=Light
dEF Lig
o36 This parameter defines the desired configuration for Relay 4 (DO4). Applicable only for ERC214.
Lig=Light
ALA=alarm
Lig ALA

Thermostat

Table 9: Thermostat
Code Parameter description Min. Max. Unit
r-- Thermostat
r00 SetPoint
This parameter defines the desired cabinet temperature at which compressor cuts out. The set point can be locked to a range within r02 and r03 settings.
-100.0 200.0 °C
r01 Differential
This defines the difference between the cut-out and the cut-in of compressor relay. Compressor relay will cut-in when the cabinet temperature reaches the set point+ differential. In case of heating application, heater will cut-in when the temperature reaches the set point-differential.
0.1 20.0 K
r02 Maximum Set Point limitation
The maximum allowable setpoint value can be configured here that would avoid setting too high values by mistake.
-100.0 200.0 °C
r03 Minimum Set Point limitation
The minimum allowable setpoint value can be configured here that would avoid setting too low values by accident/mistake.
-100.0 200.0 °C
r04 Display offset
Correction value in display temperature. If the temperature of the products / cabinet and the temperature received by the controller are not identical, an offset adjustment of the display temperature can be carried out using this parameter.
-10.0 10.0 K
r05 Display Unit
Set here if the controller is to show temperature values in °C or in °F. Switching from one to the other will cause all temperature settings to be automatically updated to respective unit.
-C -F
r09 Calibration of Sair
This parameter is a relative value and allows adjustment of the Sair sensor temperature. For instance, at a measured temperature of 7 °C and r09 set to 2K, the input from the Sair sensor will be 9 °C instead.
-20.0 20.0 K
r12 Main Switch
With this setting refrigeration can be started, stopped or a manual override of the outputs can be allowed. Stopped refrigeration will give a "OFF" signal on the display.
-1=service (manual control of outputs allowed)
0=OFF
1=ON
-1 1
r13 Night setback value
The thermostat's reference can be offset by this value during night or when there is no usage. Offset can be set both positive and negative sides (Select a negative value if there is to be cold accumulation). Activation can take place via digital input.
-50.0 50.0 K

Alarm settings

Table 10: Alarm settings
Code Parameter description Min. Max. Unit
A-- Alarm settings
A03 Delay for temperature alarm during normal conditions
High and low temperature alarm will be delayed by this value after crossing the set alarm limits. The alarm will not become active until the set time delay has been passed.
0 240 min
A12 Delay for temperature alarm during pull-down/start-up/defrost
Controller uses this time delay to trigger low and high temperature alarms during start-up, defrost and pull-down modes
0 240 min
A13 High temperature alarm limit
If the cabinet temperature stays above this limit for the time mentioned by the alarm delay parameters, high temperature alarm is raised.
-100.0 200.0 °C
A14 Low temperature alarm limit
If the cabinet temperature stays below this limit for the time mentioned by the alarm delay parameters, low temperature alarm is raised.
-100.0 200.0 °C
A27 DI1 delay
If Di1 is configured as a door open alarm or as an external alarm, this delay is used to raise the respective alarm.
0 240 min
A28 DI2 delay
If Di2 is configured as a door open alarm or as an external alarm, this delay is used to raise the respective alarm.
0 240 min
A37 Condenser high alarm limit
If the condenser temperature reaches above this limit, condenser alarm is raised immediately and no action is taken. The alarm is reset if temperature falls 5 K below the set temperature.
0 200 °C
A54 Condenser High block limit
If the condenser temperature continues to increase above the A37 limit and reaches this temperature limit, condenser block alarm is raised and compressor is stopped. It is restricted to starting again until alarm is reset manually. Manual reset of condenser block alarm can be performed by power cycling the controller either by main switch button or input supply.
0 200 °C
A72 Voltage protection
This parameter is to enable and disable the voltage protection feature, which protects compressor from adverse line voltage conditions.
no YES
A73 Minimum cut-in voltage
When the compressor is due to start, the voltage of the power supply will be checked and the compressor is allowed to start if the supply voltage is greater than this value.
0 270 V
A74 Minimum cut-out voltage
When the compressor is running, it will be switched OFF if the supply voltage goes below this value.
0 270 V
A75 Maximum voltage
When the compressor is running, it will be switched OFF if the supply voltage exceeds this value.
0 270 V

Defrost

Table 11: Defrost
Code Parameter description Min. Max. Unit
d-- Defrost
d01 Defrost type
Selection of desired defrost type
no= No defrost (defrost function disabled)
nAt = Natural defrost (Off cycle defrost)
EL = Electrical defrost
gAS = Hot gas defrost
no gAS
d02 Defrost stop temperature
This parameter defines at what temperature the defrost cycle will stop. Defrost can be stopped based on either evaporator sensor or by the cabinet temperature sensor as defined in menu code d10.
0.0 50.0 °C
d03 Defrost interval
Defines the maximum time period between the start of two defrost cycles. In case of power failure elapsed time is stored in the memory and next defrost will happen considering the stored time interval.
0 240 hour
d04 Maximum defrost time
This parameter defines the maximum time defrost will be performed. In case of temperature based defrost this is treated as safety time to stop the defrost if it is not terminated based on the temperature.
0 480 min
d05 Defrost delay at power up (or DI signal)
This parameter decides the time offset when the defrost is triggered by digital inputs or during power up. This function is only relevant if you have several refrigeration appliances or groups where you want the defrost to be staggered in relation to one another.
0 240 min

Fan

Table 12: Fan
Code Parameter description Min. Max. Unit
F-- Fan
F01 Fan control during compressor off cycle
This parameter define the fan operation during compressor off cycle.
FAo=Fan always ON
FFC=Fan follow compressor (Fan is switched off during compressor off cycle)
FPL= Fan Cycling
FAo FPL
F04 Fan stop evaporating temperature
This parameter defines the maximum evaporator temperature at which the Fan must switch OFF. If the defrost sensor registers a higher temperature than the one set here, the fans will be stopped to avoid the warm air circulation in the cabinet.
-50.0 50.0 °C
F07 Fan ON cycle
This parameter is applicable only when the Fan at Compressor cut out (F01) is set to Fan cycling mode. The Fan ON time will be as per the time set in this parameter.
0 180 min
F08 Fan OFF cycle
This parameter is applicable only when the Fan at Compressor cut out (F01) is set to Fan cycling mode. The Fan OFF time will be as per the time set in this parameter.
0 180 min

Compressor

Table 13: Compressor
Code Parameter description Min. Max. Unit
C-- Compressor
C01 Compressor minimum ON time
This parameter determines the minimum number of minutes the compressor must run before a cut-out can take effect based on temperature. This is to avoid sudden switching ON and OFF of the compressor. When used for Heating application, suggest to set this value 0 to avoid any overheating.
0 30 min
C02 Compressor minimum OFF time
This parameter determines the minimum number of minutes the compressor must switched OFF before a cut-in can take effect based on temperature. This is to avoid sudden switching OFF and ON of the compressor.
0 30 min
C04 Compressor OFF delay at door open
This parameter sets the delay to stop the compressor when the door is opened. If set to 900, the function is disabled.
0 900 sec
C70 Zero crossing selection
This feature will increase the relay life time, reduce the contact welding and switching noise by switching ON at Zero crossing.
Disable zero crossing when external relay is used.
no YES

Miscellaneous

Table 14: Miscellaneous
Code Parameter description Min. Max. Unit
o-- Others
o01 Delay of outputs at startup
After start-up the controller functions can be delayed by the time delay defined here so that overloading of the electricity supply network is avoided.
0 600 sec
o02 DI1 configuration
nC= Not configured
Sdc = Status display output
doo = Door alarm with resumption
doA = Door alarm without resumption
SCH = Main switch
nig = Day/Night mode
rFd = Reference displacement
EAL = External alarm
dEF = Defrost
Pud = Pull down
Sc = Condensor Sensor
nC Sc
o03 Serial Address
Data communication is possible by using external TTL to RS485 converter
0 247 No
o05 Password
If the settings in the controller are to be protected with an access code you can set a numerical value between 0 and 999. You can cancel the function by setting to 0.
0 999 No
o15 Display Resolution
This parameter defines the steps in which the temperature must be displayed by 0.1 or 0.5 or 1
0.1 1.0
o37 DI2 configuration
nC= Not configured
Sdc = Status display output
doo = Door alarm with resumption
doA = Door alarm without resumption
SCH = Main switch, nig = Day/Night mode
rFd = Reference displacement
EAL = External alarm
dEF = Defrost
Pud = Pull down
nC Pud
o38 This defines the method to control cabinet light
on= Always on
dAn = Day/Night
doo=Based on door action
on doo
o67 Save settings as factory
WARNING:
Original factory settings are overwritten
no YES
o91 Display during defrost
You can set what is to be displayed during defrost here.
Air = actual air temperature
FrE = freezed temperature (display the temperature just before starting defrost)
-d- = -d- is displayed
Air -d-
P73 DI1 input polarity
no (normally open) = associated functionality is activated when DI1 port is short circuit and deactivated when DI1 port is open circuit.
nc (normally closed) = associated functionality is activated when DI1 port is open circuit and deactivated when DI1 port is short circuit.
no nc
P74 DI2 input polarity
no (normally open) = associated functionality is activated when DI2 port is short circuit and deactivated when DI2 port is open circuit.
nc (normally closed) = associated functionality is activated when DI2 port is open circuit and deactivated when DI2 port is short circuit.
no nc
P75 Invert alarm relay
0=normal, 1= invert relay action
0 1
P76 Key board lock enable
Setting this parameter as "YES" enables controller keypad lock functionality after 5 minutes of no activity on the keypad. When the keypad is locked any button press shows "LoC" in the display. Press [UP] and [DOWN] buttons simultaneously for 3 seconds to unlock the keyboard. "unl" is displayed for 3 seconds.
no YES

Parameters: ERC 211

Table 16: Configuration
Function Code Min. Max. Unit AP0 AP1 AP2 AP3 AP4 AP5
Configuration cFg
Main switch (-1=Service, 0=OFF, 1=ON) r12 -1 1 1 1 1 1 1 1
Predefined applications o61(2) AP0 AP5 AP0 AP1 AP2 AP3 AP4 AP5
Cooling/Heating (rE=Cooling, Ht= Heating) o07(2) rE Ht rE rE(1) rE(1) rE(1) Ht(1) rE
Sensor type selection (n5=NTC 5K, n10=NTC10K, ptc=PTC, pt1=PT1000) o06(2) n5 ptc n10 n10 n10 n10 n10 n10

Parameters: ERC 213

Parameters: ERC 214

Product specification

Technical specification

Table 39: Technical specification
Features Description
Purpose of control Operating temperature sensing control suitable for incorporation into commercial air-conditioning and refrigeration applications
Construction of control Incorporated control
Power supply 115 V AC / 230 V AC 50/60 Hz, galvanic isolated low voltage regulated power supply
Rated power Less than 0.7 W
Inputs Sensor inputs, Digital inputs, Programming key
Connected to SELV limited energy <15 W
Allowed sensor types NTC 5000 Ohm at 25 °C, (Beta value=3980 at 25/100 °C - EKS 211)
NTC 10000 Ohm at 25 °C, (Beta value=3435 at 25/85 °C - EKS 221)
PTC 990 Ohm at 25 °C, (EKS 111)
Pt1000, (AKS 11, AKS 12, AKS 21)
Sensors included in kit Solution NTC 10000 Ohm at 25 °C, cable length: 1.5 m
Accuracy Measuring range:
-40–105 °C (-40 – 221 °F)
Controller accuracy:
±1 K below -35 °C, ±0.5 K between -35 -25 °C
±1 K above 25 °C
Type of action 1B (relay)
Output DO1 - Relay 1:
16 A, 16 (16) A, EN 60730-1
10 FLA / 60 LRA at 230 V, UL60730-1
16 FLA/72 LRA at 115 V, UL60730-1

DO2 - Relay 2:
8 A, 2 FLA/12 LRA, UL60730-1
8 A, 2 (2 A), EN60730-1

DO3 - Relay 3:
3 A, 2 FLA/12 LRA, UL60730-1
3 A, 2 (2 A), EN60730-1

DO4 - Relay 4:
2 A
Display LED display, 3 digits, decimal point and multi-function icons, °C + °F scale
Operating conditions -10+55 °C (14-131 °F), 90% Rh
Storage conditions -40-+70 °C (-40- +158°F), 90% Rh
Protection Front: IP65 (Gasket integrated)
Rear: IPOO
Environmental Pollution degree II, non-condensing
Overvoltage category II - 230 V supply version - (ENEC, UL recognized)
III - 115 V supply version - (UL recognized)
Resistance to heat and fire UL94-V0
Temperature for ball pressure test statement According to Annex G (EN 60730-1)
EMC category Emission: IEC/EN 61000 6-3, Immunity: IEC/EN 61000 6-2

Mounting

Figure 16: Mounting and Figure 17: Dismounting show the physical installation process.

Installation and Accessories

Installation steps

  • Place the wired controller in the slot and ensure rubber sealing is resting properly on the mounting surface.
  • Slide the mounting clips along the rails of the rear plastic from the rear side of the panel.
  • Slide the clips towards the mounting surface until the controller is firmly fixed.
  • To remove the controller, one needs to skillfully unlatch the snapping tab and pull the clips backwards.

Dimensions

Figure 18: Dimensions (mm) provides a diagram showing the controller's dimensions and drilling template.

Accessories

KoolKey (EKA200)

KoolKey acts as a gateway to connect PC tool KoolProg and also as a programming key.

Figure 19: KoolKey (EKA 200) as gateway and Figure 20: KoolKey (EKA 200) as programming key illustrate its use.

Mass Programming Key (EKA 201)

Mass Programming Key is a simple programming key for programming the controller in production assembly line.

Figure 21: Mass Programming Key (EKA 201) illustrates its connection.

Ordering

ERC 21X controllers

Table 40: ERC 21X controllers
Type Description Relay Qty. Code no.
ERC 211 ERC 211, Red LED, 115 V - Kit 1 1 080G3451
ERC 211, Red LED, 230 V - Kit 1 1 080G3453
ERC 211, Controller, Red LED, 230 V 1 1 080G3454
ERC 211, Controller, Red LED, 230 V, I-Pack 1 30 080G3459
ERC 213 ERC 213, Red LED, 230 V - Kit 3 1 080G3457
ERC 213, Controller, Red LED, 230 V 3 1 080G3458
ERC 213, Controller, Red LED, 230 V, I-Pack 3 30 080G3460
ERC 213 Red, 115 V USA - Kit 3 1 080G3467
ERC 213 Red, 230 V USA - Kit 3 1 080G3469
ERC 214 ERC 214, Controller, Red LED, 115 V - Kit 4 1 080G3466
ERC 214, Controller, Red LED, 230 V - Kit 4 1 080G3463

Programming tools and other accessories

Table 41: Programming tools and other accessories
Type Description Qty. Code no.
EKA 200 KoolKey - Gateway cum Programming key 1 080N0020
EKA 201 Mass Programming Key 1 080N0021
Interface cable Interface cable for ERC 21x, 1 m 1 080N0326

Sensors

Table 42: Sensors
Type Sensor element Sensor housing Cable Qty. Code no.
EKS 211 NTC 5000 ohm / 25 °C (Beta =3980 at 25/100 °C) Thermo plastic polyester 8x30 1.5 m 150 084B4403
Thermo plastic polyester 8x30 3.5 m 75 084B4404
Thermo plastic polyester 8x30 1.5 m 1 084N1220
Thermo plastic polyester 8x30 3.5 m 1 084N1221
EKS 221 NTC 10000 ohm / 25 °C (Beta =3435 at 25/85 °C) Thermo plastic rubber 6x5x15 3.5 m 150 084N3206
Thermo plastic rubber 6x5x15 3.5 m 1 084N3210
Thermo plastic rubber 6x5x15 8.5 m 50 084N3208
Thermo plastic rubber 6x5x15 8.5 m 1 084N3209
EKS 111 PTC 990 ohm / 25 °C Stainless steel 6x20 1.5 m 150 084N3200
Stainless steel 6x30 1.5 m 1 084N1178
Stainless steel 6x30 1.5 m 150 084N1161
Stainless steel 6x30 3.5 m 1 084N1179
Stainless steel 6x30 3.5 m 150 084N1163
Stainless steel 6x30 6 m 1 084N1180
Stainless steel 6x30 6 m 80 084N1173
Stainless steel 6x30 8.5 m 60 084N1168
AKS 11 PT1000 Top part: PPO (Noryl)
Bottom: stainless steel
3.5 m 1 084N0003
Top part: PPO (Noryl)
Bottom: stainless steel
5.5 m 1 084N0005
Top part: PPO (Noryl)
Bottom: stainless steel
8.5 m 1 084N0008
AKS 12 PT1000 Stainless steel 6x40 1.5 m 1 084N0036
Stainless steel 6x40 1.5 m 30 084N0035
Stainless steel 6x40 3.5 m 30 084N0039
Stainless steel 6x40 5.5 m 30 084N0038

Note: All the mounted sensors must be of same type.

Certificates, declarations, and approvals

The list contains all certificates, declarations, and approvals for this product type. Individual code numbers may have some or all of these approvals, and certain local approvals may not appear on the list.

Some approvals may change over time. You can check the most current status at danfoss.com or contact your local Danfoss representative if you have any questions.

Certificates, declarations, and approvals

Table 43: Certificates, declarations, and approvals
Regulatory and Compliance Directive / Document topic Standards Country - Marking
Electrical Safety (Incorporated Control for use in Class I or Class II equipment) Low Voltage Directive: 2014/35/EU EN IEC 60730-2-9:2019, EN IEC 60730-2-9:2019/A1:2019, EN IEC 60730-2-9:2019/A2:2020, EN 60730-1:2016, EN 60730-1:2016/A1:2019, EN 60730-1:2016/A2:2022 Europe - CE
Electrical Safety (control is validated to use as Incorporated) Recognized Component UL 60730-1 - 2009 - Revision 2014, UL 60730-2-9 : 2010, Revision : 2013 United States - CURUS
Electrical Safety (control is validated to use as Incorporated) Recognized Component CSA E60730-1 :2013, CSA E60730-2-9 : 2001, Revision : 2008, AMD 1 Canada - CURUS
Electrical Safety (Incorporated Control for use in Class I or Class II equipment) GB 14536.1:2008, GB 14536.10:2008 China - CQC
Electrical Safety & Electromagnetic Compatibility Supplier Declaration of Conformity (SDoC) EN 60730-1:2016, EN 60730 2-9:2019, EN 61000-6-2:2005 & EN 61000-6-3:2007+A1:2011 Ukraine - UA
Electrical Safety Certification of Conformity (CoC) CU TR 004/2011 Eurasia - EAC
Electromagnetic Compatibility EMC Directive: 2014/30/EU EN 61000-6-2:2005 & EN 61000-6-3:2007+A1:2011 Europe - CE
RoHS RoHS Directive: 2011/65/EU & 2015/863/EU EN IEC 63000:2018 Europe - CE
Food Safety Food Equipment NSF/ANSI standard 2 United States
Approved for use in Flammable Refrigerants Enclosed Break Device / sealed device nC (Relays) Sealed Device "nC" IEC 60079-15:2017, Europe
Enclosed-Break device "dC" IEC 60079-1:2014, clause 15.5.3
Europe
Approved for use in Flammable Refrigerants Enclosed Break Device (Relays) Sealed device "nC" UL 60079-15 and CAN/CSA C22.2 No. 60079-15, Enclosed-Break device "DC" IEC 60079-1:2014, clause 15.5.3 US and Canada
Enclosure Material Flammable Class UL 94, V-0 US
HACCP, Temperature Measuring probe in compliance with EN13485 Class I, when used with AKS 12 sensor EN 13485:2001 Europe
Certification and Manufacturer Declarations on Conformity CE, CURUS, CQC, UA, EAC, NSF, ROHS

Online support

Danfoss offers a wide range of support along with our products, including digital product information, software, mobile apps, and expert guidance. See the possibilities below.

The Danfoss Product Store

The Danfoss Product Store is your one-stop shop for everything product related—no matter where you are in the world or what area of the cooling industry you work in. Get quick access to essential information like product specs, code numbers, technical documentation, certifications, accessories, and more.

Start browsing at store.danfoss.com.

Find technical documentation

Find the technical documentation you need to get your project up and running. Get direct access to our official collection of data sheets, certificates and declarations, manuals and guides, 3D models and drawings, case stories, brochures, and much more.

Start searching now at www.danfoss.com/en/service-and-support/documentation.

Danfoss Learning

Danfoss Learning is a free online learning platform. It features courses and materials specifically designed to help engineers, installers, service technicians, and wholesalers better understand the products, applications, industry topics, and trends that will help you do your job better.

Create your Danfoss Learning account for free at www.danfoss.com/en/service-and-support/learning.

Get local information and support

Local Danfoss websites are the main sources for help and information about our company and products. Find product availability, get the latest regional news, or connect with a nearby expert—all in your own language.

Find your local Danfoss website here: www.danfoss.com/en/choose-region.

Models: ERC 211, ERC 213, ERC 214, ERC 21X Series Electronic Controller for Refrigeration, ERC 21X Series, Electronic Controller for Refrigeration, Controller for Refrigeration, for Refrigeration

PDF preview unavailable. Download the PDF instead.

BC194286421698en-001101 Danfoss A/S GPL Ghostscript 10.05.1

Related Documents

Preview Danfoss ERC 21X Series Electronic Refrigeration Control User Guide
This user guide provides comprehensive details on the Danfoss ERC 21X series of electronic refrigeration controllers, including models ERC 211, ERC 213, and ERC 214. It covers applications, functions, configuration, parameters, technical specifications, and accessories for these smart multipurpose refrigeration controllers.
Preview Danfoss ERC 21X Intelligent Multifunctional Refrigeration Controller User Manual
This user manual provides comprehensive information on the Danfoss ERC 21X intelligent multifunctional controller for refrigeration systems. It covers installation, operation, technical specifications, and troubleshooting for models ERC 211, ERC 213, and ERC 214.
Preview Danfoss ERC 102 Refrigeration Controller Reference Manual - Technical Guide
Comprehensive reference manual for the Danfoss ERC 102 electronic refrigeration controller. Ideal for OEMs and technicians, this guide details programming, installation, features, energy efficiency, and troubleshooting for commercial refrigeration applications.
Preview Danfoss EKA 201 Mass Programming Key Installation Guide
Installation guide for the Danfoss EKA 201 mass programming key, detailing its use for programming controllers on production lines. Covers writing and reading configuration files, controller programming steps, LED indicators, and compatible controller types.
Preview Danfoss EKA 201 Mass Programming Key Installation Guide
Installation guide for the Danfoss EKA 201 mass programming key, detailing how to program controllers in bulk. Covers controller compatibility, file transfer, and LED indications.
Preview Danfoss ERC 112 Bottle Cooler Controller Installation Guide
Installation guide for the Danfoss ERC 112 Bottle Cooler Controller, detailing technical specifications, wiring diagrams, parameter settings, and operational functions for optimal performance.
Preview Danfoss EKA 201 Mass Programming Key Installation Guide
Installation guide for the Danfoss EKA 201 mass programming key, detailing its use for programming regulators in a mounting chain. Includes steps for writing and reading configuration files, programming regulators, and LED indicators.
Preview KoolKey Type EKA 200 Installation Guide
Installation guide for the Danfoss KoolKey Type EKA 200, a gateway and programming device for Danfoss electronic controllers. Learn how to connect, program, and use KoolKey with KoolProg software.