Danfoss ERC 112 Bottle Cooler Controller
Installation Guide
Technical Specification
Model: ERC 112
Power Supply: 100-240 V AC Switch mode power supply. Average 0.7 W
Input: 5 inputs: 4 analogue (digital), 1 digital; user specific assignment
- Air/Evaporator / Condenser
- Light sensor: Danfoss ECO light sensor
- "DO1" (Compressor relay)
- Door sensor: all types, user specific
- Motion sensor
Output:
- "DO4": 120 V AC: 16 A resistive / FLA 16/LRA 72; 240 V AC: 10 A resistive / FLA 10/LRA 60
- "DO5": 8 A resistive, FLA 2/LRA 12, TV-1
- "DO6": 8 A resistive, 2(2) A FLA 2/LRA 12. TV-1
- Max 10 A total "DO4-6"
Probes: Danfoss NTC sensors and Danfoss ECO accessories, Danfoss PT1000 ohm/0°C
Connectors: Modular connector system for OEM customers, with optional output screw terminal adapter. Input connector type: Rast 2.5 Edge connectors. Output connector type: RAST 5 standard.
Programming: With Danfoss KoolProg, KoolKey and KoolDock
Assembly: 3 types for all controls: front mounting; brackets; fully integrated solution (requires OEM specific design of mounting hole)
Display: LED display, 3 digit, decimal point and multi functionality icons; °C/°F scale
Keypad: 4 buttons (integrated IP65 design), 2 left, 2 right; user programmable
Operating Conditions: 0°C-55 °C, 93% rH
Storage Conditions: -40 °C-85 °C, 93% rH
Range of Measurement: -40 °C-85 °C
Protection: Front: IP65. Rear: water and dust protection corresponds to IP31, accessibility of connectors limit rear part rating to IP00. Pollution degree II, non-condensing.
Environmental Resistance to heat & fire: Category D (UL94-V0). Category I.
Operating Cycles: Compressor relay: more than 175,000 at full load (16A (16A)). R290/R600a end-use applications employing in accordance to EN/IEC 60335-2-24, annex CC and EN/IEC 60335-2-89, annex BB. Glow wire according to EN/IEC 60335-1/IEC/EN 60730. UL60730.
Approvals: NSF, CQC, EAC, Ukraine
Dimensions:
- Front mounting: 78.25 mm x 71 mm
- Rear mounting: 78.25 mm x 71 mm
Wiring Diagram
ERC 112D / ERC 112C
Power Supply: 100-240 V AC ± 10% 50/60 Hz 0T55
Inputs: S1, S2, S3, S4, di
Outputs: DO1, DO2, DO3, DO4, DO5, DO6
Functional description of used sensors
Control temperature sensor
The control sensor must always be connected and is used for controlling the cut-in and cut-out of the compressor according to the set-point. The sensor is also used for the displayed temperature. Most common placement is in the return air to the evaporator.
Evaporator sensor
The evaporator sensor is only used for de-icing of the evaporator and has no control purpose. Place the sensor where the ice melts last.
Condenser temperature sensor
The condenser sensor is used to protect the compressor against high pressure when the condenser is blocked or the condenser fan fails. Place the sensor at the liquid side of the condenser. Use a metal bracket or metal tape to ensure good thermal conductivity. Be sure that the cable does not pass hot spots at the compressor or condenser that exceeds 80 °C.
ERC front and button functionality
Configurable functionality
Button | Function Operating |
---|---|
1 press | Increase/Decrease setpoint |
1 press and hold | Access menu |
2 press | OK |
2 press and hold | Toggle ECO mode |
3 press | Toggle light |
3 press and hold | Toggle defrost |
4 press | Toggle Fan |
4 press and hold | Toggle Alarm |
Configuration of outputs
Relay outputs | Compressor | Defrost Heating | Fan | Light | Alarm |
---|---|---|---|---|---|
DO1 (01C) | ON/OFF | ||||
DO2 (02C) | |||||
DO3 (03C) | |||||
DO4 (04C) |
Configuration of inputs
Input/ sensor | Cabinet sensor | Evapor. sensor | Conden. sensor | Door sensor | Light sensor | Movem. sensor | Comm. sensor |
---|---|---|---|---|---|---|---|
S1 | |||||||
S2 | |||||||
S3 | |||||||
S4 | |||||||
di | Toggle | Toggle | Increase | Decrease | Toggle | Toggle | Toggle |
Operation
Changing the setpoint:
Press UP/DOWN to adjust setup. After 30 seconds, the display automatically reverts to showing the current temperature.
Turning ON/OFF the ECO function
Press briefly to enter ECO mode. The green ECO symbol is lit when in ECO mode.
Activating manual defrost
Press briefly to start or stop defrost.
Acknowledging alarm
Press any button to acknowledge. After the acknowledge the temperature is displayed and the alarm symbol remains shown.
Menu structure
1. Parameter group
Press and hold 5 sec to access the menu.
2. Scroll through parameters group
Press: UP/DOWN to scroll through the menu.
3. Parameter name
To select: press the lower left button (OK).
4. Scroll through parameters
Press: UP/DOWN to find the desired parameter.
5. To confirm: press the lower left button (OK)
Scroll through group "dEF" parameters.
6. Press: UP/DOWN to enter the desired value
7. To accept: press the lower left button (OK) and return to parameter name
To exit without accept: press the upper left button (BACK)
To return to menu: press upper left button (BACK)
After 30 seconds of inactivity, the display automatically reverts to showing the current temperature.
Password protection
Password protection on three levels:
- LEVEL 1: shop (daily use by shop personnel)
- LEVEL 2: ser (service technician)
- LEVEL 3: OEM (OEM programming)
Parameter table
The parameter table lists all configurable settings for the ERC 112 controller, organized by function such as Thermostat, Fan, Light, Defrost, Compressor, Display, Alarm, Auto Heater Control, ECO strategy, and Assignment.
Each parameter includes a menu code, parameter name, description, default value, minimum and maximum allowed values, unit of measurement, and the current setting.
Example Parameters:
- Thermostat: Set point (SEt), Differential (diF), High Set point (HSE), Low Set point (LSE)
- Fan: Fan control method (FCt), Fan On Delay (Fod), Fan Stop delay (FSd)
- Defrost: Defrost type (dFt), Defrost terminate temp (dtt), Defrost Min Interval (dii)
- Compressor: Minimum Cutin voltage (uLi), Minimum cut-out voltage (uLo), Min Stop time (CSt)
- Display: Display intensity auto control (diC), Display Unit (CFu), Display Offset (doF)
- Alarm: High Temp Alarm (HAt), Low Temp Alarm (LAt), Door Open delay (dod)
- ECO strategy: ECO on / off (ECo), Door Actions (EdA), PIR Actions (EPA)
- Assignment: Sensor type configuration (S1C, S2C, S3C, S4C), Sensor application (S1A, S2A, S3A, S4A), Digital I/O configuration (diC), Output configuration (o1C, o2C, o3C, o4C), Button configuration (b1C, b2C, b3C, b4C, b5C, b1L, b2L, b3L, b4L, b5L)