KE2 Temp + Air Defrost Controller
For Medium Temperature Applications with Air Defrost
Condensed Quick Start Guide PN 20611
Q.3.65 September 2021
Complete Instructions Locations
Visit: http://ke2therm.com/product/ke2-temp-defrost/ and click the Link to Literature button.
QR code: KE2 Temp Literature
YouTube: KE2 Temp Videos
What's in the Kit
The following parts are included:
- (1) KE2 Temp + Air Defrost controller
- (1) temperature sensor - 45"
- (1) sensor ziptie
- (1) liquid tight cord grip
- (4) self-tapping mounting screws
- (2) screws for high voltage shield
- (1) programming sticker
Supplies List
The accessories required for the controller to work are supplied. However, some truck stock items may be needed. See the following list:
- Conduit to go between the controller & evaporator
- (2) conduit connectors (straight or elbow as required)
- (4) high voltage wires (matched to the load of the liquid line solenoid/compressor and the controller.)
- Wire labeling (numbers, colors, etc.)
- Additional wire ties
- 18 gauge twisted shielded pair (if extending sensor wires)
- Cat5e or cable rated for RS-485 communication (if adding communication)
- Foam insulation (if running wires outside the space)
- Silicone (for sealing any box penetrations)
Controller Navigation
Indicator Lights:
- Red blinking - Real Time Clock battery needs to be replaced
- Yellow light - non-critical alarm (system running)
- Green light - Liquid Line Solenoid (LLS) relay energized
- Green blinking - waiting on minimum run or off timer to start/stop refrigeration
Accessing Setpoints:
- Access Setpoint mode by pressing and holding ENTER until tS (temperature setpoint) displays on the screen.
- Use ▲ and ▼ buttons to scroll through available setpoints.
- Press ENTER to view the current setting.
- Use ▲ and ▼ to change the setpoint.
- Press ENTER to move between the digits to accelerate the changes.
- Press and hold ENTER to confirm each setpoint change.
- Press BACK to escape.
Setpoints
- tS = Temperature Setpoint
- diF = Differential
- CSH = Compressor Starts/Hour, Maximum
- dPd = Defrost Per Day
- dFt = Defrost Time
- HAO = High Alarm Offset
- LAO = Low Alarm Offset
- tAd = Temp Alarm Delay
- Adr = Mod Bus Address
- Unt = Units for temp display (FAH or CEL)
Only visible if CUS (custom) is selected for dPd (Defrost per day):
d1, d2, d3, d4, d5, d6, d7, d8, d9, d10, d11, d12
Alarms
When amber LED is lit:
- SSA = Shorted Sensor Alarm
- OSA = Open Sensor Alarm
- HtA = High Temp Alarm
- LtA = Low Temp Alarm
For a complete list of setpoints and descriptions see Q.3.20.
Basic Setpoints
Setpoint | Description | Minimum | Default | Maximum |
---|---|---|---|---|
tS | Temperature Setpoint | -50°F (-45°C) | 35°F | 100°F (38°C) |
diF | Differential | 1°F (1K) | 2°F | 30°F (17K) |
CSH | Max. Comp. Starts/Hr. | 5 (Off)* | 6 | 10 |
dPd | Defrost Per Day | 0 | 6 | 12, CUS** |
dFt | Defrost Time | 0 min | 15 min | 720 min |
HAO | High Alarm Offset | 1°F (1K) | 5°F | 10°F (6K) |
LAO | Low Alarm Offset | 1°F (1K) | 3°F | 10°F (6K) |
tAd | Temp Alarm Delay | 1 min | 90 min | 180 min |
Adr | Mod Bus Address | 1 | 1 | 247 |
Unt | Units for temp display | FAH | FAH | CEL |
*Selecting fewer than 5 compressor starts per hour results in the starts per hour feature being turned off. The compressor will then function on temperature only.
**Selecting CUS (custom) unlocks additional Setpoints. See Advanced Setpoints table.
Dimensions - Inches
Top View:
Width: 2.30, Height: 2.79, Depth: 2.30
Hole Diameter: 0.20
End View:
Width: 2.14
Overall Height: 4.50, Overall Width: 6.68
Wiring Diagram
Air Temp Sensor: Observe proper orientation of Ribbon Cable connection.
Controller Power Supply: Select correct voltage for controller power: 115 or 230V.
Relay Connections:
- Put jumper wire from L1 (terminal 1) to COM (terminal 5).
- 115/230 VAC
- NC, NO, COM terminals for relay.
Controller Power Supply: 120 (208-240)/1/60 CONTROLLER POWER SUPPLY
Load Connections:
- LLS (Liquid Line Solenoid) or COMPRESSOR CONTACTOR
- Neutral (L2)
Controller Navigation
Indicator Lights:
- Red blinking - Real Time Clock battery needs to be replaced
- Yellow light - non-critical alarm (system running)
- Green light - Liquid Line Solenoid (LLS) relay energized
- Green blinking - waiting on minimum run or off timer to start/stop refrigeration
Access Setpoint Mode:
- Press and hold ENTER until tS (temperature setpoint) displays on the screen.
- Use ▲ and ▼ to scroll through available setpoints.
- Press ENTER to view the current setting.
- Use ▲ and ▼ to change the setpoint.
- Press ENTER to move between the digits to accelerate the changes.
- Press and hold ENTER to confirm each setpoint change.
- Press BACK to escape.
Setpoints
- tS = Temperature Setpoint
- diF = Differential
- CSH = Compressor Starts/Hour, Maximum
- dPd = Defrost Per Day
- dFt = Defrost Time
- HAO = High Alarm Offset
- LAO = Low Alarm Offset
- tAd = Temp Alarm Delay
- Adr = Mod Bus Address
- Unt = Units for temp display (FAH or CEL)
Only visible if CUS (custom) is selected for dPd (Defrost per day):
d1, d2, d3, d4, d5, d6, d7, d8, d9, d10, d11, d12
Alarms
When amber LED is lit:
- SSA = Shorted Sensor Alarm
- OSA = Open Sensor Alarm
- HtA = High Temp Alarm
- LtA = Low Temp Alarm
For a complete list of setpoints and descriptions see Q.3.20.
Basic Setpoints
Setpoint | Description | Minimum | Default | Maximum |
---|---|---|---|---|
tS | Temperature Setpoint | -50°F (-45°C) | 35°F | 100°F (38°C) |
diF | Differential | 1°F (1K) | 2°F | 30°F (17K) |
CSH | Max. Comp. Starts/Hr. | 5 (Off)* | 6 | 10 |
dPd | Defrost Per Day | 0 | 6 | 12, CUS** |
dFt | Defrost Time | 0 min | 15 min | 720 min |
HAO | High Alarm Offset | 1°F (1K) | 5°F | 10°F (6K) |
LAO | Low Alarm Offset | 1°F (1K) | 3°F | 10°F (6K) |
tAd | Temp Alarm Delay | 1 min | 90 min | 180 min |
Adr | Mod Bus Address | 1 | 1 | 247 |
Unt | Units for temp display | FAH | FAH | CEL |
*Selecting fewer than 5 compressor starts per hour results in the starts per hour feature being turned off. The compressor will then function on temperature only.
**Selecting CUS (custom) unlocks additional Setpoints. See Advanced Setpoints table.
Related Documents
![]() |
KE2 Low Temp+Defrost Controller: Condensed Quick Start Guide A quick start guide for the KE2 Low Temp+Defrost controller (pn 20903) from KE2 Therm Solutions, covering parts, installation, navigation, menu access, wiring, and sensor placement for refrigeration systems. |
![]() |
KE2 Temp + Air Defrost Condensed Quick Start Guide A quick start guide for the KE2 Temp + Air Defrost controller, detailing its features, installation, and basic setpoints for medium temperature applications with air defrost. |
![]() |
KE2 Temp+Valve Control Installation Manual Installation manual for the KE2 Temp+Valve Control system by KE2 Therm Solutions, covering setup, wiring, programming, and operation for temperature, air defrost, and electronic valve control. |
![]() |
KE2 Therm Door Switch Installation and Configuration Guide A comprehensive guide to installing and configuring the KE2 Therm Door Switch for enhanced energy efficiency and temperature stability in refrigeration systems. Covers setup for various KE2 controllers, including Ethernet enabled and non-Ethernet enabled models. |
![]() |
KE2 EvapPanel Quick Start Guide A quick start guide for the KE2 EvapPanel, covering parts lists, installation, controller webpages, wiring schematics, sensor installation, and setpoint menus. |
![]() |
KE2 EdgeManager: Advanced Refrigeration Monitoring and Control The KE2 EdgeManager by KE2 Therm Solutions provides advanced communication for monitoring and controlling up to 35 KE2 Therm controllers and KE2 Wireless Sensors. Features include real-time data tracking, local data access, remote monitoring, and email alarm notifications for various refrigeration applications. |
![]() |
KE2 Evap-RE2 Contactor Panel Installation and Operation Guide Comprehensive guide for the KE2 Evap-RE2 Contactor Panel, detailing installation, setup, operation, and troubleshooting for optimal refrigeration system efficiency. |
![]() |
KE2 Therm Controller Firmware Update Guide (Bootloader v4.01) A comprehensive guide from KE2 Therm Solutions on how to update the firmware of KE2 Therm controllers using the bootloader utility, covering connection methods and verification. |