KE2 Temp+Valve Control Installation Manual

For Temp. Air Defrost, & Electronic Valve Control

KIT PN: 21301

Publication Date: Q.3.49 January 2023

What's in the Kit - Parts List

The following are included in the KE2 Temp + Valve kit, pn 21301:

  • (1) KE2 Temp+ Valve controller (pn21393 - controller only)
  • (1) 10' pressure transducer
  • (1) temperature sensor - 45"
  • (1) temperature sensor - 10'
  • (4) self-tapping mounting screws
  • (1) sensor zip tie
  • (1) screwdriver
  • (2) screws for high voltage shield

Supplies List

Standard truck stock items are required to install the controller. A list is provided below:

  • Conduit to go between the controller and the evaporator.
  • (2) Conduit connectors (straight or elbow as required).
  • (4) High voltage wires matched to the load of the liquid line solenoid/compressor and the controller.
  • Wire labeling (numbers, colors, etc.).
  • Additional wire ties.
  • 18 gauge twisted shielded pair (if extending sensor wires/adding communication).
  • Foam insulation (if running wires outside the space).
  • Silicone (for sealing any box penetrations).

Select Mounting Location

The KE2 Temp + Valve is designed for a wide range of applications, with many potential installation locations. Breaking down the installation location, by application, provides the most helpful reference.

Application Locations
Under counter Evaporator cabinet
Outside controlled space
Walk-in Evaporator cabinet
Adjacent to entrance
Above door
Side-by-side Above door

Visuals: Images depict typical mounting locations for Walk-in, Under Counter, Wine Cabinet, and Commercial applications.

Remote Monitoring, Control, Alarm Notifications

The Temp + Valve includes RS-485 Modbus communications, and can now be accessed remotely using the KE2 Edge Manager (KE2-EM). See page 4 for additional details.

Service Call Saver - Post Defrost Indicator

To eliminate unnecessary service calls, the KE2 Temp + Valve alerts the user when it is coming out of a defrost cycle using the onboard display. The display alternates between dEF and the actual temperature measured by the air sensor. This continues until the temperature has reached setpoint, or for the amount of time set by dFt (Defrost Time), whichever is shorter.

Wiring the Controller

The Temp + Valve was designed with functionality in mind. The controller accepts 120V / 208-240V to power the controller through the lower conduit connection. The temperature sensor, pressure transducer, valve, and communication wires are attached via the upper conduit connector.

  1. When wiring the controller, first remove the display by loosening the four corner screws. The display is connected to the lower board by a short ribbon cable. Caution: The board may be damaged if excessive force is used when removing the cover.
  2. After the four screws have been detached from the lower section, the cover may be gently moved to the side.
  3. Next, remove the high voltage protective cover. There are two screws holding it in place.
  4. With the high voltage cover removed, the two screw terminal connectors can be seen. The Red 2-position connector is the controller's power supply.
  5. Connect line (L1) 1 to the rightmost terminal position and neutral (L2) 2 to the terminal position.
  6. The liquid line solenoid-compressor contactor relay accepts a variety of input voltages and is not required to match the controller's input. See the table for relay ratings. The relay uses the 3-position screw terminal to make the connection on the board. It may control either the liquid line solenoid or as a pilot to the compressor contactor. When connecting the wires to the relay, the controller will be breaking one leg of the power.
  7. If the solenoid will use the same voltage as the controller, one leg of incoming power (L1) 5 should be connected to the common terminal of the liquid line solenoid relay (the leftmost terminal connection). The other leg of the incoming power (L2) should be connected directly to the solenoid lead. The remaining lead from the solenoid should be connected to the NO (normally open) 3 terminal (the center terminal location).
  8. Proper wiring practices must be followed. Local wiring codes take precedence over any information in this bulletin.
  9. Replace high voltage shield after wiring is completed.

Relay Rating

Outputs: (1) Relay Single Pole Double Throw Normally Open Normally Closed
140V 240V 120V 240V
FLA 5A 5A 5A 5A
Resistive 5A 5A 5A 5A
Pilot Duty 800VA 720VA 290VA 360VA

Low Voltage Connections

Air Temperature Sensor

The air temperature sensor terminal is located on the cover's circuit board and is permanently attached. The temperature sensor input consists of the right two terminal positions. The sensor is not polarized and may be connected in either orientation. The sensor should be fed through the top conduit connection before being attached to the board. This terminal is also used for an External System Off signal in certain control modes. (See diagrams for more detailed information.)

Suction Temperature Sensor

The suction temperature sensor terminal is located on the cover's circuit board and is permanently attached. The temperature sensor input consists of the middle two terminal positions. The sensor is not polarized and may be connected in either orientation. The suction temperature sensor is required when applying the controller with an electronic expansion valve. The sensor's proximity to the evaporator outlet differs slightly for electronically controlled valves from the placement of a TEV bulb. Due to the more refined control from an electronically controlled valve, the sensor must be placed as close to the outlet of the coil as feasible. Although the distance from the outlet is different, the nature of the refrigerant's flow through the tube remains unchanged, thus the orientation of the sensor remains at the 4 or 8 o'clock position. The sensor should be secured to the suction line using the included wire ties designed for low ambient operation. Only zip tie the sensor bulb; DO NOT zip tie the sensor cable. This terminal is also used for an External System Off signal in certain control modes. (See diagrams for more detailed information.)

Pressure Transducer

The pressure transducer terminal is located on the cover's circuit board and is permanently attached. The pressure transducer input consists of the 3 terminal positions on the left-hand side of the board. When replacing a mechanical expansion valve, the external equalizer can be repurposed for the pressure transducer. Cut and braze a 1/4" male SAE fitting with schrader valve to the external equalizer. The pressure transducer can alternatively be attached to the suction service port on the evaporator's suction header. If a suction port is not available, mount the pressure tap on the top of a horizontal section of tube, approx. 3 inches downstream of the suction temperature sensor.

Visuals: Diagrams show terminal connections for Air Temperature Sensor (TEMP 1, TEMP 2), Suction Temperature Sensor (TEMP 2, TEMP 3), and Pressure Transducer (3 terminals on the left). Also shows RS-485 communication terminals.

Accessing the KE2 Temp + Valve on a Local Area Network

When the KE2 Temp + Valve is connected to the KE2-EM communication device's serial terminal, the device will find the controller and provide immediate local network communication. More information on the KE2-EM is found in bulletin Q.5.62.

Accessing the KE2 Temp + Valve on the Internet

When used with the KE2-EM, the KE2 Temp + Valve can be accessed remotely through the KE2 Smart Access portal, anywhere Internet service is available. This allows monitoring and setup of alarm alerts (email/text) for system issues, even during holidays or vacations. More information on KE2 Smart Access is found in bulletin Q.1.34 and A.1.76.

Visual: Network diagram illustrating connection from existing network (wired or Wi-Fi) via KE2 Switch to KE2-EM, then to KE2 Wireless Sensors, and finally to WiFi-enabled devices (Smartphone, Tablet, Laptop) for service. Also shows KE2 Therm Ethernet and Modbus Controllers.

Webpage View

From the Webpage, users can monitor temperatures, relay status, and alarms, as well as make changes to setpoints and manually control the system.

Visual: Screenshot of the KE2 Temp + Valve webpage interface showing System State, Alarms, Setpoints, Device Info, and Manual Control options.

Programming the Controller

The controller's preset defrosts per day can be adjusted, automatically spacing defrosts based on the number of defrost cycles selected (0-12). Individual defrosts can also be scheduled for specific times.

KE2 Temp + Valve Control Basic Navigation

Understanding the KE2 Temp + Valve Defrost's menu structure simplifies configuration. Figure 1 shows basic button functions and a list of basic setpoints. A brief description of abbreviations is found on pages 15-16.

Figure 1:

Visual: Image of the KE2 Temp+Valve controller display showing "35.7" and "Hold for manual defrost".

Indicator lights:

  • Red light: Critical alarm (system is NOT running)
  • Yellow light: Non-critical alarm (system running)
  • Green light: Calling for refrigeration, liquid Line Solenoid (LLS)/compressor contactor relay energized.
  • Green blinking: Waiting on short cycle timer to energize/de-energize LLS/comp. contactor relay.

Accessing Setpoints:

  • Press and hold the ENTER button until 'CtL' (control type) displays.
  • Use the ↑ arrow to advance through available setpoints.
  • Press ENTER to view the current setting.
  • Use the ↑ and ↓ arrows to change the setpoint.
  • Press ENTER to move between digits to accelerate changes.
  • Press ENTER and hold to confirm each setpoint change.
  • Press BACK to escape.

Accessing the Menus

Visuals: Diagrams illustrate the navigation paths for ADVANCED MENUS and BASIC MENUS, showing button presses (BACK, ENTER, hold for 3 seconds) and setpoint selections (CtL, SHt, SH, HGb, SUb, etc.).

Variables Menu

Name Description Range
rtPRoom Temperature (not shown if in SUb, EEPR or EHGBP control, and input is pressure)-50°F to 100°F
LLtLeaving Liquid Temp (Subcool control only)-50°F to 150°F
SYSSystem Mode: Refrigerate, Defrost, Off, System Off (manually)rEF, dEF, OFF, SOF, ESO
SHSuperheat (only shown if SH or SHt control selected)0°F to 200°F
PrsPressure (only if input control type is pressure)-14.6 to 150 psig
SUtSuction Temperature (only if in SH or SHt control selected)-50°F to 150°F
SAtSaturation Temperature (only if in SH or SHt control selected, and Pt is selected as input)-87°F to 150°F
inLInlet Temperature (only if in SH or SHt control selected, and tt selected as input)-50°F to 150°F
OPnValve Percent Open0 to 100%
COrCompressor RelayOFF-On
ALSAlarm Status: See table below for alarm descriptions.nOA (no alarm), PSA, SSA, iSA, ASA, HSH, LSH, LPA, Pdt, SCC, HtA, HPA, LtA, LPA, PF

Alarm List

Alarms Description LED Refrigerant Abbreviation
CRITICAL System is off.System is off.RedR-22R22
iSA Inlet Sensor AlarmValve closes and turns system off.RedR-134a134
PSA Pressure Sensor AlarmValve closes and turns system off.RedR-404A404
SSA Suction Temperature Sensor AlarmValve closes and turns system off.RedR-407A40A
ASA Room (Air) Sensor AlarmAlarm occurs when the room temperature sensor input is open or shorted.AmberR-407C40C
HPA High Pressure AlarmOccurs when the temperature reading is above the Pressure set point + High Alarm Offset setpoint for the amount of time in setpoint High/Low Alarm Delay.; High Temperature or pressure alarm is suppressed while in defrost.AmberR-410A410
HSH High Superheat AlarmOccurs when superheat is 2 or more degrees above setpoint and valve is 100% open for 90 minutes; Clears when superheat is within 2 degrees of setpointAmberR-717717
NON-CRITICAL System is still running, and trying to maintain coolingSystem is still running, and trying to maintain coolingAmberR-422A42A
HtA High Temperature AlarmOccurs when the temperature reading is above the Temperature set point + Temperature differential set point + High Alarm Offset set point for the amount of time in setpoint High/Low Alarm Delay; High Temperature or pressure alarm is cleared and disabled while in defrostAmberR-422D42d
LPA Low Pressure AlarmWhen LPC (Low Pressure Cut Out) is enabled while in refrigeration mode, if compressor is shut off 3 times for pressure going below LPC set point without being satisfied on temperature, set alarm; Alarm is cleared when temperature is satisfiedAmberR-507507
LSH Low Superheat AlarmOccurs when superheat is less than 3 degrees for 5 minutes; Clears when superheat is above 3 Fahrenheit degreesAmberR-448A448
LSA Leaving Liquid Temp Sensor AlarmLeaving Liquid Temp Sensor (Temp 2) input is open or shorted. SUb (subcool) control mode only.AmberR-449A449
LtA Low Temperature AlarmOccurs when the temperature reading is below the Temperature setpoint - Low Alarm Offset setpoint for the amount of time in setpoint High & Low Temperature Alarm Delay; Low temperature or pressure is cleared and disabled when in defrostAmberR-450A450
Pdt Pump Down Timeout AlarmOccurs when call for pumping system down and the compressor is turned off due to time out instead of pressure reaching LPC setpoint for 2 consecutive times; Alarm is cleared when pressure reaches LPC setpoint instead of timing out.AmberR-438A438
PF Power FailureOccurs when the controller has lost power at some point, and controller had CUS (custom defrost schedule) selected under Defrosts Per DayAmberR-408A408
SCC Short Cycle Compressor AlarmOccurs when the compressor has to come back on because of pressure going above LPC set point without satisfying minimum off time. If this occurs 4 times while in Off mode, can be over multiple cycles, set alarm; Clear alarm if pressure does not go above LPC setpoint through minimum off time.AmberR-409A409
R-407F407
R-744744
R-513A513
R-458A458

Basic Menu: "Out of Box" or if Superheat (SHt)

SetpointDescriptionRangeDefault
CtLControl Type - EEV+Temp, EEV Only, EEPR, EHGBP, SubcoolSHt, EPr, HGb, SH, SUbSHt
EdtValve Type: Mechanical (tHr), KE2-HSV (HS), KE2-RSV (rS), SEI, SER, Carel (CrL), Custom (CUS)tHr, HS, rS, SEi, SEr, CrL, CUS**rS
SrStep Rate30 - 40030
SFSSteps Full Stroke20(0)-640(0)***50(0)***
UbMotor TypeUni-(unipolar), bi (bipolar)Unipolar
inPInput type when CtL is SH: pressure/temp (Pt) or temperature/temperature (tt)Pt, ttPt
rFGRefrigerant TypeSee Refrigerant List on Page 6404
SSPSuperheat Setpoint5.0°F (2.8K) to 50°F (28K)8.0°F (4.4K)
tSTemperature Setpoint-50°F (-45°C) to 100°F (38°C)35.0°F (9.7°C)
AdFAir Differential1.0°F (0.5K) to 30°F (17K)2.0°F (1.1K)
CSHCompressor Starts/Hour Maximum5 (Off)* to 106
dPdDefrost Per Day0 to 12, CUS**4
tOdTime of Day00:00 to 23:5912:00
d1Start time of Defrost #100 - 23diS (disabled)
d2Start time of Defrost #200 - 23diS
d3Start time of Defrost #300 - 23diS
d4Start time of Defrost #400 - 23diS
d5Start time of Defrost #500 - 23diS
d6Start time of Defrost #600 - 23diS
d7Start time of Defrost #700 - 23diS
d8Start time of Defrost #800 - 23diS
d9Start time of Defrost #900 - 23diS
d10Start time of Defrost #1000 - 23diS
d11Start time of Defrost #1100 - 23diS
d12Start time of Defrost #1200 - 23diS
dFtDefrost Time6 min to 720 min45 min

*Selecting fewer than 5 compressor starts per hour results in the starts per hour feature being turned off. The compressor will then function on temperature only.
** Selecting CUS (custom) unlocks additional Setpoints.
*** Last zero is truncated on the display.

Advanced Menu: "Out of Box" or if Superheat (SHt)

SetpointDescriptionRangeDefault
CtLControl Type - EEV+Temp, EEV Only, EEPR, EHGBP, SubcoolSHt, EPr, HGb, SH, SUbSHt
EdtValve Type: Mechanical (tHr), KE2-HSV (HS), KE2-RSV (rS), SEI, SER, Carel (CrL), Custom (CUS)tHr, HS, rS, SEi, SEr, CrL, CUS**rS
SrStep Rate30 - 40030
SFSSteps Full Stroke20(0)-640(0)***50(0)***
UbMotor TypeUni-(unipolar), bi (bipolar)Unipolar
inPInput type when CtL is SH: pressure/temp (Pt) or temperature/temperature (tt)Pt, ttPt
rFGRefrigerant TypeSee Refrigerant List on Page 6404
SSPSuperheat Setpoint5°F (2.8K) to 50°F (28K)8.0°F (4.4K)
tOPMaximum (Top) Operating Pressure setpointStandard: 10 psig to 150 psig
R-410A 10psig to 300 psig
R-744 10 psig to 500 psig
150 psig
LPCLow Pressure Cut Out Setpoint-5 psig to 138 psig8.0 psig
LPdLow Pressure Cut Out Differential1 to 50 psig15.0 psig
LPtLow Pressure Cut Out Delay0 to 15 min.0 min.
tSTemperature Setpoint-50°F (-45°C) to 100°F (38°C)35.0°F (4.4K)
AdFAir Differential1.0°F (0.5K) to 30.0°F (17K)2.0°F (1.1K)
CSHCompressor Starts/Hour Maximum5 (Off)* to 106
dPdDefrost Per Day0 to 12, CUS**4
tOdTime of Day00:00 to 23:5912:00
d1Start time of Defrost #100 - 23diS (disabled)
d2Start time of Defrost #200 - 23diS
d3Start time of Defrost #300 - 23diS
d4Start time of Defrost #400 - 23diS
d5Start time of Defrost #500 - 23diS
d6Start time of Defrost #600 - 23diS
d7Start time of Defrost #700 - 23diS
d8Start time of Defrost #800 - 23diS
d9Start time of Defrost #900 - 23diS
d10Start time of Defrost #1000 - 23diS
d11Start time of Defrost #1100 - 23diS
d12Start time of Defrost #1200 - 23diS
dFtDefrost Time6 min to 720 min.45 min.
HAOHigh Alarm Offset1°F (1K) to 10°F (6K)5.0°F
LAOLow Alarm Offset1°F (1K) to 10°F (6K)3.0°F
tAdTemp Alarm Delay1 min. to 180 min90 min
AdrAddress, Mod Bus Communications1 to 2471
UntUnits for temperature displayFAH or CELFAH
PrOProportional0 to 2553
intIntegral0 to 2555
dErDerivative0 to 2553
CLAManually Clear Alarms
FACReturn Controller to Factory Default Settings
SOFManually Enter System Off Mode
POSManually Adjust Valve Position0 to 100%
rELManually Control Relay

Basic Menu: EEV Control Only - No Thermostat (SH)

SetpointDescriptionRangeDefault
CtLControl Type - EEV+Temp, EEV Only, EEPR, EHGBP, SubcoolSHt, EPr, HGb, SH, SUbSH
EdtValve Type: Mechanical (tHr), KE2-HSV (HS), KE2-RSV (rS), SEI, SER, Carel (CrL), Custom (CUS)tHr, HS, rS, SEi, SEr, CrL, CUS**rS
SrStep Rate30 - 40030
SFSSteps Full Stroke20(0)-640(0)***50(0)***
UbMotor TypeUni-(unipolar), bi (bipolar)Unipolar
inPInput type when CtL is SH: pressure/temp (Pt) or temperature/temperature (tt)Pt, ttPt
rFGRefrigerant TypeSee Refrigerant List on Page 6404
SSPSuperheat Setpoint5.0°F (2.8K) to 50.0°F (28K)8°.0F (4.4K)

* Selecting fewer than 5 compressor starts per hour results in the starts per hour feature being turned off. The compressor will then function on temperature only.
** Selecting CUS (custom) unlocks additional Setpoints.
*** Last zero is truncated on the display.

Advanced Menu: EEV Control Only - No Thermostat (SH)

SetpointDescriptionRangeDefault
CtLControl Type - EEV+Temp, EEV Only, EEPR, EHGBP, SubcoolSHt, EPr, HGb, SH, SUbSH
EdtValve Type: Mechanical (tHr), KE2-HSV (HS), KE2-RSV (rS), SEI, SER, Carel (CrL), Custom (CUS)tHr, HS, rS, SEi, SEr, CrL, CUS**rS
SrStep Rate30 - 40030
SFSSteps Full Stroke20(0)-640(0)***50(0)***
UbMotor TypeUni (unipolar), bi (bipolar)Unipolar
inPInput type when CtL is SH: pressure/temp (Pt) or temperature/temperature (tt)Pt, ttPt
rFGRefrigerant TypeSee Refrigerant List on Page 6404
SSPSuperheat Setpoint5.0°F (2.8K) to 50.0°F (28K)8.0°F (4.4K)
tOPMaximum (Top) Operating Pressure setpointStandard: 10 psig to 150 psig
R-410A 10psig to 300 psig
R-744 10 psig to 500 psig
150 psig
LPCLow Pressure Cut Out Setpoint-5 psig to 138 psig8.0 psig
LPdLow Pressure Cut Out Differential1 to 50 psig15.0 psig
LPtLow Pressure Cut Out Delay0 to 15 min0 min.
tAdTemp Alarm Delay1 min to 180 min90 min
AdrAddress, Mod Bus Communications1 to 2471
UntUnits for temperature displayFAH or CELFAH
PrOProportional0 to 2553
intIntegral0 to 2555
dErDerivative0 to 2553
CLAManually Clear Alarms
FACReturn Controller to Factory Default Settings
SOFManually Enter System Off Mode
POSManually Adjust Valve Position0 to 100%
rELManually Control Relay

Basic Menu: Hot Gas Bypass (HGb) or EEPRV (EPr)

SetpointDescriptionRangeDefault
CtLControl Type - EEV+Temp, EEV Only, EEPR, EHGBP, SubcoolSHt, EPr, HGb, SH, SUbHGb/EPr
EdtHot Gas Bypass Valve Options
Electronic Pressure Regulating Valve Options
SDR-3(Sd3), SDR-4 (Sd4), Custom (CUS)
CDS 2-7 (Cd2), CDS 9-17 (Cd9 ), ESR12 (ES1), ESR20 (ES2), KVS15 (dS1), KVS42 (dS4) , Custom (CUS)
Sd4
Cd9
SrStep Rate30 - 40030
SFSSteps Full Stroke20(0)-640(0)***50(0)***
UbMotor TypeUni-(unipolar), bi (bipolar)Unipolar
inPPressure Setpoint0 psig to 138 psig50 psig
tSTemperature Setpoint-50.0°F (-45°C) to 100°F (38°C)35.0°F (9.7°C)
CSHCompressor Starts/Hour Maximum5 (Off)* to 106
dPdDefrost Per Day0 to 12, CUS**4
tOdTime of Day00:00 to 23:5912:00
d1Start time of Defrost #100 - 23diS (disabled)
d2Start time of Defrost #200 - 23diS
d3Start time of Defrost #300 - 23diS
d4Start time of Defrost #400 - 23diS
d5Start time of Defrost #500 - 23diS
d6Start time of Defrost #600 - 23diS
d7Start time of Defrost #700 - 23diS
d8Start time of Defrost #800 - 23diS
d9Start time of Defrost #900 - 23diS
d10Start time of Defrost #1000 - 23diS
d11Start time of Defrost #1100 - 23diS
d12Start time of Defrost #1200 - 23diS
dFtDefrost Time6 min to 720 min45 min

Advanced Menu: Hot Gas Bypass (HGb) or EEPRV (EPr)

SetpointDescriptionRangeDefault
CtLControl Type - EEV+Temp, EEV Only, EEPR, EHGBP, SubcoolSHt, EPr, HGb, SH, SUbHGb / EPr
EdtHot Gas Bypass Valve Options
Electronic Pressure Regulating Valve Options
SDR-3(Sd3), SDR-4 (Sd4), Custom (CUS)
CDS 2-7 (Cd2), CDS 9-17 (Cd9 ), ESR12 (ES1), ESR20 (ES2), KVS15 (dS1), KVS42 (dS4) , Custom (CUS)
Sd4
Cd9
SrStep Rate30 - 40030
SFSSteps Full Stroke20(0)-640(0)***50(0)***
UbMotor TypeUni-(unipolar), bi (bipolar)Unipolar
inPInput type when CtL is HgB: pressure (PrS )or temperature (tPr)PrS, tPrtPr
PSPPressure Setpoint0 psig to 138 psig50 psig
tSTemperature Setpoint-50.0°F (-45°C) to 100°F (38°C)35.0°F (9.7°C)
CSHCompressor Starts/Hour Maximum5 (Off)* to 106
dPdDefrost Per Day0 to 12, CUS**4
tOdTime of Day00:00 to 23:5912:00
d1Start time of Defrost #100 - 23diS (disabled)
d2Start time of Defrost #200 - 23diS
d3Start time of Defrost #300 - 23diS
d4Start time of Defrost #400 - 23diS
d5Start time of Defrost #500 - 23diS
d6Start time of Defrost #600 - 23diS
d7Start time of Defrost #700 - 23diS
d8Start time of Defrost #800 - 23diS
d9Start time of Defrost #900 - 23diS
d10Start time of Defrost #1000 - 23diS
d11Start time of Defrost #1100 - 23diS
d12Start time of Defrost #1200 - 23diS
dFtDefrost Time6 min to 720 min45 min
HAOHigh Alarm Offset1.0°F (1K) to 10.0°F (1K)5.0°F
LAOLow Alarm Offset1.0°F (1K) to 10.0°F (1K)3.0°F
tAdHigh & Low Temp or Pressure Alarm Delay1 min to 180 min90 min
AdrAddress, Mod Bus Communications1 to 2471
UntUnits for temperature displayFAH or CELFAH
PrOProportional0 to 2553
intIntegral0 to 2555
dErDerivative0 to 2553
CLAManually Clear Alarms
FACReturn Controller to Factory Default Settings
SOFManually Enter System Off Mode
POSManually Adjust Valve Position0 to 100%
rELManually Control Relay

Basic Menu: Subcool (SUb)

SetpointDescriptionRangeDefault
CtLControl Type - EEV+Temp, EEV Only, EEPR, EHGBP, SubcoolSHt, EPr, HGb, SH, SUbSUb
EdtValve Type: Mechanical (tHr), KE2-HSV (HS), KE2-RSV (rS), SEI, SER, Carel (CrL), Custom (CUS)tHr, HS, rS, SEi, SEr, CrL, CUS**rS
SrStep Rate30 - 40030
SFSSteps Full Stroke20(0)-640(0)***50(0)***
UbMotor TypeUni-(unipolar), bi (bipolar)Unipolar
inPInput type when CtL is SH: pressure/temp (Pt) or temperature/temperature (tt)Pt, ttPt
rFGRefrigerant TypeSee Refrigerant List on Page 6404
SSPSuperheat Setpoint5°F (2.8K) to 50°F (28K)8.0°F (4.4K)
tSTemperature Setpoint-50°F (-45°C) to 100°F (38°C)35.0°F (4.4K)

** Selecting CUS (custom) unlocks additional Setpoints.
*** Last zero is truncated on the display.

Advanced Menu: Subcool (SUb)

SetpointDescriptionRangeDefault
CtLControl Type - EEV+Temp, EEV Only, EEPR, EHGBP, SubcoolSHt, EPr, HGb, SH, SUbSUb
EdtValve Type: Mechanical (tHr), KE2-HSV (HS), KE2-RSV (rS), SEI, SER, Carel (CrL), Custom (CUS)tHr, HS, rS, SEi, SEr, CrL, CUS**rS
SrStep Rate30 - 40030
SFSSteps Full Stroke20(0)-640(0)***50(0)***
UbMotor TypeUni-(unipolar), bi (bipolar)Unipolar
inPInput type when CtL is SH: pressure/temp (Pt) or temperature/temperature (tt)Pt, ttPt
rFGRefrigerant TypeSee Refrigerant List on Page 6404
SSPSuperheat Setpoint5°F (2.8K) to 50°F (28K)8.0°F (4.4K)
tOPMaximum (Top) Operating Pressure setpointStandard: 10 psig to 150 psig
R-410A 10psig to 300 psig
R-744 10 psig to 500 psig
150 psig
tSTemperature Setpoint-50°F (-45°C) to 100°F (38°C)35.0°F (4.4K)
HAOHigh Alarm Offset1°F (1K) to 10°F (6K)5.0°F
LAOLow Alarm Offset1°F (1K) to 10°F (6K)3.0°F
tAdTemp Alarm Delay1 min to 180 min90 min
AdrAddress, Mod Bus Communications1 to 2471
UntUnits for temperature displayFAH or CELFAH
PrOProportional0 to 2553
intIntegral0 to 2555
dErDerivative0 to 2553
CLAManually Clear Alarms
FACReturn Controller to Factory Default Settings
SOFManually Enter System Off Mode
POSManually Adjust Valve Position0 to 100%
rELManually Control Relay

Abbreviations - Alphabetical Listing

AbbreviationNameTypeDescription
AdFAir DifferentialSetpointNumber of degrees air temp must be above room temp setpoint (tS) to return system to refrigeration mode
AdrModbus AddressSetpointController's address for communications
ALSAlarm StatusVariablePressing ENTER from ALS will show active alarm list; scroll through list using up or down arrow.
ASARoom/Air Sensor AlarmAlarmAlarm occurs when the room temperature sensor input is open or shorted
biBipolarSetpointOption under (Ub) Motor Type when using a CUS (custom) valve
Cd2CDS 2-7 ValveSetpointOption under EDt valve selection for pressure regulating valves
Cd9CDS 9 ValveSetpointOption under EDt valve selection for pressure regulating valves
CELCelsiusSetpointOption for temperature units
CLAClear Alarms ManuallyManualAllows user to manually clear alarms
COrCompressor RelayVariablesCurrent state of liquid line solenoid/compressor relay
CrLCarel ValveSetpointOption under EDt (Expansion Device Type) when SH (Superheat) is selected
CtLControl TypeSetpointSelect the type of control: SH (Electronic Expansion Valve), SHt (Electronic Expansion Valve with Thermostat) EPR (Electronic Pressure Regulating Valve), HGB (Electronic Hot Gas Bypass Valve),
CUSCustomSetpointUsed for Custom defrost schedule or Custom valve option
d1Defrost #1SetpointStart time of Defrost #1 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d2Defrost #2SetpointStart time of Defrost #2 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d3Defrost #3SetpointStart time of Defrost #3 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d4Defrost #4SetpointStart time of Defrost #4 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d5Defrost #5SetpointStart time of Defrost #5 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d6Defrost #6SetpointStart time of Defrost #6 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d7Defrost #7SetpointStart time of Defrost #7 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d8Defrost #8SetpointStart time of Defrost #8 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d9Defrost #9SetpointStart time of Defrost #9 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d10Defrost #10SetpointStart time of Defrost #10 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d11Defrost #11SetpointStart time of Defrost #11 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d12Defrost #12SetpointStart time of Defrost #12 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
dErDerivativeSetpointShould not be adjusted unless instructed by KE2 Therm technical support
dFtDefrost TimeSetpointMaximum time system is allowed in defrost
diSDisabledSetpointChoice under Start time when setting CUS (custom) dPd (defrosts per day)
dPdDefrost Per DaySetpointNumber of defrosts per day 0-12, CUS (custom)
ds1Danfoss KVS 15 ValveSetpointOption under EDt (valve selection) for pressure regulating valves
ds4Danfoss KVS 42 ValveSetpointOption under EDt (valve selection) for pressure regulating valves
EdtExpansion Device TypeSetpointValve Selection
EPrElectronic Pressure RegulatingSetpointType of control option under CtL (control type)
ES1ESR 12 ValveSetpointOption under EDt valve selection for pressure regulating valves
ES2ESR 20 ValveSetpointOption under EDt valve selection for pressure regulating valves
ESOExternal System OffSetpointWhen 3rd party signal present valve closes
FAHFahrenheitSetpointDefault for all temperatures displayed
FACFactory DefaultManualManual option to return controller to Factory Default settings
HAOHigh Alarm OffsetSetpointNumber of degrees above the Temperature Setpoint (tS) for a High Temp Alarm (HtA) condition.
HGbHot Gas Bypass ValveSetpointOption under CtL (Control Type)
HPAHigh Pressure AlarmAlarmOccurs when the temperature reading is above the Pressure setpoint + High Alarm Offset setpoint for the amount of time in setpoint High Low Alarm Delay.; High Temperature or pressure alarm is cleared and disabled while in defrost.
HSKE2-HSV ValveSetpointElectronic expansion valve option under EDt (valve selection)
HSHHigh Superheat AlarmAlarmOccurs when superheat is 2 or more degrees above set point and valve is 100% open for 90 minutes; Clears when superheat is within 2 degrees of setpoint
HtAHigh Temperature AlarmAlarmOccurs when the temperature reading is above the Temperature set point + Temperature differential set point + High Alarm Offset set point for the amount of time in set point High & Low Alarm Delay; High Temperature or pressure alarm is cleared and disabled while in defrost
inLInlet TemperatureVariableTemperature measured at the evaporator inlet. Only if SH and tt are selected as the input
inPInput TypeSetpointSelect type of control: EPR & HGb - PrS (pressure) or tPr (temp); EEV - Pt (pressure/temp)or tt (temp/temp)
intIntegralSetpointA coefficient to the valve control algorithm that increases valve responsiveness
iSAInlet Sensor AlarmAlarmValve closes and turns system off.
LAOLow Alarm OffsetSetpointNumber of degrees below the Temperature Setpoint (tS) for a Low Temp Alarm (LtA) condition.
LPALow Pressure AlarmAlarmPressure is below Low Pressure Cutout (LPC) after 3 consecutive attempts to start the system
LPCLow Pressure Cut OutSetpointPressure at which controller de-energizes the Compressor/Liquid Line Solenoid relay (COr)

Visuals: Diagrams show various control types including Superheat and Temperature w. Air Defrost, Superheat Only, Hot Gas Bypass: Temperature Control, Hot Gas Bypass: Pressure for Capacity Control, Electronic Evaporator Pressure Regulator: Discharge or Return Air Temperature, and Electronic Evaporator Pressure Regulator: Pressure Control. These diagrams illustrate wiring connections and system configurations.

Visuals: Diagrams show Multi-Evaporator Setups with Master and Slave controllers configured for Superheat & Temperature (SHt) and Superheat (SH). Also shows a Subcool control setup. These diagrams illustrate controller interconnections and system flow.

Visuals: Wiring Diagram shows overall connections including Air Temp Sensor, Suction Sensor, Suction Pressure Transducer, EEV, Transformer, Relay, LLS/Compressor Contactor, and Modbus. Dimensions in inches are provided for the controller unit. An Alternate Wiring Method is also shown.

Custom Defrost Setup

The following steps guide the setup of the KE2 Temp's custom defrost feature. Note: The KE2 Temp + Valve Control does not have an on-board battery backup. If power is lost, the defrost schedule may be offset by the duration of the power outage.

Abbreviations: CUS = custom, d1 = custom defrost 1, diS = disabled, dPd = defrosts per day, tS = temperature setpoint, tOd = time of day.

  1. STEP 1: Press and hold the ENTER button; 'tS' is displayed on the LEDs.
  2. STEP 2: Press the ↑ arrow until 'dPd' is displayed, then press ENTER. '6' (default) will be displayed.
  3. STEP 3: Press the ↑ arrow until 'CUS' is displayed. Press and hold the ENTER button for 3 seconds until 'dPd' is displayed.
  4. STEP 4: Press the ↑ arrow until 'tOd' (time of day) is displayed, then press ENTER. Use the ↑ and ↓ arrows to set the time. Note: Time is displayed in military format (24-hr clock). The first 2 digits are the hour; minutes are after the decimal. The time is set to the nearest 10 minutes (e.g., 8:10 am is 8.1, 4:32 p.m. is 16.3). After setting the time, press and hold ENTER for 3 seconds until 'tOd' is displayed.
  5. STEP 5: Press the ↑ arrow to display Defrost 1 ('d1'). To set the first defrost, press ENTER. 'diS' (disabled) will be displayed. Use the ↓ arrow to set the defrost time (on the hour). Once the correct time is displayed, press and hold ENTER until 'd1' is displayed.
  6. STEP 6: Repeat steps as necessary for d2 to d12.
  7. STEP 7: Press the BACK button to save settings and return to the main screen (room temp will be displayed).

CONTROL TYPE: Superheat and Temperature w. Air Defrost

Diagrams illustrate the step-by-step configuration for this control type, showing connections for Control Type, Superheat & Temperature, Input, Pressure/Temperature, and wiring for the LLS/Comp. Contactor Relay. Communication via Modbus to a Building Management System (BMS) or KE2-EM is also described.

CONTROL TYPE: Superheat Only

Diagrams illustrate the step-by-step configuration for this control type, showing connections for Control Type, Superheat, Input, Pressure/Temperature. It notes that the KE2 Temp + Valve should be supplied with a signal from a 3rd party to close the valve when function is not desired. Communication via Modbus is also described.

CONTROL TYPE: Hot Gas Bypass: Temperature Control

Diagrams illustrate the step-by-step configuration for this control type, showing connections for Control Type, Hot Gas Bypass, Input, and Temperature. It notes that the KE2 Temp + Valve should be supplied with a signal from a 3rd party to close the valve when function is not desired. Communication via Modbus is also described.

CONTROL TYPE: Hot Gas Bypass: Pressure for Capacity Control

Diagrams illustrate the step-by-step configuration for this control type, showing connections for Control Type, Hot Gas Bypass, Input, and Pressure. It notes that the KE2 Temp + Valve should be supplied with a signal from a 3rd party to close the valve when function is not desired. Communication via Modbus is also described.

CONTROL TYPE: Electronic Evaporator Pressure Regulator: Discharge or Return Air Temperature

Diagrams illustrate the step-by-step configuration for this control type for CASES and WALK-INS, showing connections for Control Type, Evaporator Pressure Regulating, Input, and Temperature. It notes that the KE2 Temp + Valve should be supplied with a signal from a 3rd party to close the valve when function is not desired. Communication via Modbus is also described.

CONTROL TYPE: Electronic Evaporator Pressure Regulator: Pressure Control

Diagrams illustrate the step-by-step configuration for this control type, showing connections for Control Type, Evaporator Pressure Regulating, Input, and Pressure. It notes that the KE2 Temp + Valve should be supplied with a signal from a 3rd party to close the valve when function is not desired. Communication via Modbus is also described.

MULTI-EVAPORATOR SETUP

Master: Controller 1 - Superheat & Temperature (SHt)

Diagram shows a Master controller (SHt) with connections for Control Type, Superheat & Temperature, Pressure Transducer, Suction Temperature, Air Temperature, and Return Air Temperature. It also shows Slave controllers (SH) for Evaporator 2 and Evaporator 3, with their respective connections. Wiring for LLS (Liquid Line Solenoid) or COMP CONTACTOR is also depicted.

Control Type: Subcool

Diagram shows the Subcool control setup with connections for Control Type, Pressure Transducer, Suction Temperature, Liquid Leaving Temp, and Warm Liquid/Subcooled Liquid flow through a Subcooling Heat Exchanger. Wiring for LLS and EEV is also shown. A note indicates that shorting the suction temperature sensor input will cause the controller to go to System Off mode (SOF) and close the LLS and EEV.

Wiring Diagram

The wiring diagram provides a comprehensive overview of the controller's connections. It includes:

  • Sensors: Air Temp Sensor, Leaving Liquid Temp (Subcooling Control), Suction Sensor, Suction Pressure Transducer.
  • Controller Terminals: Ribbon Cable connection, PWR CB, ModBus terminals (CN2, CN7, CN3), EEV connection, Transformer, Relay terminals (COM, NC, NO, L2, L1), LLS (Liquid Line Solenoid) or COMPRESSOR CONTACTOR connection.
  • Dimensions: Top View and End View dimensions (in inches) of the controller unit are provided.
  • Alternate Wiring Method: An alternative wiring configuration is shown for EEV, LLS Power Supply, and COMP Neutral.
  • Power Supply: 120 (208-240)/1/60 CONTROLLER POWER SUPPLY is indicated.
Models: PN21301 KE2 Temp Valve Control, PN21301, KE2 Temp Valve Control, Temp Valve Control, Valve Control

File Info : application/pdf, 23 Pages, 7.59MB

PDF preview unavailable. Download the PDF instead.

KE2-Temp-Plus-Valve-Control-Quick-Start-Guide-en

References

Adobe PDF Library 17.0 Adobe InDesign 18.1 (Macintosh)

Related Documents

Preview KE2 Therm Door Switch Installation and Configuration Guide
A comprehensive guide to installing and configuring the KE2 Therm Door Switch for enhanced energy efficiency and temperature stability in refrigeration systems. Covers setup for various KE2 controllers, including Ethernet enabled and non-Ethernet enabled models.
Preview KE2 Temp+Air Defrost Controller - Product Information and Specifications
Detailed product information for the KE2 Temp+Air Defrost controller by KE2 Therm Solutions, covering features, applications, navigation, specifications, and connectivity options for refrigeration systems.
Preview KE2 Temp + Air Defrost (pn 20611) Installation Manual
Installation manual for the KE2 Temp + Air Defrost controller (pn 20611) by KE2 Therm Solutions. Covers wiring, mounting, programming, and remote access for medium temperature applications.
Preview KE2 Temp + Air Defrost Controller Quick Start Guide
A concise guide to installing and operating the KE2 Temp + Air Defrost controller for medium temperature applications with air defrost. Includes kit contents, setup instructions, controller navigation, setpoints, and wiring diagrams.
Preview KE2 Low Temp+Defrost Controller: Condensed Quick Start Guide
A quick start guide for the KE2 Low Temp+Defrost controller (pn 20903) from KE2 Therm Solutions, covering parts, installation, navigation, menu access, wiring, and sensor placement for refrigeration systems.
Preview KE2 Evap-RE2 Contactor Panel Installation and Operation Guide
Comprehensive guide for the KE2 Evap-RE2 Contactor Panel, detailing installation, setup, operation, and troubleshooting for optimal refrigeration system efficiency.
Preview KE2 Temp + Air Defrost Condensed Quick Start Guide
A quick start guide for the KE2 Temp + Air Defrost controller, detailing its features, installation, and basic setpoints for medium temperature applications with air defrost.
Preview KE2 EdgeManager: Advanced Refrigeration Monitoring and Control
The KE2 EdgeManager by KE2 Therm Solutions provides advanced communication for monitoring and controlling up to 35 KE2 Therm controllers and KE2 Wireless Sensors. Features include real-time data tracking, local data access, remote monitoring, and email alarm notifications for various refrigeration applications.