Mitsubishi Electric P-Series Submittal Data
PKA-A24KA7 & PUZ-A24NHA7
24,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM
Job Information
Job Name: [Not Specified]
Purchaser: [Not Specified]
Submitted To: [Not Specified]
Submitted By: [Not Specified]
System Designation: [Not Specified]
Engineer: [Not Specified]
Application: [Not Specified]
For: Reference, Approval, Construction [Checkboxes not selected]
Location: [Not Specified]
Schedule No.: [Not Specified]
Unit Information
Indoor Unit: PKA-A24KA7
Outdoor Unit: PUZ-A24NHA7
Unit Option: Standard Model, Seacoast (BS) Model
Accessories: Controls (Wireless Controller MHK1, Advanced Wired Controller PAR-32MAA / PAR-33MAA, Simple Wired Controller PAC-YT53CRAU, Wireless Remote Controller PAR-FL32MA, Thermostat Interface PAC-US444CN, M-NET Adapter PAC-SF83MA-E), External Heater Adaptor (PAC-SE59RA-E), Wind Guards (Front PFR-24-30, Rear PRE-24-30, Side PSD-24-30).
Note: Mitsubishi Electric (MESCA) supports the use of only MESCA supplied and approved Snow Guard / Wind Deflectors / Windscreens and accessories for proper functioning of the unit(s). Use of non-MESCA supported Snow Guard / Wind Deflectors / Windscreens and accessories will affect warranty coverage.
Electrical Requirements
Voltage: 208/230V, 1-Phase, 60 Hz
Parameter | Indoor | Outdoor | MOCP (Outdoor) |
---|---|---|---|
Minimum Circuit Ampacity (MCA) | 1 AMP | 19 AMP | 25 AMP |
Breaker Size | [Not Applicable] | [Not Applicable] | 26 AMP |
*All electrical work shall comply with National (CEC) and local codes and regulations.
Specifications
Parameter | Indoor Unit | Outdoor Unit |
---|---|---|
Fan Motor (ECM) F.L.A. | 0.36 | 0.4 |
Fan Motor Output | 56 W | 86 W |
SHF / Moisture Removal | 0.77 / 5.0 pt./h | [Not Specified] |
Field Drainpipe Size O.D. | 5/8 in. (16 mm) | [Not Specified] |
Compressor | [Not Applicable] | DC INVERTER-driven Twin Rotary |
Airflow Rate (Low-Mid-Hi) CFM | DRY: 635-705-775 COOLING WET: 570-635-700 |
DRY: 1,940 |
Sound Pressure Level
Location | Condition | Sound Pressure Level (dB(A)) |
---|---|---|
Indoor | Low | 39 |
Mid | 42 | |
Hi | 45 | |
Outdoor | Cooling | 47 |
Heating | 48 |
Rated Conditions (Capacity / Input)
Condition | Capacity (Btu/h) | Input (W) |
---|---|---|
Cooling | 24,000 | 1,960 |
Heating at 47° F | 26,000 | 1,750 |
Heating at 17° F | 15,700 | 1,750 |
* Rating Conditions per AHRI Standard:
Cooling: Indoor 80°F (27°C)DB / 67°F (19°C)WB; Outdoor 95°F (35°C)DB / 75°F (24°C)WB
Heating at 47°F: Indoor 70°F (21°C)DB/60°F (16°C)WB; Outdoor 47°F (8°C)DB / 43°F (6°C)WB
Heating at 17°F: Indoor 70°F (21°C)DB / 60°F (16°C)WB; Outdoor 17°F (-8°C)DB / 15°F (-9°C)WB
Capacity Range
Condition | Capacity Range (Btu/h) |
---|---|
Cooling | 10,000 - 24,000 |
Heating at 47° F | 9,000 - 28,000 |
Operating Range
Condition | Temperature Range |
---|---|
Cooling | 0°F** (-18°C) to 115°F (46°C) DB |
Heating | -4°F (-20°C) to 70°F (21°C) DB |
**Windscreens required for cooling operation below 23°F (-5°C)
AHRI Efficiency Ratings
Rating | Value |
---|---|
EER | 12.2 |
SEER | 21.4 |
HSPF | 11.0/8.2 |
COP at 47° F | 4.35 |
COP at 17° F | 2.62 |
Dimensions
Indoor Unit (PKA-A24KA7)
External Dimensions (H x W x D): 14 3/8 x 46 1/16 x 11 5/8 in. (365 x 1170 x 295 mm)
Net Weight: 46 lbs. (21 kg)
Outdoor Unit (PUZ-A24NHA7)
External Dimensions (H x W x D): 37-1/8 x 37-13/32 x 13 + 1-3/16 in. (943 x 950 x 330 + 30 mm)
Net Weight: 153 lbs. (69 kg)
External Finish
Indoor: White Munsell No. 1.0Y 9.2/0.2
Outdoor: Ivory Munsell No. 3Y 7.8 / 1.1
Refrigerant
Type: R410A
Charge: 7 lbs., 11 oz. (3.5kg)
Piping (Flared):
- Liquid (High Pressure): 3/8 in. (9.52 mm)
- Gas (Low Pressure): 5/8 in. (15.88 mm)
Maximum Total Refrigerant Pipe Length: 165 ft. (50 m)
Maximum Vertical Separation: 100 ft. (30 m)
Diagrams and Visuals
The document includes detailed dimension drawings for both the indoor unit (PKA-A24KA7) and the outdoor unit (PUZ-A24NHA7). These diagrams show the placement of pipes, electrical connections, mounting holes, and overall unit measurements in inches and millimeters.
Indoor Unit (PKA-A24KA7) Diagram Features:
- Shows front, top, left, right, and underside views.
- Highlights knockout holes for piping (left, right, lower).
- Indicates filter hook, operation lamp, DEFROST/STAND BY lamp, receiver, terminal blocks (outdoor unit, power supply, MA-remote controller), emergency operation switch.
- Details piping connections for liquid and gas pipes, including diameter and flared connection size.
- Shows vane (auto) and louver (manual) positions.
Outdoor Unit (PUZ-A24NHA7) Diagram Features:
- Shows front, side, and top views.
- Illustrates installation feet, handles for moving, air intake (rear, side), and air discharge.
- Details foundation bolt locations (M10 / 3/8).
- Shows terminal connections for power supply and indoor/outdoor wiring, including ground wire.
- Indicates service panel and front/rear piping covers.
Certifications
The document displays logos for AHRI Certified, ETL Listed, and ENERGY STAR Participant, indicating compliance with relevant industry standards and energy efficiency programs.
Specifications are subject to change without notice.
© 2016 Mitsubishi Electric Sales Canada Inc.