PKA-AK24NL & PUZ-AH24NL
24,000 BTU/H WALL-MOUNTED INDOOR UNIT / 24,000 BTU/H HEAT PUMP OUTDOOR UNIT
Indoor Unit Features
- Auto fan speed mode: Automatic adjustment of fan speed.
- Ideal PKA spaces: Suitable for server rooms, daycare centers, classrooms, churches, and small offices.
- Light commercial: Units with this icon are suitable for light commercial applications such as small offices, restaurants, and retail.
- Multiple control options: Includes the comfort app for remote access, third-party interfaces, and both wired and wireless controllers.
- Simple installation.
- Single-zone: One outdoor unit connects to one indoor unit to control comfort in a single space.
- Sleek, compact design.
- Up and down swing-mode: The indoor unit can move air up and down throughout the room using horizontal vanes, similar to an oscillating fan.
- Vane settings: Allows for air flow direction control.
Outdoor Unit Features
- Blue Fin Coating: An anti-corrosion treatment applied to the aluminum fins of the heat exchanger to protect against corrosion from salt, sulfur, and other airborne contaminants, especially in coastal and industrial areas.
- Continuous operation: Supports 24-hour continuous operation in cooling mode.
- Fast restart.
- High pressure protection.
- High pressure/temperature protection.
- INVERTER-driven compressor: Generates precise capacity to maintain a set temperature point.
- Low ambient cooling: Provides 100% capacity down to 0°F.
- Pre-charged refrigerant: Units from 12k-30k BTU/h come pre-charged for ease of installation. 24k-30k BTU/h units are pre-charged for a maximum line length of 225 feet. 12k-18k BTU/h units are pre-charged for up to 165 feet of line length. Units 36,000 BTU/h and above may require additional refrigerant charges.
- Seacoast protection: Standard in 2022 production, featuring a robust anti-corrosion system with phosphate and acrylic-enamel coated external panels, epoxy resin-coated fan motor support, separator assembly valve beds, and Blue Fin treatment for the heat exchanger coil. These components are rated for 2,000 hours of durability under ASTM B117 testing standards for longevity in corrosive coastal environments.
- Superior energy and operational efficiency.
Specifications
Feature | Specification | Unit |
---|---|---|
Cooling at 95°F | ||
Maximum Capacity | 24,500 | Btu/h |
Rated Capacity | 24,000 | Btu/h |
Minimum Capacity | 10,100 | Btu/h |
Maximum Power Input | 2,050 | W |
Rated Power Input | 1,990 | W |
Moisture Removal | 6.2 | Pints/h |
Sensible Heat Factor | 0.72 | - |
Power Factor [208V/230V] | 97/97 | % |
Heating at 47°F | ||
Maximum Capacity | 31,000 | Btu/h |
Rated Capacity | 28,000 | Btu/h |
Minimum Capacity | 8,300 | Btu/h |
Maximum Power Input | 2,770 | W |
Rated Power Input | 2,414 | W |
Power Factor [208V/230V] | 98/98 | % |
Heating at 17°F | ||
Maximum Capacity | 15,300 | Btu/h |
Rated Capacity | 15,300 | Btu/h |
Maximum Power Input | 1,600 | W |
Rated Power Input | 1,600 | W |
Heating at 5°F | ||
Maximum Capacity | 11,600 | Btu/h |
Maximum Power Input | 1,620 | W |
Heating at -4°F | ||
Maximum Capacity | 10,400 | Btu/h |
Efficiency | ||
SEER2 | 21.1 | - |
EER21 | 12 | - |
HSPF2 [IV] | 9.2 | - |
COP at 47°F | 3.4 | - |
COP at 17°F at Maximum Capacity | 2.8 | - |
COP at 5°F at Maximum Capacity | 2 | - |
COP at -4°F at Maximum Capacity | 1.96 | - |
ENERGY STAR® Certified | Yes | - |
Electrical | ||
Voltage, Phase, Frequency | 208/230V, 1Ø, 60Hz | - |
Guaranteed Voltage Range | 198 - 264 | V AC |
Voltage: Indoor - Outdoor, S1-S2 | 208/230 | V AC |
Voltage: Indoor - Outdoor, S2-S3 | 12-24 | V DC |
Short-circuit Current Rating [SCCR] | 5 | kA |
Recommended Fuse/Breaker Size (Outdoor) | 25 | A |
Recommended Wire Size [Indoor - Outdoor] | 14 | AWG |
Indoor Unit | ||
Fan Motor Output | 69 | W |
Airflow Rate at Cooling, Dry | 635, 705, 775 | CFM |
Airflow Rate at Heating, Dry | 635, 705, 775 | CFM |
Sound Pressure Level [Cooling] | 39, 42, 45 | dB(A) |
Sound Pressure Level [Heating] | 39, 42, 45 | dB(A) |
External Finish Color | 0.7PB 9.2/0.4 | - |
Unit Dimensions (W x D x H) | 46-1/16 x 11-5/8 x 14-3/8 | inch [mm x mm x mm] |
[1,170 x 295 x 365] | ||
Package Dimensions (W x D x H) | 51-3/16 x 14-3/16 x 18-9/16 | inch [mm x mm x mm] |
[1,300 x 360 x 470] | ||
Unit Weight | 46 [21] | lbs [kg] |
Package Weight | 51 [23] | lbs [kg] |
Fan Motor Type | DC Motor | - |
IDU Operating Temp. Range | ||
Cooling Intake Air Temp [Maximum / Minimum] | 90°F DB, 73°F WB / 66°F WB | °FDB, °FWB / °FWB |
Heating Intake Air Temp [Maximum / Minimum] | 82°F / 50°F | °FDB |
Outdoor Unit | ||
MCA | 22 | A |
MOCP | 37 | A |
Fan Motor Output | 74 | W |
Airflow Rate Cooling | 1,940 | CFM |
Airflow Rate Heating | 1,940 | CFM |
Defrost Method | Reverse Cycle | - |
Coating on Heat Exchanger (Bluefin, Sea Coast) | Yes, Yes | - |
Sound Pressure Level, Cooling | 49 | dB(A) |
Sound Pressure Level, Heating | 52 | dB(A) |
Compressor Type | Twin Rotary | - |
Compressor Model | SRB172FQHMC-L1 | - |
Compressor Oil [Type // Charge] | RM68EH // 23 oz | Type // oz |
External Finish Color | Munsell No.3Y 7.8/1.1 | - |
Base Pan Heater | Optional | - |
Unit Dimensions (W x D x H) | 37-13/32 x 14 x 37-1/8 | inch [mm x mm x mm] |
[950 x 355 x 943] | ||
Package Dimensions (W x D x H) | 41-15/16 x 17-3/4 x 42-1/2 | inch [mm x mm x mm] |
[1,065 x 450 x 1,079] | ||
Unit Weight | 155 [70] | lbs [kg] |
Package Weight | 179 [81] | lbs [kg] |
ODU Operating Temp. Range | ||
Cooling Intake Maximum Air Temp [Maximum / Minimum] | 115°F DB / 23°F DB | °FDB |
Heating Air Temp [Maximum / Minimum] | 70°F DB, 59°F WB / -4°F DB, -4°F WB | °FDB, °FWB / °FDB, °FWB |
Heating Thermal Lock-out / Re-start Temperatures | -13°F / -4°F | °FDB |
Refrigerant Type | R454B | - |
Pre-Charged Refrigerant Amount | 7 lbs, 11 oz | lbs, oz |
Maximum Pre-Charged Piping Length | 165 [50] | ft [m] |
Additional Refrigerant Charge Per Additional Piping Length | 0 | oz/ft |
Gas Pipe Size O.D. [Flared] | 5/8 | inch [mm] |
[15.88] | ||
Liquid Pipe Size O.D. [Flared] | 3/8 | inch [mm] |
[9.52] | ||
Piping | ||
Maximum Piping Length | 165 [50] | ft [m] |
Maximum Height Difference | 100 [30] | ft [m] |
Maximum Number of Bends | 15 | - |
Indoor Unit Accessories
- Condensate Pumps: Blue Diamond Advanced Mini Condensate Pump w Reservoir Sensor (208-230V recommended) (X87-721), Blue Diamond MaxiBlue Advanced Mini Condensate Pump w Reservoir Sensor (110V up to 48000 BTUH recommended) (X87-711), Blue Diamond MegaBlue Advanced Condensate Pump w Reservoir Sensor (X87-835), Blue Diamond Sensor Extension Cable 15 Ft (C13-103).
- Drain Pan Level SensorControl: SS610E.
- Condensate Pumps (Refco): Refco Condensate Pump 100-240 VAC (GOBI-II), Refco Condensate Pump 100-240 VAC up to 120000 BTUH (COMBI).
- Condensate Pump (Sauermann): Sauermann Condensate Pump (SI30-230).
- Remote Sensors: Flush Mount Remote Temperature Sensor for SEZ SLZ SVZ and all P-Series models (PAC-USSEN002-FM-1), Wall Mount Remote Temperature Sensor (PAC-SE41TS-E), Wireless temperature and humidity sensor for the Comfort app (PAC-USWHS003-TH-1).
- Wireless Remote Controller Accessories: Lockdown Bracket for Wireless Handheld Remote Controllers (RCMKP1CB), RedLINK Wireless Remote Controller (MHK2), Universal Wireless MA Handheld Remote Controller (PAR-FL32MA-E), Universal Wireless Receiver for PAR-FL32MA-E (PAR-FA32MA-W).
- Lineset Insulation: 10 x 3/8 x 10 x 5/8 Lineset Twin-Tube Insulation (MPLS385812T-10), 100 x 3/8 x 100 x 5/8 Lineset Twin-Tube Insulation (MPLS385812T-100), 15 x 3/8 x 15 x 5/8 Lineset Twin-Tube Insulation (MPLS385812T-15), 30 x 3/8 x 30 x 5/8 Lineset Twin-Tube Insulation (MPLS385812T-30), 50 x 3/8 x 50 x 5/8 Lineset Twin-Tube Insulation (MPLS385812T-50), 65 x 3/8 x 65 x 5/8 Lineset Twin-Tube Insulation (MPLS385812T-65).
- Wired Remote Controllers: Deluxe Wired MA Remote Controller 1 (PAR-42MAAUB), Simple Direct Wired Remote Controller (PAC-SDW01RC-1), Simple MA Remote Controller 1 (PAC-YT53CRAU-J), Touch MA Wired Remote Controller 1 (PAR-CT01MAU-SB).
- Airzone Controllers: Airzone Wired Blueface Controller Black (AZZBSBLUEZEROCN), Airzone Wired Blueface Controller White (AZZBSBLUEZEROCB), Airzone Wireless Lite Controller Black (AZZBSLITERN), Airzone Wireless Lite Controller White (AZZBSLITERB), Airzone Wireless Think Controller Black (AZZBSTHINKRN), Airzone Wireless Think Controller White (AZZBSTHINKRB).
- Control Interface Accessories: IT Extender for kumo station (PAC-WHS01IE-E), kumo station for the Comfort app (PAC-WHS01HC-E), Procon BACnet and Modbus Interface (PAC-UKPRC001-CN-1), Thermostat Interface for 3rd Party Thermostats (PAC-US445CN-1), Wireless Interface Adapter for the Comfort app (PAC-USWHS002-WF-2).
- Mini-Split Wire: 14 Gauge 4 wire Armored MiniSplit Cable 250 ft roll (SW144-250), 14 Gauge 4 wire Armored MiniSplit Cable 50 ft roll (SW144-50).
- Disconnect Switch: 30A 600V UL fits 2 X 4 utility box - Black (TAZ-MS303), 30A 600V UL fits 2 X 4 utility box - White (TAZ-MS303W).
- Power Supplies & Auxiliary Components: 3-Pin Wiring Harness (PAC-715AD), 5-Pin Wiring Harness (PAC-725AD), Backup Heat Relay Kit Adapter for CN24 or CN152 Connector (CN24RELAY-KIT-CM3).
- Drain Hose: Flexible Mini-Split Drain Hose (DRX-16).
Outdoor Unit Accessories
- Mini-Split Wire: 14 Gauge 4 wire Armored MiniSplit Cable 250 ft roll (SW144-250), 14 Gauge 4 wire Armored MiniSplit Cable 50 ft roll (SW144-50), 14 Gauge 4 wire MiniSplit Cable 250 ft roll (S144-250), 14 Gauge 4 wire MiniSplit Cable 50 ft roll (S144-50).
- Stand: 18 Single Fan Stand (QSMS1801M), 24 Single Fan Stand (QSMS2401M), Condenser Wall Bracket (QSWB2000M-1), Condenser Wall Bracket - Stainless Steel Finish (QSWBSS), Outdoor Unit 3-14 inch Mounting Base Pair - Plastic (DSD-400P), Outdoor Unit Stand 12 High (QSMS1201M).
- Power Supplies & Auxiliary Components: 3-Pin Wiring Harness (PAC-715AD), 5-Pin Wiring Harness (PAC-725AD).
- Wind Baffle: Front Wind Baffle (WB-PA5), Rear Wind Baffle (WB-RE5), Side Advanced Wind Baffle (WB-SD5).
- M-NET Converter: M-Net Interface for P-Series (PAC-SJ95MA-E).
- Air Outlet Guide: Air Outlet Guide 1 Piece (PAC-SG59SG-E).
- Mounting Pad: Condensing Unit Mounting Pad 24 x 42 x 3 (ULTRILITE2).
- Hail Guards: Hail Guard (HG-A6).
- Drain Socket: Drain Socket (PAC-SG61DS-E).
- Control/Service Tool: ControlService Tool (PAC-SK52ST), M- & P-Series Maintenance Tool Cable Set (M21EC0397).
- Optional Defrost Heater: Optional Defrost Heater (PAC-SK62BH-E).
- Centralized Drain Pan: Centralized Drain Pan (PAC-SG64DP-E).
- Snow/Rain Diverter: SnowRain Diverter (SRD-4).
Dimensions and Installation Notes
Indoor Unit Dimensions (PKA-AK24NL)
The PKA-AK24NL indoor unit dimensions are detailed with front, side, top, and under views. Key dimensions include:
- Overall Width: 1170 mm (46-1/16 inches)
- Overall Depth: 295 mm (11-5/8 inches)
- Overall Height: 365 mm (14-3/8 inches)
- Air Outlet Height: Minimum 220 mm (8-21/32 inches)
- Mounting Board Dimensions: Approximately 339 mm (13-11/32 inches) width.
- Piping Knock-out Holes: Provided for left, right, rear, and lower piping connections.
- Terminal Blocks: Located for outdoor unit connection, power supply (optional), and MA-remote controller.
- Emergency Operation Switch: Included.
Detailed measurements for clearances, screw holes, and piping entry points are provided in the diagrams.
Outdoor Unit Dimensions (PUZ-AH24NL)
The PUZ-AH24NL outdoor unit dimensions and installation clearances are specified. Key aspects include:
- Unit Dimensions (W x D x H): 950 mm x 355 mm x 943 mm (37-13/32 x 14 x 37-1/8 inches).
- Package Dimensions (W x D x H): 1,065 mm x 450 mm x 1,079 mm (41-15/16 x 17-3/4 x 42-1/2 inches).
- Required Space: Minimum clearances are indicated for service access (e.g., 500 mm / 19-11/16 inches).
- Foundation Bolts: M10 (3/8 inch) foundation bolts are recommended for securing the unit.
- Piping-Wiring Directions: Connections can be made from four directions: front, right, rear, and below.
- Piping Knock-out Hole Details: Specific dimensions for piping and wiring holes are provided for front, right, rear, and bottom connections.
- Air Intake/Discharge: Locations for air intake (side and rear) and air discharge are shown.
- Terminal Connections: Power supply wiring and indoor/outdoor wiring terminals are accessible.
The diagrams illustrate the unit's footprint, service access requirements, and connection points.