Durastar HVAC Product Specifications

Durastar Wall Mounted Indoor Units (IDU)

This section details specifications for various Durastar Wall Mounted Indoor Units (IDUs).

DRAW09F1B - 9,000 BTU/H

Project Name
Location
Architect
Engineer
Contractor
Reference
Submitted By
Date

Indoor Unit (IDU)

Model: DRAW09F1B

Product Features:

Specifications

Cooling Capacity (BTU/hr) 9000
Heating Capacity (BTU/hr) 10000
Voltage/Phase/Frequency 208-230V, 1 Phase, 60 Hz
Voltage Range 187-253V
Indoor Unit Air Flow (CFM) Low: 153, Medium: 194, High: 291
Moisture Removal (Pints/day) 37.20
Drain Port O.D. Ø5/8" (Ø16mm)
Recommended Breaker (Amps) 15
Sound Pressure (dB(A)) Low: 23.5, Medium: 35, High: 40
Refrigerant R410A

Line Set Requirements

Connection Type Flare
Liquid Ø1/4" (Ø6.35mm)
Gas Ø3/8" (Ø9.52mm)

Dimensions and Weight

Unit Dimensions Width: 31 9/16", Depth: 7 7/8", Height: 11 5/8"
Carton Dimensions Width: 34 7/16", Depth: 11 1/4", Height: 14 15/16"
Net Weight 19 lbs.
Gross Weight 24.3 lbs.

Diagrams (Textual Description)

Unit Dimensions Diagram: Shows the width, depth, and height of the indoor unit. Front view displays width and height, side view displays depth and height.

Mounting Plate Dimensions Diagram: Illustrates the dimensions of the mounting plate, including hole placements for wall mounting. Shows width, height, and various hole dimensions and distances.

Clearance Distances Diagram: Indicates required clearances around the unit for proper operation. Specifies minimum distances for top, sides, and rear.

DRAW12F1B - 12,000 BTU/H

Project Name
Location
Architect
Engineer
Contractor
Reference
Submitted By
Date

Indoor Unit (IDU)

Model: DRAW12F1B

Product Features:

Specifications

Cooling Capacity (BTU/hr) 12000
Heating Capacity (BTU/hr) 12000
Voltage/Phase/Frequency 208-230V, 1 Phase, 60 Hz
Voltage Range 187-253V
Indoor Unit Air Flow (CFM) Low: 153, Medium: 194, High: 291
Moisture Removal (Pints/day) 78.24
Drain Port O.D. Ø5/8" (Ø16mm)
Recommended Breaker (Amps) 15
Sound Pressure (dB(A)) Low: 25, Medium: 36, High: 42
Refrigerant R410A

Line Set Requirements

Connection Type Flare
Liquid Ø1/4" (Ø6.35mm)
Gas Ø1/2" (Ø12.7mm)

Dimensions and Weight

Unit Dimensions Width: 31 9/16", Depth: 7 7/8", Height: 11 5/8"
Carton Dimensions Width: 34 7/16", Depth: 11 1/4", Height: 14 15/16"
Net Weight 18.7 lbs.
Gross Weight 24.3 lbs.

Diagrams (Textual Description)

Unit Dimensions Diagram: Shows the width, depth, and height of the indoor unit. Front view displays width and height, side view displays depth and height.

Mounting Plate Dimensions Diagram: Illustrates the dimensions of the mounting plate, including hole placements for wall mounting. Shows width, height, and various hole dimensions and distances.

Clearance Distances Diagram: Indicates required clearances around the unit for proper operation. Specifies minimum distances for top, sides, and rear.

DRAW18F1B - 18,000 BTU/H

Project Name
Location
Architect
Engineer
Contractor
Reference
Submitted By
Date

Indoor Unit (IDU)

Model: DRAW18F1B

Product Features:

Specifications

Cooling Capacity (BTU/hr) 18000
Heating Capacity (BTU/hr) 18000
Voltage/Phase/Frequency 208-230V, 1 Phase, 60 Hz
Voltage Range 187-253V
Indoor Unit Air Flow (CFM) Low: 382, Medium: 459, High: 531
Moisture Removal (Pints/day) 87.36
Drain Port O.D. Ø5/8" (Ø16mm)
Recommended Breaker (Amps) 15
Sound Pressure (dB(A)) Low: 25, Medium: 41, High: 46
Refrigerant R410A

Line Set Requirements

Connection Type Flare
Liquid Ø1/4" (Ø6.35mm)
Gas Ø1/2" (Ø12.7mm)

Dimensions and Weight

Unit Dimensions Width: 42 5/8", Depth: 9 5/8", Height: 13 1/4"
Carton Dimensions Width: 45 1/2", Depth: 12 3/8", Height: 16 5/16"
Net Weight 29.5 lbs.
Gross Weight 37.5 lbs.

Diagrams (Textual Description)

Unit Dimensions Diagram: Shows the width, depth, and height of the indoor unit. Front view displays width and height, side view displays depth and height.

Mounting Plate Dimensions Diagram: Illustrates the dimensions of the mounting plate, including hole placements for wall mounting. Shows width, height, and various hole dimensions and distances.

Clearance Distances Diagram: Indicates required clearances around the unit for proper operation. Specifies minimum distances for top, sides, and rear.

DRAW24F1B - 24,000 BTU/H

Project Name
Location
Architect
Engineer
Contractor
Reference
Submitted By
Date

Indoor Unit (IDU)

Model: DRAW24F1B

Product Features:

Specifications

Cooling Capacity (BTU/hr) 24000
Heating Capacity (BTU/hr) 26000
Voltage/Phase/Frequency 208-230V, 1 Phase, 60 Hz
Voltage Range 187-253V
Indoor Unit Air Flow (CFM) Low: 382, Medium: 459, High: 601
Moisture Removal (Pints/day) 131.52
Drain Port O.D. Ø5/8" (Ø16mm)
Recommended Breaker (Amps) 15
Sound Pressure (dB(A)) Low: 28, Medium: 40, High: 48
Refrigerant R410A

Line Set Requirements

Connection Type Flare
Liquid Ø3/8" (Ø9.52mm)
Gas Ø5/8" (Ø16mm)

Dimensions and Weight

Unit Dimensions Width: 42 5/8", Depth: 9 3/16", Height: 13 1/4"
Carton Dimensions Width: 45 1/2", Depth: 12 3/8", Height: 16 5/16"
Net Weight 30 lbs.
Gross Weight 39.1 lbs.

Diagrams (Textual Description)

Unit Dimensions Diagram: Shows the width, depth, and height of the indoor unit. Front view displays width and height, side view displays depth and height.

Mounting Plate Dimensions Diagram: Illustrates the dimensions of the mounting plate, including hole placements for wall mounting. Shows width, height, and various hole dimensions and distances.

Clearance Distances Diagram: Indicates required clearances around the unit for proper operation. Specifies minimum distances for top, sides, and rear.

Durastar Sirius Heat Multi-Zone Heat Pump

DRA5H55M1A - 55,000 BTU/H

Project Name
Location
Architect
Engineer
Contractor
Reference
Submitted By
Date

Outdoor Unit (ODU)

Model: DRA5H55M1A

Product Features:

System Data

Refrigerant Type R-410A
Refrigerant Charge (oz.) 162.26
Design Pressure (PSIG) 550/340
Outdoor Coil Coating Golden Fin Coating

Capacities

DUCTLESS MIXED DUCTED
Cooling (BTU/hr) Rated¹ 55000 55000 55000
Cooling (BTU/hr) at 5°F³ 43410 40660 37910
Cooling (BTU/hr) Minimum 11600 15500 19400
Cooling (BTU/hr) Maximum 56900 57000 57100
Heating (BTU/hr) Rated² 55000 55000 55000
Heating (BTU/hr) at 5°F⁴ 45500 45750 46000
Heating (BTU/hr) Minimum 33000 48500 15500
Heating (BTU/hr) Maximum 63000 62300 61600
Nominal ODU Capacity⁵ 55000

Efficiency Data

DUCTLESS MIXED DUCTED
SEER2 20.00 19.40 18.80
EER2 10.50 10.50 10.50
HSPF2 9.50 9.40 9.30
SEER 19.00 19.00 19.00
EER 10.50 10.50 10.50
HSPF 10.80 10.90 11.00
COP at 47°F 3.20 3.20 3.20
COP at 5°F 1.80 1.85 1.90

Line Set Requirements

Connection Type Flare
Liquid 5 x 1/4" (Ø6.35mm)
Gas 3 x 3/8" (Ø9.52mm)
2 x 1/2" (Ø12.7mm)
Refrigeration Adaptors Included 3 x 3/8"--1/2"
2 x 1/2"--3/8"
2 x 1/4"--3/8"
2 x 1/2"--5/8"
Minimum Indoor Units Connected 2
Pre-Charge Length 123'
Maximum Length (combined IDUs) 263'
Maximum Length (per IDU) 115'
Minimum Length (per IDU) 10'
Max. Height Differential between IDU and ODU 49'
Max. Height Differential between IDUS 33'
Additional Refrigerant for Ø1/4" Liquid Pipe (oz./ft) 0.161
Additional Refrigerant for Ø3/8" Liquid Pipe (oz/ft) 0.322

Electrical Data

DUCTLESS DUCTED
Voltage/Phase/Frequency 208-230V, 1 Phase, 60 Hz
Voltage Range 187-253V
Recommended Breaker (Amps) 60
Minimum Circuit Ampacity (Amps) 40
Communication Wire Size 14*4 AWG Stranded
Rated Current - Cooling (Amps)¹ 23.5 23.5
Rated Current – Heating (Amps)² 22.5 22.5

Outdoor Unit Data

Unit Dimensions Width: 37-1/2", Depth: 16-5/16", Height: 52-1/2"
Carton Dimensions Width: 43-1/8", Depth: 19-1/2", Height: 58-1/4"
Net Weight 233 lbs.
Gross Weight 266 lbs.
Cooling Operating Temperature 5°F - 122°F
Heating Operating Temperature -22°F - 75°F
Airflow (CFM) 4500
Sound Pressure (dB(A)) Low: 61, Medium: 750, Medium: 800, High: 850, High: 900
Fan Speed (r/min) Low: 750, Medium: 800, Medium: 850, High: 900
Fan Motor Current Type DC

Compressor

Type DC Inverter Twin Cylinder Rotary
Oil Type VG74
Oil Charge (oz.) 49 (1460mL)

Diagrams (Textual Description)

Clearances Diagram: Shows required clearances around the outdoor unit. Specifies distances for left, right, front, and above the unit.

Dimensions Diagram: Illustrates the overall dimensions of the outdoor unit, including width, depth, and height. Also shows carton dimensions.

Note: Illustrations are for explanatory purposes; actual shape may vary slightly.

PDF preview unavailable. Download the PDF instead.

durastar-dra5l55w09121824-specification-sheet PyPDF2

Related Documents

Preview Durastar Split-Style Air Conditioner Installation Manuals
Comprehensive installation guides from Durastar for split-style air conditioning systems, covering indoor units (DRAW series) and multi-zone outdoor units (DRA series). Includes detailed steps, safety precautions, troubleshooting, and wiring diagrams.
Preview Durastar Wall Mounted Mini-Split Air Conditioner Owner's Manual
Comprehensive owner's manual for Durastar wall-mounted split-style air conditioners, covering operation, safety, maintenance, troubleshooting, and warranty for models DRAW06F1B, DRAW09F1B, DRAW12F1B, DRAW18F1B, DRAW24F1B, DRAW33F1B.
Preview Durastar Wall Mounted Indoor Unit Installation Manual
Comprehensive installation manual for Durastar split-style air conditioners, covering model numbers DRAW06F1B, DRAW09F1B, DRAW12F1B, DRAW18F1B, and DRAW24F1B. Includes safety precautions, parts identification, step-by-step installation procedures, troubleshooting, and wiring diagrams.
Preview Durastar Wall Mounted Indoor Unit Split-Style Air Conditioner Owner's Manual
Comprehensive owner's manual for Durastar wall-mounted split-style air conditioners (models DRAW06F1B, DRAW09F1B, DRAW12F1B, DRAW18F1B, DRAW24F1B), covering installation, operation, maintenance, troubleshooting, and warranty information.
Preview Durastar Split-Style Air Conditioner Installation Manual
Comprehensive installation manual for Durastar Wall Mounted Indoor Unit Split-Style Air Conditioners, covering safety, setup, operation, and troubleshooting for models DRAW06F1B, DRAW09F1B, DRAW12F1B, DRAW18F1B, and DRAW24F1B.
Preview Durastar DRA1U24S1A 24,000 BTU/H Single Zone Outdoor Unit Specifications
Detailed specifications and submittal information for the Durastar DRA1U24S1A, a 24,000 BTU/H single zone outdoor unit, including capacities, electrical data, dimensions, operating conditions, and system requirements.
Preview Durastar 14 SEER Series Heat Pump Installation Manual
Comprehensive installation guide for Durastar 14 SEER Series Heat Pumps (1.5-5 Tons) featuring R-410A refrigerant. Covers safety, system sizing, installation procedures, troubleshooting, and maintenance for qualified HVAC professionals.
Preview Durastar Multi-Zone Heat Pump Outdoor Unit Installation Manual
Comprehensive installation manual for Durastar Multi-Zone Heat Pump Outdoor Units, covering safety precautions, installation steps, troubleshooting, and specifications for models like DRA3U18M2A, DRA3H18M2A, and others.