24,000 BTU/H SINGLE ZONE OUTDOOR UNIT

SUBMITTAL COVER SHEET

Model: DRA1U24S1A

Project Information

Project Name: [Not Specified]

Location: [Not Specified]

Architect: [Not Specified]

Engineer: [Not Specified]

Contractor: [Not Specified]

Reference: [Not Specified]

Submitted By: [Not Specified]

Date: [Not Specified]

Unit Overview

Single Zone Outdoor Unit (ODU): DRA1U24S1A

(Image of the Durastar DRA1U24S1A outdoor unit is present on the cover sheet.)

Capacities

Rated1MinimumMaximum
Cooling Capacity (BTU/hr)24000685024500
Heating Capacity (BTU/hr)25000720027500

1 Rated cooling capacity measured at 95 °F.

2 Rated heating capacity measured at 47 °F.

Outdoor Temperature Operation

Cooling-13 °F - 122 °F (-25°C - 50° C)
Heating-13 °F - 86 °F (-25°C - 30° C)

Electrical Data

Voltage/Phase/Frequency208-230V, 1 Phase, 60 Hz
Voltage Range187-253V
Recommended Breaker (Amps)25
Minimum Circuit Ampacity (Amps)18
Minimum Wire Size16 AWG
Rated Current - Cooling (Amps)18.4
Rated Current - Heating (Amps)210.1

Product Features

  • Variable Speed Inverter Compressor
  • Auto Restart
  • Base Pan Heater

Certifications

AHRI CERTIFIED® Unitary Small HP, AHRI Standard 210/240. Certification applies only when the complete system is listed with AHRI.

ETL US LISTED

System Data

Refrigerant TypeR-410A
Refrigerant Charge (oz.)82.9
Oil TypeVG74
Oil Charge (oz.)22.7 (670 ml)
Design Pressure (PSIG)550/340

Line Set Requirements

Connection TypeFlare
LiquidØ3/8" (Ø9.52mm)
GasØ5/8" (Ø15.9mm)
Pre-Charge Length25'
Maximum Length164'
Minimum Length (One Indoor Unit)10'
Max. Height Differential Between Indoor and Outdoor Unit82'
Additional Refrigerant (oz/ft)0.32

Outdoor Unit Fan Data

Airflow (CFM)2235
Sound Pressure (dB(A))61
TypeDC
RLA (A)0.6

Outdoor Unit Dimensions

Unit Dimensions

Width37 1/4"
Depth16 1/8"
Height31 7/8"

Carton Dimensions

Width42 15/16"
Depth19 11/16"
Height34 1/8"

Weights

Net Weight141.1 lbs.
Gross Weight152.1 lbs.

Dimensional Diagram Description

The document includes diagrams illustrating the dimensions and clearances for the Durastar DRA1U24S1A outdoor unit. Key dimensions and required clearances are provided:

Unit Dimensions and Clearances:

  • Overall Unit Width: 37 1/4 inches (946 mm)
  • Overall Unit Depth: 16 1/8 inches (410 mm)
  • Overall Unit Height: 31 7/8 inches (810 mm)
  • Clearance to the left of the unit: 12 inches (305 mm)
  • Clearance to the right of the unit: 24 inches (610 mm)
  • Clearance in front of the unit: 79 inches (2007 mm)
  • Clearance above the unit: 24 inches (610 mm)
  • Clearance from the back wall: 12 inches (305 mm)
  • The diagram also shows a bottom view with dimensions: 26 1/2 inches (673 mm) width and 15 7/8 inches (403 mm) depth.

Note: Illustrations in this document are for explanatory purposes. The actual shape of the mini-split equipment may vary slightly.

PDF preview unavailable. Download the PDF instead.

4U72836713 S 2103 Adobe PDF Library 16.0

Related Documents

Preview Durastar Split-Style Air Conditioner Installation Manuals
Comprehensive installation guides from Durastar for split-style air conditioning systems, covering indoor units (DRAW series) and multi-zone outdoor units (DRA series). Includes detailed steps, safety precautions, troubleshooting, and wiring diagrams.
Preview Durastar Wall Mounted IDU and Sirius Heat Multi-Zone Heat Pump Specifications
This document provides specifications and dimensions for Durastar Wall Mounted Indoor Units (IDUs) and Sirius Heat Multi-Zone Heat Pumps. It includes details on cooling and heating capacity, electrical requirements, line set requirements, dimensions, weight, and product features for models DRAW09F1B, DRAW12F1B, DRAW18F1B, DRAW24F1B, and DRA5H55M1A.
Preview Durastar Wall Mounted Mini-Split Air Conditioner Owner's Manual
Comprehensive owner's manual for Durastar wall-mounted split-style air conditioners, covering operation, safety, maintenance, troubleshooting, and warranty for models DRAW06F1B, DRAW09F1B, DRAW12F1B, DRAW18F1B, DRAW24F1B, DRAW33F1B.
Preview Durastar Split-Style Air Conditioner Installation Manual for Outdoor Units
This installation manual provides comprehensive guidance for Durastar single-zone outdoor split-style air conditioners, including models DRA1U09S1B, DRA1U12S1B, DRA1U18S1B, and DRA1U24S1B. It covers safety precautions, installation steps, wiring, refrigerant piping, system evacuation, and troubleshooting.
Preview Durastar DRAS12F1B Floor Mounted Indoor Unit Owner's Manual
Comprehensive owner's manual for the Durastar DRAS12F1B split-style air conditioner, covering installation, operation, maintenance, troubleshooting, and warranty information.
Preview Durastar DRAS12F1B Floor Mounted Mini-Split Air Conditioner Installation Manual
This installation manual provides detailed instructions for the Durastar DRAS12F1B floor-mounted split-style air conditioner. It covers safety precautions, installation steps, parts identification, troubleshooting, and wiring diagrams.
Preview Durastar Floor Console Indoor Unit Installation Manual | DRAS09F2A, DRAS12F2A, DRAS16F2A, R-454B
Comprehensive installation manual for Durastar Floor Console Indoor Units (DRAS09F2A, DRAS12F2A, DRAS16F2A) using R-454B refrigerant. Covers safety precautions, installation steps, troubleshooting, wiring diagrams, and error codes.
Preview Durastar Warranty Information: Two-Year Parts and Labor Coverage
Comprehensive details on the Durastar two-year parts and labor warranty, outlining what is covered, common exclusions, and the process for obtaining warranty service for Durastar products.