Durastar Split-Style Air Conditioner Installation Manual

Brand: Durastar

Models Covered: DRAW06F1B, DRAW09F1B, DRAW12F1B, DRAW18F1B, DRAW24F1B

Introduction

This manual provides essential information for the installation of Durastar Wall Mounted Indoor Unit Split-Style Air Conditioners. Before contacting customer service, users are advised to:

Warnings and Symbols

The following symbols are used in this manual:

Important Safety Precautions

Improper handling can cause serious damage or injury. Please read the following safety information carefully.

Operation, Cleaning, and Maintenance Safety Precautions

Electrical Safety

Installation Safety

Additional Precautions

Operating Temperatures

The air conditioner is designed for specific indoor and outdoor temperatures. Exceeding these ranges may activate safety features to protect the unit.

Temperature RangesCOOL modeHEAT modeDRY mode
Indoor Air Temperature60°F - 90°F (16°C - 32°C)32°F - 86°F (0°C - 30°C)50°F - 90°F (10°C - 32°C)
Outdoor Air Temperature5°F - 122°F (-15°C - 50°C)-13°F - 75°F* (-25°C - 24°C)*32°F - 122°F (0°C - 50°C)

* The minimum operating temperature in heat mode depends on the outdoor unit; low ambient models operate down to -22°F (-30°C).

To optimize performance:

NOTE: The outdoor unit has a base pan heater, allowing operation down to -22°F (-30°C). It is recommended to keep the unit plugged in at all times when outdoor temperatures are 32°F (0°C) or below for smooth performance.

NOTE: Maintain room relative humidity below 80%. To prevent condensation, set the vertical airflow louver to its maximum angle and the fan to HIGH.

Accessories

Included Installation Accessories

AccessoryQuantityImage DescriptionAccessoryQuantityImage Description
Manual1-2Booklet iconRemote Control1Remote control icon
Mounting Plate1Mounting plate diagramBattery2Battery icon
Wall Anchor5-8 (depending on model)Wall anchor diagramRemote Control Holder1Remote control holder icon
Mounting Plate Screw5-8 (depending on model)Screw diagramRemote Control Holder Mounting Screw2Screw diagram
Copper Nut2Nut diagramInstallation Template1Template diagram
Drain Joint1Drain joint diagramCarbon Filter2Filter diagram
Drain Joint Seal1Seal diagram

Field Supplied Installation Accessories

The following are required and must be purchased separately:

Tools Needed

The following tools are required for installation:

Parts Identification

NOTE: Installation must comply with local and national standards. Installation may vary slightly by area.

The indoor and outdoor units consist of the following parts:

NOTE: Illustrations are for explanatory purposes; actual equipment may vary slightly.

Installation Overview - Indoor Unit

The installation process involves the following key steps:

  1. Select Installation Location: Ensure proper clearances (e.g., 6" from ceiling, 4 3/4" from walls).
  2. Determine Wall Hole Position: Mark the location for piping.
  3. Attach Mounting Plate: Secure the mounting plate to the wall, ensuring it is level.
  4. Drill Wall Hole: Drill a hole through the wall for connective piping, angled slightly downwards for drainage.
  5. Connect Piping: Connect refrigerant and drain pipes.
  6. Connect Wiring: Connect the signal cable and power supply.
  7. Prepare Drain Pipe: Ensure proper drainage and insulation.
  8. Wrap Piping and Cable: Bundle and insulate the pipes and cable.
  9. Mount Indoor Unit: Securely attach the indoor unit to the mounting plate.

Indoor Unit Installation

STEP 1: SELECT INSTALLATION LOCATION

Choose an appropriate location based on the following standards:

DO NOT install the unit in the following locations:

Ensure proper clearances from walls and ceiling:

NOTE: If no pre-existing refrigerant piping is present, allow ample room for the wall hole to accommodate the signal cable and refrigerant piping connecting the indoor and outdoor units. Piping typically exits the right side of the indoor unit but can be routed left or right.

STEP 2: ATTACH MOUNTING PLATE TO WALL

  1. Remove the screw securing the mounting plate to the back of the indoor unit.
  2. Secure the mounting plate to the wall using the provided anchors and screws. Ensure the plate is flat and level.

Diagram Description: Shows correct orientation of mounting plate with checkmarks and incorrect orientations with crosses.

STEP 3: DRILL WALL HOLE FOR CONNECTIVE PIPING

  1. Determine the wall hole location based on the mounting plate dimensions, using the installation template or the provided illustrations.
  2. Drill the wall hole using a 2 1/2" (65mm) core drill for pipes up to 5/8" (16mm) or a 3 1/2" (90mm) drill for pipes 5/8" (16mm) or larger. The hole should be drilled at a slight downward angle (3/16" – 1/4" or 5mm – 7mm) from indoor to outdoor for proper water drainage.
  3. Insert the protective wall hole sleeve into the drilled hole to protect pipes and cables from sharp edges and seal the opening. Attach the wall hole cover to the sleeve on the outside wall, ensuring it is flush.

Diagram Description: Shows dimensions for wall hole placement for Model 9K and 12K, and Model 18K and 24K.

STEP 4: PREPARE REFRIGERANT PIPING

  1. Choose the side (left or right) for piping exit based on the wall hole position relative to the mounting plate.
  2. If the wall hole is behind the unit, do not remove the knock-out panel. If the hole is to the side, remove the plastic knock-out panel from that side to create an exit slot for the piping. Use pliers if the panel is difficult to remove; grooves are provided for easier cutting. The size of the removed piece depends on the piping diameter.
  3. If pre-existing piping is in the wall, proceed to Step 5. If not, connect the indoor unit's refrigerant piping to the connective piping for the outdoor unit, referring to the outdoor unit's installation manual for details.
  4. Position the piping to align with the wall hole. Piping can exit from the left-hand side, right-hand side, left rear, or right rear.

WARNING: Be extremely careful not to dent or damage the piping while bending them away from the unit. Any dents will affect performance.

STEP 5: CONNECT THE DRAIN PIPE

The drain pipe is typically attached to the left-hand side of the unit (facing the back) but can be moved to the right. Attach the drain pipe on the same side as the refrigerant piping exit for proper drainage. Attach any extension pipe (5/8" inner diameter) securely to the existing drain pipe.

Diagram Description: Shows correct drain pipe routing (no kinks/dents) and incorrect routing (kinks create water traps, placing end in water prevents drainage).

WARNING: Plug the unused drain hole with the provided rubber plug to prevent unwanted leaks.

STEP 6: CONNECT SIGNAL CABLE

BEFORE PERFORMING ANY ELECTRICAL WORK, READ THESE REGULATIONS:

  1. All wiring must comply with local/national electrical codes and be installed by a licensed electrician.
  2. Electrical connections must follow the Electrical Connection Diagram on the unit panels.
  3. If there is a serious safety issue with the power supply, stop work and contact a licensed electrician.
  4. Power voltage should be within 90-110% of rated voltage. Insufficient supply can cause malfunction, shock, or fire.
  5. For fixed wiring, install a surge protector and main power switch rated 1.5 times the unit's maximum current.
  6. For fixed wiring, a switch or circuit breaker with at least 1/8" (3mm) contact separation must be used.
  7. Connect the unit only to an individual branch circuit outlet; do not connect other appliances to it.
  8. Properly ground the air conditioner.
  9. Ensure all wires are firmly connected. Loose wiring can cause overheating, malfunction, or fire.
  10. Keep wires away from refrigerant tubing, the compressor, or moving parts.
  11. If the unit has an auxiliary electric heater, install it at least 40" away from combustible materials.
  12. To avoid electric shock, wait at least 10 minutes after turning off power before touching electrical components.

WARNING: Before performing any electrical or wiring work, turn off the main power to the system.

The signal cable enables communication between indoor and outdoor units. Choose the correct cable size and run a continuous length, avoiding splices.

CABLE SIZING

The required power supply cable, fuse, and switch size depend on the unit's maximum current, indicated on the nameplate.

Wiring the Indoor Unit

  1. Open the front panel of the indoor unit.
  2. Using a screwdriver, open the wire box cover on the right side to access the terminal block.
  3. Unscrew the cable clamp below the terminal block and set it aside.
  4. Remove the plastic panel on the bottom left-hand side (facing the back of the unit).
  5. Feed the signal wire through this slot from the back to the front.
  6. Connect a spade u-lug onto the end of each wire.
  7. Facing the front, connect the wires to the terminal block according to the indoor unit's wiring diagram, screwing each lug firmly.
  8. After ensuring all connections are secure, use the cable clamp to fasten the signal cable to the unit, screwing it down tightly.
  9. Replace the wire cover on the front and the plastic panel on the back.

NOTE: All wiring must strictly adhere to the wiring diagram located on the back of the indoor unit's front panel.

STEP 7: PREPARE REFRIGERANT PIPING

  1. If pre-existing refrigerant piping is embedded in the wall, skip to Step 9 and begin outdoor unit installation, referring to the outdoor unit's manual for Refrigerant Piping Connections.
  2. If no pre-existing piping, connect the indoor unit's refrigerant piping to the connective piping that will join the indoor and outdoor units, again referring to the outdoor unit's manual.

STEP 8: WRAPPING THE CABLES

Bundle the drain pipe, refrigerant pipes, and signal cable together before passing them through the wall hole to save space, protect them, and insulate them.

  1. Bundle the components as shown in the diagram.
  2. Using adhesive vinyl tape, attach the drain pipe to the underside of the refrigerant pipes.
  3. Using insulation tape, wrap the signal wire, refrigerant pipes, and drain pipe tightly together. Double-check that all items are bundled.

NOTE: The drain pipe MUST be at the bottom of the bundle to prevent drain pan overflow, which could lead to fire or water damage.

NOTE: DO NOT intertwine the signal cable with other wires while bundling.

NOTE: Keep the ends of the piping unwrapped for leak testing at the end of the installation process.

STEP 9: MOUNT INDOOR UNIT

If new connective piping was installed to the outdoor unit:

  1. If refrigerant piping is already through the wall, proceed to step 4.
  2. Double-check that the ends of the refrigerant pipes are sealed to prevent dirt or foreign materials from entering.
  3. Slowly pass the wrapped bundle of refrigerant pipes, drain pipe, and signal wire through the wall hole.
  4. Hook the top of the indoor unit onto the upper hook of the mounting plate.
  5. Check that the unit is firmly mounted by applying slight pressure to the sides; it should not jiggle or shift.
  6. Using even pressure, push down on the bottom half of the unit until it snaps onto the lower hooks of the mounting plate.
  7. Re-check that the unit is firmly mounted.

If refrigerant piping is already embedded in the wall:

  1. Hook the top of the indoor unit onto the upper hook of the mounting plate.
  2. Use a bracket or wedge to prop up the unit, providing room to connect the refrigerant piping, signal cable, and drain pipe.
  3. Connect the drain pipe and refrigerant piping (refer to the outdoor unit's installation manual).
  4. Keep the pipe connection point exposed for the leak test (refer to the outdoor unit's installation manual).
  5. After the leak test, wrap the connection point with insulation tape.
  6. Remove the bracket or wedge.
  7. Push down on the bottom half of the unit until it snaps onto the lower hooks of the mounting plate.

NOTE: We recommend a second person assist with supporting the indoor unit while connections are made.

NOTE: The indoor unit is adjustable. The mounting plate hooks are smaller than the unit's back holes, allowing left/right adjustment of approximately 1 1/4"–2" (30–50mm) depending on the model.

Diagram Description: Shows adjustment range for left/right positioning.

Troubleshooting

Safety Precautions

If any of the following occur, turn off the unit immediately:

DO NOT attempt to fix these issues yourself! Contact an authorized service provider immediately!

Common Issues

IssuePossible Causes
Unit does not turn on when pressing ON/OFF buttonThe unit has a 3-minute protection feature to prevent overloading. It cannot be restarted within three minutes of being turned off.
The unit changes from COOL/HEAT mode to FAN modeThe unit may change settings to prevent frost formation. It will resume the selected mode once the temperature increases. The set temperature has been reached, causing the compressor to turn off. The unit will resume operation when temperature fluctuates.
The indoor unit emits white mistIn humid regions, a large temperature difference between room air and conditioned air can cause white mist.
Both indoor and outdoor units emit white mistWhite mist may be emitted when the unit restarts in HEAT mode after defrosting, due to moisture generated during the defrosting process.
The indoor unit makes noisesA rushing air sound may occur when the louver resets its position. A squeaking sound may occur in HEAT mode due to expansion and contraction of plastic parts.

Additional Troubleshooting

IssuePossible Causes
Both indoor and outdoor units make noisesLow hissing sound during operation is normal, caused by refrigerant gas flow. Low hissing when starting, stopping, or defrosting is also normal, caused by refrigerant gas changes. Squeaking sounds are normal due to temperature changes affecting plastic and metal parts.
The outdoor unit makes noisesThe unit makes different sounds based on its current operating mode.
Dust is emitted from either the indoor or outdoor unitDust may accumulate during extended periods of inactivity and be emitted when the unit is turned on. Covering the unit during long periods of inactivity can mitigate this.
The unit emits a bad odorThe unit may absorb environmental odors (e.g., from furniture, cooking, cigarettes). The unit's filters may have become moldy and require cleaning.
The fan of the outdoor unit does not operateFan speed is controlled during operation to optimize product performance.
Operation is erratic, unpredictable, or unit is unresponsiveInterference from cell phone towers or remote boosters may cause malfunction. Try disconnecting and reconnecting power, or pressing the ON/OFF button on the remote control to restart.

NOTE: If problems persist, contact a local dealer or customer service center with a detailed description of the malfunction and the model number.

Troubleshooting - Performance and Operation

ProblemPossible CausesSolution
Poor Cooling PerformanceTemperature setting higher than ambient room temperature.Lower the temperature setting.
Dirty heat exchanger (indoor or outdoor unit).Clean the affected heat exchanger.
Dirty air filter.Remove and clean the filter according to instructions.
Blocked air inlet or outlet.Turn off the unit, remove obstruction, and turn it back on.
Doors and windows are open.Ensure all doors and windows are closed while operating.
Low refrigerant due to leak or long-term use.Check for leaks, re-seal if necessary, and top off refrigerant.
Poor Heating PerformanceExcessive heat generated by sunlight.Block sunlight in the installation area. Close windows and curtains during periods of high heat or bright sunshine.
Too many heat sources in the room (people, computers, electronics, etc.).Reduce the number of heat sources.
Extremely low outdoor temperature.This model works down to -13°F, but heating performance is impacted below freezing.
Cold air entering through doors and windows.Ensure all doors and windows are closed during use.
Low refrigerant due to leak or long-term use.Check for leaks, re-seal if necessary, and top off refrigerant.
The unit starts and stops frequentlyToo much or too little refrigerant in the system.Check for leaks and recharge the system with refrigerant.
Incompressible gas or moisture has entered the system.Evacuate and recharge the system with refrigerant.
The compressor is broken.Replace the compressor.
Voltage is too high or too low.Install a manostat to regulate the voltage.

Troubleshooting - Unit Not Working / Indicator Lamps

ProblemPossible CausesSolution
The unit is not workingPower failure.Wait for power restoration.
Power is turned off.Turn on the power.
The fuse is burned out.Replace the fuse.
Remote control batteries are dead.Replace the batteries.
The Unit's 3-minute protection has been activated.Wait three minutes after restarting the unit.
Timer is activated.Turn timer off.
Indicator lamps continue flashing or error code appearsThe unit may stop operation or continue safely. If lamps flash or error codes appear, wait about 10 minutes; the problem may resolve itself. If not, disconnect and reconnect power, then turn the unit on. If the problem persists, disconnect power and contact your nearest customer service center.

NOTE: If problems persist after checks, turn off the unit immediately and contact an authorized service center.

Wiring Diagram

Wiring diagrams are provided for different model series:

Diagram Description: The diagrams illustrate the electrical connections between the indoor unit, outdoor unit, main board, and various sensors and control modules. Optional components are indicated by dotted lines.

Error and Operating Codes

The following table lists common operating codes and error codes displayed by the unit:

Running LampTimer LampDisplayInformation
----dFDefrost
----5CSelf clean
----CLFilter cleaning reminder (power on display for 15 seconds)
------Active clean (for some units)
----FPFilter replacement reminder (power on display for 15 seconds)
----FCFreeze protection heating 46°F/54°F (8°C/12°C)
----APForced cooling
----CPAP mode of WIFI connection
------Remote switched off
1 timeOFFEH00/EH0RIndoor unit EEPROM parameter error
2 timesOFFEL01Indoor/outdoor unit communication error
3 timesOFFEH02Zero-crossing signal detection error
4 timesOFFEH03The indoor fan speed is operating outside of the normal range
5 timesOFFEC51Outdoor unit EEPROM parameter error
5 timesOFFEC52Condenser coil temperature sensor T3 is in open circuit or has short circuited
5 timesOFFEC53Outdoor room temperature sensor T4 is in open circuit or has short circuited
5 timesOFFEC54Compressor discharge temperature sensor TP is in open circuit or has short circuited
5 timesOFFEC56Evaporator coil outlet temperature sensor T2B is in open circuit or has short circuited (for free-match indoor units)
6 timesOFFEH60Indoor room temperature sensor T1 is in open circuit or has short circuited
6 timesOFFEH61Evaporator coil middle temperature sensor T2 is in open circuit or has short circuited
12 timesOFFEC01The outdoor fan speed is operating outside of the normal range
9 timesOFFEH01bIndoor PCB/Display board communication error
8 timesOFFEL0CRefrigerant leakage detection
7 timesFLASHPC00IPM malfunction or IGBT over-strong current protection
2 timesFLASHPC01Over voltage or over low voltage protection
3 timesFLASHPC02Top temperature protection of compressor or High temperature protection of IPM module or High pressure protection
5 timesFLASHPC04Inverter compressor drive error
1 timeFLASHPC08Current overload protection
6 timesFLASHPC40Communication error between outdoor main chip and compressor driven chip
7 timesFLASHPC03Low pressure protection
1 timeON--Indoor units mode conflict (match with multi outdoor unit)

* Normal operating codes, not malfunctions.

PDF preview unavailable. Download the PDF instead.

durastar-draw24f1b-installation-sheet Adobe PDF Library 17.0

Related Documents

Preview Durastar Wall Mounted Mini-Split Air Conditioner Owner's Manual
Comprehensive owner's manual for Durastar wall-mounted split-style air conditioners, covering operation, safety, maintenance, troubleshooting, and warranty for models DRAW06F1B, DRAW09F1B, DRAW12F1B, DRAW18F1B, DRAW24F1B, DRAW33F1B.
Preview Durastar Wall Mounted Indoor Unit Installation Manual
Comprehensive installation manual for Durastar split-style air conditioners, covering model numbers DRAW06F1B, DRAW09F1B, DRAW12F1B, DRAW18F1B, and DRAW24F1B. Includes safety precautions, parts identification, step-by-step installation procedures, troubleshooting, and wiring diagrams.
Preview Durastar Split-Style Air Conditioner Installation Manuals
Comprehensive installation guides from Durastar for split-style air conditioning systems, covering indoor units (DRAW series) and multi-zone outdoor units (DRA series). Includes detailed steps, safety precautions, troubleshooting, and wiring diagrams.
Preview Durastar Wall Mounted Indoor Unit Split-Style Air Conditioner Owner's Manual
Comprehensive owner's manual for Durastar wall-mounted split-style air conditioners (models DRAW06F1B, DRAW09F1B, DRAW12F1B, DRAW18F1B, DRAW24F1B), covering installation, operation, maintenance, troubleshooting, and warranty information.
Preview Durastar Wall Mounted IDU and Sirius Heat Multi-Zone Heat Pump Specifications
This document provides specifications and dimensions for Durastar Wall Mounted Indoor Units (IDUs) and Sirius Heat Multi-Zone Heat Pumps. It includes details on cooling and heating capacity, electrical requirements, line set requirements, dimensions, weight, and product features for models DRAW09F1B, DRAW12F1B, DRAW18F1B, DRAW24F1B, and DRA5H55M1A.
Preview Durastar Floor Console Indoor Unit Installation Manual | DRAS09F2A, DRAS12F2A, DRAS16F2A, R-454B
Comprehensive installation manual for Durastar Floor Console Indoor Units (DRAS09F2A, DRAS12F2A, DRAS16F2A) using R-454B refrigerant. Covers safety precautions, installation steps, troubleshooting, wiring diagrams, and error codes.
Preview Durastar DRAS12F1B Floor Mounted Mini-Split Air Conditioner Installation Manual
This installation manual provides detailed instructions for the Durastar DRAS12F1B floor-mounted split-style air conditioner. It covers safety precautions, installation steps, parts identification, troubleshooting, and wiring diagrams.
Preview Durastar Wall Mounted Indoor Unit Installation Manual
Comprehensive installation manual for Durastar split-style air conditioners, covering safety precautions, installation steps, troubleshooting, and specifications for models DRAW06F2A through DRAW33F2A using R-454B refrigerant.